Heat pump sizing note

Calculated to NF EN 12831-1

General information

Beneficiary

Mrs Margaret Hughes

Email

contact@argile.ai

Phone

+44 7700 900457

Works address

7 Rosewood Close, Sheffield

Air-to-water heat pump

Model

Alféa Extensa S. 10

Make

Atlantic

Rated output

10 kW

ηs at 35 °C / 55 °C

195 % / 154 %

COP

3,5

Controller

Classe VI

EPREL no.

2491075

Heat loss of the home

6,0 kW

Output at the design temperature

5,80 kW

3,59 kW

7,78 kW

0 %

60 %

130 %

Coverage of the demand

Equipment output / heat loss of the home

97 %

Sizing of the appliance

Roofs

Transmittance W/m².K

1,8

Area

65,2

Heat loss W/K

135,0

Floors

Transmittance W/m².K

0,6

Area

63,0

Heat loss W/K

15,6

Thermal bridges

Conductivity W/K/m

0,4

Lengths m

33,4

Heat loss W/K

12,5

Façades

Transmittance W/m².K

0,9

Area

162,4

Heat loss W/K

151,4

Openings

Transmittance W/m².K

1,2

Area

5,5

Heat loss W/K

10,9

Air renewal

Air change rate h⁻¹

0,8

Heat loss W/K

102,3

Temperature difference

Outdoor design temperature

-7 °C

Heat pump cut-off temperature

5 °C

Indoor set temperature

19 °C

DeltaT

14,0 °C

Construction coefficient

Volume (area × ceiling height)

378,0 m³

Equivalent G value

1,13 W/m³/K

Compliant with EN 12831-1 and built from the data collected during the site visit, the sizing report comes out of the flow with no extra work, ready for the customer's file.

01

Compliant with EN 12831-1

the heating demand is calculated to the standard, and Argile flags an undersized machine as readily as an oversized one

Total heat loss

6,0 kW

Façades

35 %

2,1 kW

Roof

32 %

1,9 kW

Ventilation

24 %

1,4 kW

Floors

4 %

0,2 kW

Thermal br.

3 %

0,2 kW

Windows

3 %

0,2 kW

Emitter output at P50

11,9 kW

reference regime, 50 K delta

At the chosen water temperature

6,3 kW

55 °C flow, 45 °C return

Heat loss of the home

6,0 kW

80 %

120 %

Coverage rate

emitter output / heat loss

105 %

Sufficient

02

Generated automatically

nothing to re-enter: the radiators' output is recomputed at every entry, at P50 as at the chosen flow temperature

Roofs

Transmittance W/m².K

1,8

Area

65,2

Heat loss W/K

135,0

Façades

Transmittance W/m².K

0,9

Area

162,4

Heat loss W/K

151,4

Floors

Transmittance W/m².K

0,6

Area

63,0

Heat loss W/K

15,6

Openings

Transmittance W/m².K

1,2

Area

5,5

Heat loss W/K

10,9

03

The calculation, item by item

roofs, façades, floors, openings, thermal bridges and air renewal, each with the transmittance and the area used

0 kW1.75 kW3.5 kW5.25 kW7 kW-10 °C-6 °C-2 °C2 °C6 °C10 °C14 °C18 °CWh

-8 °C

Heat pump

5 620 W

Backup

612 W

Heat loss

6 232 W

Temperature histogram

6 h

Backup

Heat pump

Heat loss

Temperature histogram

04

Output by temperature

the heat pump's output, the electric backup and the home's heat loss, outdoor temperature by outdoor temperature over a year

Heat loss of the home

6,0 kW

Output at the design temperature

5,80 kW

3,59 kW

7,78 kW

0 %

60 %

130 %

Coverage of the demand

Equipment output / heat loss of the home

97 %

05

A solid file

heat loss, output at the design temperature and coverage of the demand on a single page, to attach to the quote for customers, lenders and grant bodies

