Blog/Thermodynamic heat-recovery ventilation: what it actually heats
Energy renovation

June 10, 2026

5 min read

Updated August 6, 2026

Thermodynamic heat-recovery ventilation: real output, the EPC and the grant file

A thermodynamic heat-recovery unit is sold as ventilation that heats. The question nobody asks at quote stage is how much heat the supply air can actually carry, and that is bounded by the regulatory flow rates. We work it out here, along with what the French EPC keeps from the machine and what the decree of 17 November 2020 requires for the grant.

Contents

A thermodynamic heat-recovery unit is a balanced ventilation unit to which a heat pump module adds heat on the supply side. The output it can actually deliver is bounded by the air flow rate: with the volumetric heat capacity of air of 0.34 Wh/(m³.K) used by the 3CL-DPE 2021 method, a four-room home ventilated at the minimum modulated total flow rate of 90 m³/h set by article 4 of the French decree of 24 March 1982 carries only about 610 W with supply air 20 K above the room. On the grant side, article 7 of the decree of 17 November 2020 requires a temperature ratio of at least 85% measured to NF EN 13141-7, regardless of the thermodynamic module.

What the machine is, and what it is not

Extract-only, balanced, thermodynamic

In an extract-only system, stale air is drawn out and fresh air enters through inlets in the habitable rooms. In a balanced system, a second network supplies fresh air after it passes through an exchanger that recovers part of the heat in the extract air. The thermodynamic version adds a heat pump that takes further energy from the discharge air after the exchanger, to warm the supply air and sometimes to produce domestic hot water. Ventilation remains the primary function, heating is a supplement carried by the same air.

The physical bound nobody puts on the quote

The heat a given air flow can carry equals 0.34 x flow rate x temperature difference between the supply air and the room. Taking the minimum modulated total flow rates of article 4 of the decree of 24 March 1982, here is what the air can carry.

Habitable rooms Minimum total flow rate (m³/h) Supply at +10 K at +15 K at +20 K
3 75 255 W 383 W 510 W
4 90 306 W 459 W 612 W
5 105 357 W 536 W 714 W
6 120 408 W 612 W 816 W
7 135 459 W 689 W 918 W

Supply air 20 K above the room already means 40 °C at the diffuser, the upper comfort limit for air distribution. Anything claimed beyond this table assumes a flow rate above the regulatory minima, therefore fan energy and noise that are not on the quote.

Where it works, and where it does not

It holds up on high-performance new build and on whole-house renovation with a treated envelope, controlled airtightness, short duct runs and room for the network, in homes whose heat losses stay in the same range as the table above. On a poorly insulated house, the machine ventilates correctly and heats nothing anyone can feel: the client pays for electric backup and blames the ventilation. The prescribing rule is therefore to check heat losses before talking about integrated heating, not the other way round.

What the EPC and the texts keep from the machine

The EPC does not know the thermodynamic unit

The ventilation type table of the 3CL-DPE 2021 method contains no line for a thermodynamic heat-recovery unit. The ventilation side is treated as an individual heat-recovery unit with exchanger, and it is the conventional flow rate that drives the heat loss, through Hvent = 0.34 x Qvarepconv x Sh.

Ventilation type applied Qvarepconv (m³/(h.m²))
Individual heat-recovery unit with exchanger, after 2012 0.26
Individual heat-recovery unit with exchanger, up to 2012 0.60
Balanced unit without exchanger, after 2012 1.32
Humidity-controlled type B extract unit, after 2012 1.09

In other words, the EPC argument for the machine rests on the exchanger, not on the thermodynamic module. That reading is developed in our article on heat-recovery ventilation efficiency.

When the machine also produces hot water

If the unit handles domestic hot water, the 3CL-DPE 2021 method tabulates default annual COPs where the exact characteristics cannot be entered.

Appliance Zones H1 and H2, from 2015 Zone H3, from 2015
Extract-air heat pump water heater 2.8 2.9
Outside-air or ambient-air heat pump water heater 2.5 2.8
Dual-service heat pump 2.3 2.6

The dual-service heat pump is credited less than the extract-air water heater alone. If the client's real need is hot water, a dedicated pairing makes a better case, as covered in our article on extract-air heat pump water heaters.

