Back to the blog
Louis Meneteau

Louis Meneteau

CPO of Argile

200 articles published

Louis is CPO of Argile. An engineer by training, he spent four years in systems engineering, validating calculation software and designing the trials that test it, then three years in software product. He turns the installer's daily reality into product workflows: technical survey, sizing, quotes and subsidy files, with a hard requirement on the compliance of what comes out. His articles describe field gestures rather than principles, because he watches them on site before specifying them. When one entry flips a result, he says so and explains how to decide on the spot.

Argile is software for energy renovation companies and RGE-certified installers in France: AI-assisted building survey, equipment sizing to NF EN 12831-1, works plans and quotes with MaPrimeRénov' and CEE subsidies deducted.

Subjects covered

Technical site surveyQuotes and subsidy filesInstaller workflow

Their articles

ContractorsNovember 16, 2026
Over-insulating in retrofits: real gains and limits

Beyond a certain level, insulation still improves U-value, but with mechanically diminishing returns because U = 1/R, a relationship set out in NF EN ISO 6946 (calculation of thermal resistance and transmittance of building elements). With a 100 m² wall and 2,400 heating degree days, moving from R=6 to R=8 reduces heat losses by about 242 kWh/year, whereas from R=8 to R=10 the gain drops to 144 kWh/year, as shown by the Q=U×A×HDD×24/1000 calculation set out in the body. These gaps explain why payback periods lengthen and why, if thermal bridges, airtightness and vapour strategy do not follow, you shift the risk toward summer overheating and interstitial condensation rather than saving kWh.

6 min read

ContractorsNovember 16, 2026
3-Way Temperature Control Valve: Selection and Installation

To size a three-way temperature control valve without unstable control, start from the hydraulic relationship Q = Kvs × √ΔP (therefore Kvs = Q/√ΔP, with Q in m³/h and ΔP in bar), then check the authority a = ΔPvalve/(ΔPvalve + ΔPsystem), typically targeted between 0.3 and 0.7. These two values and formulas are those given in the body of the article. In practice, an oversized Kvs causes ΔPvalve to drop, the loop hunts in mid-season, and swapping ports A, B, AB is enough to make the heating curve inconsistent.

6 min read

ContractorsNovember 14, 2026
3-A Certification and Pumps: Useful Requirements for Buildings

The “3-A certificate” is a North American sanitary standard for food-processing equipment, and it is largely irrelevant on most HVAC and building plumbing jobs, where you will first be asked for the CE marking and an EU Declaration of Conformity. To keep a quote on track without debate, rely on a simple, site-checkable metric: the IP rating, as defined by IEC 60529, with at least IPX4 as soon as there is a risk of water splashing in a boiler room or basement. For domestic hot water, replace the 3-A requirement with suitability for contact with water intended for human consumption and archiving the documents in the as-built file (EU declaration, manual, nameplate, ACS if applicable).

6 min read

ContractorsNovember 13, 2026
Warm-edge glazing spacer: Psi calculation and impact on Uw

Under EN ISO 10077-1, switching from an aluminium spacer to a warm edge typically halves the edge Ψg from 0.08 to 0.04 W/m·K, which lowers the Uw of the complete joinery by about 0.11 W/m²·K on a 1.23 x 1.48 m window (from 1.32 to 1.21). This Ψg value is not a commercial option but an input used in the Uw = (Ag·Ug + Af·Uf + lg·Ψg)/(Ag+Af) formula from EN ISO 10077-1. In practice, by raising the surface temperature at the perimeter, warm edge shifts the dew point and limits misting and mould at the edge, provided the spacer reference and the selected Ψ are stated in the quotation.

6 min read

ContractorsNovember 13, 2026
Methane LHV values and conversions for your calculations

For your calculations, use a lower heating value (LHV) for pure methane (CH₄) of 9.94 kWh per Nm³ at 0 °C and 1.01325 bar, and 13.9 kWh per kg, values taken from reference thermochemical tables (NIST Chemistry WebBook) used in combustion calculations. These benchmarks apply only to pure methane: distributed natural gas is a mixture, and the bill is already converted into kWh using the delivery point conversion factor, which depends on the supply zone and the local higher heating value (HHV) applied by the distributor.