They already trust us

DorémiSaint-GobainIllico TravauxCarrierCrédit Mutuel ArkéaChadapauxLa Maison des TravauxEffyCrédit AgricoleGC GruppeHomeServeDualSunEnsol

+2000

installers

generate their sizing reports with Argile

10,000

products

kept up to date in our manufacturer catalogues

The journey

Camille Martin

/

Works plan

/

Air-to-water heat pump installation

Air-to-water heat pump installation

Save the job

1

Home details

2

Works

3

Equipment choice

4

Projected works

Next step

Zones to heat

Emitter coverage

105 %

Radiators

Area to heat *

Simple

Expert

130 m²

Add an emitter

Click to add an underfloor heating zone

The customer’s heating preferences

Flow water temperature

35°

40°

45°

50°

55°

60°

65°

70°

75°

Low temp.

Medium temp.

Recommended

High temp.

Indoor set temperature

19°

20°

21°

22°

23°

Economy

Standard

Comfort

Comfort +

High performance

6,00 kW

Heat loss of the home over the heated area

11,90 kW

Estimated emitter output at P50

6,30 kW

(105 % coverage)

Estimated emitter output at the chosen water temperature

01

Home details

Zones to heat declared by emitter type, radiators or underfloor heating, with the area each one covers, then the customer's preferences: flow water temperature and indoor set temperature, from which Argile derives the emitter coverage.

Heat pump project

Document the air-to-water heat pump project

Zone to heat

Rooms & emitters

Unit positions

4

Sizing

Choose an indoor set temperature

19°

20°

21°

22°

23°

Economy

Standard

Comfort

Comfort +

High performance

Planned insulation

External wall insulation

Upper floor insulation

Ground floor insulation

Window replacement

Check of the radiators’ output

Estimated heating demand

6,0 kW

Low temperature

2,2 kW

UNDERSIZED

Medium temperature

6,3 kW

RECOMMENDED

High temperature

12,2 kW

OVERSIZED

Back

Confirm

02

Heat loss calculation

The heating demand is estimated from the survey and the planned insulation, then checked against the radiators' output: low, medium and high temperature, each judged undersized, recommended or oversized.

Camille Martin

/

Works plan

/

Air-to-water heat pump installation

Air-to-water heat pump installation

Save the job

Home details

Works

3

Equipment choice

4

Projected works

Next step

Equipment

Switch to separate units

HEAT PUMP KIT SELECTED

Alféa Extensa S. 10

Default

Atlantic

HEAT PUMP COVERAGE

97 %

Controller

VI

Application

Medium temp.

Max temp.

60 °C

ηs 35 °C

195 %

ηs 55 °C

154 %

Output

10 kW

COP

3,50

Use

Heating

Phases

Single-phase

Quantity

x1

Price excl. VAT

4 890,00 €

VAT

5,50 %

Price incl. VAT

5 158,95 €

Labour

5 390,00 € TTC

3 items selected

DEFAULT

Removal

Price incl. VAT

1 500,00 €

Installation

Price incl. VAT

3 000,00 €

Adaptation package

Price incl. VAT

890,00 €

Accessories

589,00 € TTC

1 item selected

DEFAULT

Safety group supply

Price incl. VAT

589,00 €

03

Choosing the equipment

The machine picked from your catalogues shows its coverage against the calculated demand, with its application, its ηs at 35 °C and 55 °C, its COP and its output, labour and accessories attached to the job.

Heat pump sizing note

Calculated to NF EN 12831-1

General information

Beneficiary

Mrs Margaret Hughes

Email

contact@argile.ai

Phone

+44 7700 900457

Works address

7 Rosewood Close, Sheffield

Air-to-water heat pump

Model

Alféa Extensa S. 10

Make

Atlantic

Rated output

10 kW

ηs at 35 °C / 55 °C

195 % / 154 %

COP

3,5

Controller

Classe VI

EPREL no.