6 min read

ContractorsNovember 12, 2026
PCI accounting: converting fuels into kWh

To convert your purchases of heating oil, pellets, gas or propane into kWh in your accounting records, remember the simple rule: PCI kWh = quantity purchased × unit PCI, using typical values of 10.0 kWh/L for heating oil, 4.8 kWh/kg for wood pellets, 10.5 kWh/m³ for natural gas and 12.8 kWh/kg for propane, as shown in the conversion table in the article body. For gas, keep in mind that the bill is issued in kWh HHV using a coefficient specific to the delivery point (PCE), which explains the gaps with a “home-made” PCI calculation, and document on the quote or the re-invoicing appendix the PCI/HHV ratio used and your reference conditions (m³ vs Nm³, humidity, density) so it stands up to inspection.

6 min read

ContractorsNovember 10, 2026
Window condensation: identifying inside, outside, and glazing

On site, the first clue is where the moisture forms: outside, it is generally transient dew that disappears 30 to 120 minutes after sunrise, and therefore a normal effect of high-performance glazing, as noted in our section “Outside-side condensation: 30 to 120 minutes duration.” By contrast, persistent fogging between the panes indicates a “dead” insulating glass unit (failure of the spacer seal) and calls for glazing replacement, not a ventilation adjustment.

6 min read

ContractorsNovember 10, 2026
Stairwell insulation in condominiums: method

On site, classify the stairwell on the basis of measured facts, not intent: at least 24 hours of temperature logging during the heating season, as the foundation of the file, then lock in the “heated volume” or “unheated space” hypothesis on the quote and calculation note. This minimum logging period is the one used in the body of the page, in line with field diagnostic practice for substantiating evidence (time-stamped photos, sketches, readings). Then price first the separating wall between the dwelling and the stairwell and the entrance door air-tightness, where the temperature gradient and air leakage cause the real heat loss.

6 min read

ContractorsNovember 10, 2026
Cascade Control: Boiler Commissioning Settings

In a cascade, the basic settings that prevent short cycling are minimum run and stop times. For a gas condensing boiler, start with at least 3 to 5 minutes of run time and 3 to 10 minutes of stop time; these are commissioning values given in the body of the page. You then stabilize staging with a N+1 enable differential of +2 to +5 °C and a stage hysteresis of 1 to 3 °C, as shown in the tables in the text.

5 min read

ContractorsNovember 8, 2026
PV inverter sizing to choose and validate voltages

To select the inverter from an already-defined PV array, the key constraint is not kW but the DC voltage in cold weather. It must be calculated from the module’s STC Voc, corrected using its βVoc coefficient (%/°C) and the number of modules in series, then kept strictly below the inverter’s maximum allowable DC voltage. This method is defined by NF C 15-712-1 and IEC 62548, which also remind you to check Vmpp in hot weather within the MPPT window and to compare the Isc increased by the normative safety coefficient with the admissible input current. In practice, different orientations should be assigned to separate MPPTs, otherwise you lose yield and make compliance more difficult.

5 min read

ContractorsNovember 6, 2026
Exterior solar shading: how to choose fixed or movable by orientation

For a project that is genuinely aimed at summer comfort, a properly sized external shading system can bring the overall solar factor g_tot down to around 0.10 to 0.20, whereas an internal blind generally stays in the 0.35 to 0.60 range. These are the benchmarks used in the body text below, and they should be locked into the quotation for the glazing-plus-shading package in the deployed position. On east- and west-facing façades, a movable solution is usually the right choice to cope with low-angle sun, while already accounting for wind resistance, automatic shutdown and maintenance access at the selection stage.

6 min read

ContractorsNovember 5, 2026
Boiler-stove: telling a boiler from a boiler stove

When pricing, clearly distinguish a wood boiler (central heat generator) from a boiler stove or boiler insert, which remains a room heater and transfers only part of its output to the water. This is stated in black and white in the manual, the Declaration of Performance and the test reports, which specify the heat output to water to use for sizing the heating circuit and the buffer tank. Because the firebox and combustion don’t stop instantly, your quote must include the safety devices referenced in DTU 24.1 for the flue system and the manufacturer’s requirements for thermal safety discharge.

5 min read

ContractorsNovember 5, 2026
VMC anti-vibration mounts: choosing and buying the right model

To choose and buy a VMC anti-vibration mount without making a mistake, first size it based on the load per point, with a safety margin of 1.5 to 2 times the supported mass, then distribute the load over 4 supports as soon as the casing is long or asymmetrically loaded. As for stiffness, in practice allow 40 to 55 Shore A for light loads, and 60 to 70 Shore A if the allowable travel is limited, aiming for a service deflection midway through the stated travel. These values come from the body of the article, and they provide a numerical basis to compare quotes and troubleshoot before ordering, after ruling out impeller imbalance or duct contact.

6 min read

ContractorsNovember 4, 2026
Off-site boiler plant: how to choose a ready-to-connect module

An off-site, “ready-to-connect” boiler plant only cuts time on site if you set a clear redundancy threshold from the quotation stage, for example N+1 continuity in cascade, as noted in the “Power, cascade, redundancy” section of your article body. The module is delivered assembled, wired and tagged (generator, hydraulics, control panel, automation, safety devices), but the slab, service connections, flue system, power supply and connections to the primary network still remain your responsibility; otherwise, the schedule slips.

6 min read

ContractorsNovember 3, 2026
Buffer tank: preserving stratification at the connection

To preserve stratification in a buffer tank at the connection points, follow one simple site rule: supply at the top tapping and return at the bottom tapping, with a baffle or dip tube to break the jet and prevent mixing. For commissioning, verify that the temperature gradient holds with three temperature readings at top, middle, and bottom over a 20- to 30-minute log, as explained in the body of the article. This control method gives you a clear benchmark to push back with if the tank is being used as a hydraulic separator and ends up acting like a mixing vessel.

6 min read

ContractorsNovember 3, 2026
Pressure testing pipe networks: passing the test and producing the report

A pressure test only carries weight in a dispute through its dated and signed report, because whoever claims performance of an obligation must prove it (French Civil Code, art. 1353). Test values are taken from the reference document for each network and are not merged: 1.5 times the maximum operating pressure with a minimum of 6 bar for heating pipework (French professional rules of December 2021, §7.2), and 2 times the operating pressure with a minimum of 6 bar for underfloor heating loops (AQC CH-PC sheet). For domestic water, gas and buried networks, the value comes from the document covering the package and is copied as it stands into the report.

7 min read

ContractorsNovember 1, 2026
Insulating Lime-Hemp Render: dosage, passes, drying

The 2024 professional rules of Construire en Chanvre treat a lime-hemp render applied against a wall as a hempcrete lining: 20 mm minimum on an existing substrate, machine-sprayed below 12 cm, and at least 21 days of drying before any finish. The lime / hemp mix is that of the validated binder-aggregate pair, stated in the manufacturer’s certificate. The only figures the rules give are for the lime render that covers it: a scratch coat at 350 to 400 kg of lime per m³ of sand, a 48-hour wait, 20 to 25 mm in total.

7 min read

ContractorsOctober 28, 2026
Internal Basement Wall Waterproofing: Diagnosis and Solutions

On a below-ground wall, no coating or lining goes on until the source of the water has been identified: lateral penetration, rising damp or condensation. The French tanking standard, NF DTU 14.1, sets out three types of tanking, and the one applied from the inside, the waterproofing coating, does not withstand cracking of the substrate and still allows damp patches, according to the 2025 guidance sheet from the AQC. The relatively watertight structure, for its part, allows 0.5 l/m²/day of water through as an annual average.

7 min read

ContractorsOctober 27, 2026
Condensing wood boiler: checking that it condenses

A wood boiler only condenses if the return water stays below the dew point of the flue gases, which rises with fuel moisture and falls with excess air: that is measured on site, not read from a brochure. In Great Britain, the retained Ecodesign regulation requires a solid fuel boiler to reach a seasonal space heating efficiency of at least 75 % up to 20 kW and 77 % above, and does not require it to condense. In England and Wales, the Boiler Upgrade Scheme gives £5,000 towards a biomass boiler, but only for a rural property off the gas grid.

7 min read

ContractorsOctober 27, 2026
Ventilation duct silencer: choosing and fitting one without losing airflow

A duct silencer only deals with airborne noise carried along the ductwork, never with vibration passed on by the hangers or with a fan unit radiating noise into the loft. It goes between the fan unit and the ductwork serving the rooms, at the duct's own diameter, and is chosen on two figures from the manufacturer's datasheet: insertion loss per octave band and pressure drop at the system's airflow. Once fitted, the extract rates at the terminals still have to be met.

6 min read

ContractorsOctober 12, 2026
Facade hydroblasting: preparing the substrate before bonding

Before a bonded ETICS, CSTB Cahier 3035_V4 (June 2026) does not require hydroblasting: it requires a result. The substrate must be sound, dust-free, cleared of any non-adherent product, not sweating moisture and not frozen, with a cohesion of at least 0.1 MPa. All paints and all organic coatings are stripped over the whole surface, then adhesive bond tests are carried out to Annex 1. Hydroblasting is one of the processes that get you there: its settings are validated on a test area, and the pull-off test decides whether you bond, switch adhesive or move to mechanical fixing.