2491075

Heat loss of the home

6,0 kW

Output at the design temperature

5,80 kW

3,59 kW

7,78 kW

0 %

60 %

130 %

Coverage of the demand

Equipment output / heat loss of the home

97 %

Sizing of the appliance

Roofs

Transmittance W/m².K

1,8

Area

65,2

Heat loss W/K

135,0

Floors

Transmittance W/m².K

0,6

Area

63,0

Heat loss W/K

15,6

Thermal bridges

Conductivity W/K/m

0,4

Lengths m

33,4

Heat loss W/K

12,5

Façades

Transmittance W/m².K

0,9

Area

162,4

Heat loss W/K

151,4

Openings

Transmittance W/m².K

1,2

Area

5,5

Heat loss W/K

10,9

Air renewal

Air change rate h⁻¹

0,8

Heat loss W/K

102,3

Temperature difference

Outdoor design temperature

-7 °C

Heat pump cut-off temperature

5 °C

Indoor set temperature

19 °C

DeltaT

14,0 °C

Construction coefficient

Volume (area × ceiling height)

378,0 m³

Equivalent G value

1,13 W/m³/K

04

Issuing the report

The report comes out of the flow as one document: heat loss item by item, the temperature difference used, the construction coefficient, the machine's output and the coverage of the demand, attached to the customer file.

Cengiz Donmez, Whole-home renovation
Cengiz DonmezWhole-home renovationGroupe TILKEO50 employees

“When several teams are involved, everyone needs to work with the same information. Argile helps us standardize our visits and better manage our projects.”

These features should interest you too

The Argile building blocks that pair best with this one, from the survey through to the job site.

Air-to-water heat pump

From the site visit to a sizing report compliant with EN 12831-1: Argile guides your teams at every step, calculates the required output, picks the equipment from up-to-date catalogues and shows the customer the energy they will save.

Customers

/

Camille Martin

Details

Dwelling

Works plans

Quotes

Admin & finance

Quote no. D2026-0042

History

Analysis

Preview

Save

The property

Energy renovation

Information

4

The quote

5

Terms

Next step

The quote

No.

Description

Qty

Unit

Unit price excl.

Total excl.

VAT

Price incl.

1

Installing an air-to-water heat pump

Technical specifications of the heat pump (mandatory)

3 STILL TO FILL IN

Area heated by the heat pump (m²)

e.g. 120

Seasonal energy efficiency ηs (%)

e.g. 126

Controller class

I

II

III

IV

V

VI

VII

VIII

1.1

Installing an air-to-water heat pump

10 600,00 €

11 183,00 €

1.1.1

Air-to-water heat pump 14 kW

1,00

U

3600,00

3 600,00 €

5,5%

3798,00

B

I

U

Heat output +7 °C / +35 °C: 13.00 kW. Heat output -7 °C / +60 °C: 10.10 kW. Seasonal space heating efficiency (35 °C / 55 °C): 150 % / 117 %.

1.1.2

Heat pump fitting and commissioning

1,00

U

7000,00

7 000,00 €

5,5%

7385,00

Add a line

2

External wall insulation (EWI)

2.1

External wall insulation (EWI)

22 500,00 €

23 737,50 €

2.1.1

Polystyrene insulation, R of 3.7 m².K/W or above

120,00

M2

120,00

14 400,00 €

5,5%

15192,00

2.1.2

Insulation labour package

120,00

M2

75,00

9 000,00 €

5,5%

9495,00

Discount

-900,00 €

8 545,50 €

Quotes

Equipment, labour and accessories come from the works plan, VAT applies line by line, grants are deducted from the amount due and the mandatory wording is already written: the quote goes out for signature without a proofread.

Remote design

Remote design

From your desk, qualify the home, sketch the project and give the customer a dependable first estimate before the site visit: you only travel for the projects that are worth it.

FAQ

Browse the answers to the most frequent questions. And if needed, our team is here to help.

Contact us

Yes: heat loss and the heating demand are calculated to EN 12831-1, from the outdoor design temperature of the municipality.

Ready to generate compliant sizing reports?

One demo, and you see your expertise proven.

Contact us