5 min read

ContractorsOctober 11, 2026
Heat pump weather compensation: setting the curve

A heat pump's weather compensation curve is set in three stages: you fix the water regime the emitters need in very cold weather, you cap the flow temperature, then you correct the parallel offset and the slope in small steps, one parameter at a time. Regulation (EU) No 813/2013 rates a heat pump's performance at two regimes, 35 °C and 55 °C outlet, and the curve must aim for one of those two points, not the machine's maximum. The rest comes down to readings: sensors, flow rate, ΔT and cycles before touching the curve, then 48 to 72 h of observation between two trials.

6 min read

ContractorsOctober 5, 2026
Custom Secondary Glazing: Measuring and Pricing Accurately

Custom secondary glazing is ordered on the smallest of the measurements taken, never on a single one: on old joinery, measure the rebate width and height at three points each and record both diagonals. The fitting clearance is then set with the workshop that makes the frame, based on that survey. On funding, promise nothing the obligated supplier has not confirmed: ECO4 has had secondary glazing measure types since Ofgem's note of 28 September 2026, notifiable only where an RdSAP assessment would recognise the installation.

6 min read

ContractorsSeptember 30, 2026
Rebound effect: secure your quotes and avoid complaints

After a renovation, the gap between theoretical savings and actual bills often comes from a rebound effect, typically measured at around 10 to 30% of the expected gains, when comfort is increased (setpoint temperature, heated rooms, duration). These benchmarks are recalled in ADEME publications on renovation and usage, and they never replace proper commissioning checks (airtightness, settings, balancing, ventilation). On your quotes, protect yourself by stating a reference temperature, a usage scenario, and the list of settings and tests carried out at handover, so that behaviour changes and installation defects are clearly distinguished.

5 min read

ContractorsSeptember 25, 2026
Construction Supervisor: Role, Tools, and Hiring Threshold

Between scheduling, crews, and clients, you are often the balancing point on site. Structuring this role means improving margin without burning people out: fewer surprises, tighter hours, faster decisions. Here is a straightforward approach to clarify responsibilities, set the right KPIs, and make profitability visible week after week.

5 min read

ContractorsSeptember 25, 2026
Walk-in Shower in Renovation: How to Install It Without Leaks

In renovation, a level-access shower comes down to two unforgiving points: slope and waterproofing. As a tradesperson, you save time and avoid call-backs when you secure the substrate, upstands, and critical details around the drain from the outset. Good layout and the right products, installed in the right order, make the difference between a smooth job and a claim.

5 min read

Energy renovationJuly 25, 2026
District Heating Networks: How They Work and Their Benefits

On a district heating network, one figure drives the whole file: the share of renewable and recovered energy. From 50% upward it opens the 5.5% VAT rate on the heat supplied, allows the network to be classified, and triggers the duty to connect above 30 kW inside the priority development perimeter. Here are the values to record before pricing a substation, and the texts that set them.

5 min read

Energy renovationJuly 23, 2026
Refrigerant Log Book: The Traceability Requirement

On site, a leak sometimes comes down to a few grams, but it can cost you dearly if traceability isn't rock solid. A well-kept log book means less stress during an inspection, cleaner interventions, and a team that knows exactly what was added, recovered or replaced. Here's a rundown of what to record and the right habits to stay compliant, without unnecessary paperwork.

5 min read

ContractorsJuly 23, 2026
Fixed windows: when not opening is an advantage

In renovation, every opening counts. When you're aiming for a genuinely airtight, high-performing envelope, a window with no opening sash becomes a simple ally to install, robust and formidable against heat loss. It's up to you to choose where to place it to gain comfort, limit thermal bridges and add value to your project, without complicating the installation or day-to-day use.

5 min read

ContractorsJuly 22, 2026
Insulating the Window Reveal in External Wall Insulation: The Sensitive Point

A poorly treated window reveal is often exactly where cold air sneaks in, even after a well-executed job. By carefully handling this sensitive point, you secure the continuity of the insulation, cut down on callbacks, and improve the comfort your client actually feels. Here's a rundown of the right habits, without unnecessary added thickness or complicated finishes.

5 min read

1 / 7

Next

Reveal your expertise

One demo, and you see your expertise proven.

Contact us