The requirements that gate the grant and the market

Article 7 of the decree of 17 November 2020 asks for a temperature ratio measured to NF EN 13141-7 of at least 85%, certified by a body accredited to NF EN ISO/IEC 17065 by COFRAC, and a weighted electrical power input of the unit no greater than 47.6 W-ThC in a four-room configuration with one bathroom and one WC. A unit certified to NF 205 is deemed to satisfy it. Upstream, Regulation (EU) No 1253/2014 has required since 1 January 2018 a recovery thermal efficiency of at least 73%, a thermal bypass, a variable-speed drive and a filter change signal.

Assessing feasibility before pricing

What you record on the technical visit

Locate the unit position with power supply, external discharge and condensate drain, then the routes through lofts or suspended ceilings: this is precisely what a guided site survey records on the spot, photos and equipment positions included. Measure the real lengths, count the bends, check there is room to hold the diameters all the way. Also record the service rooms to extract from and the habitable rooms to supply, because that count sets the flow rate and therefore, through the table above, the available output.

Pressure losses are a compliance item

Every tight bend and every extra metre of flexible is paid for in power input, therefore in headroom against the 47.6 W-ThC cap. Keep runs short, bends wide, flexible on the last few metres only, and ducts supported without crushing. Network sizing is covered in detail in our guide on ventilation ductwork.

Condensate, acoustics and maintenance access

The exchanger and the thermodynamic module both produce condensate: continuous fall, primed trap, no back-fall, an access point for cleaning. Insulate ducts outside the heated volume, or you will recover on one side what you lose on the other. Mount the unit on anti-vibration supports, away from bedrooms, and leave clear access to the filters and the module: impossible maintenance turns into lost performance within two years.

Pricing and installing without creating callbacks

Settle the flow rate before anything else

The flow rate is set from the values of the decree of 24 March 1982, not from the output you would like. Article 3 requires a kitchen peak extract rate from 75 m³/h with one habitable room to 135 m³/h from five upwards, reachable at any time. Article 4 sets the modulated floors in the table above. The room-by-room detail is in our article on the flow rates of the decree of 24 March 1982.

Installation, where most of the performance is decided

Aim for an airtight and accessible network: clamps, sleeves and suitable tape on every joint, penetrations treated as detail points, ducts insulated outside the heated volume. The unit goes on anti-vibration supports with its condensate drain. Duct leakage, the first cause of the gap between quoted and measured performance, is developed in our article on duct airtightness.

What you measure and what you record

At commissioning, read flow rates terminal by terminal on extract and supply, check the overall balance, note the supply air temperature after the exchanger and test the thermal bypass. Record those values in a dated report, with the references of the unit and the filters. The method and the instruments are covered in our article on measuring ventilation flow rates.

Selling the machine without committing to what you cannot hold

What goes on the quote

Write the reference of the unit, its certified temperature ratio, its weighted electrical power input, the flow rates guaranteed room by room, and the thermal output of the module at the test point declared by the manufacturer. Separate the ventilation line from the supplementary heating line: that is what lets you demonstrate, if it is ever disputed, that the heating you announced was a supplement. That split comes from the pricing itself: the ventilation works open onto your catalogues, unit, vents and ducting, with your price, your VAT rate and your installation labour.

What does not go on it

Do not put a heating saving as a percentage or in currency: it depends on the envelope, the existing appliance and occupancy, and no text lets you guarantee it. Do not present the machine as an alternative to a heat generator on a home whose heat losses you have not calculated. Do not promise a filter interval in advance: the on-board warning signal, mandatory since 2018, is your reference.

What you commit to against a cheaper bid

A competitor announcing several kilowatts of integrated heating on a four-room home runs into the table at the top of this article. Put it on the desk, set the regulatory flow rate beside it, and let the client do the arithmetic. Your argument is not a bigger number, it is the certificate of the unit, the flow rate record and a quote line that separates what the machine ventilates from what it heats. It is also what protects your liability cover.

Key figures

≈ 610 W

output carried, four-room home at minimum flow

0.26 m³/(h.m²)

what the EPC keeps, ventilation side

85%

temperature ratio required for the grant

Frequently asked questions

No, and the arithmetic settles it in two lines. The heat a supply air stream can carry equals 0.34 x flow rate x temperature difference, taking 0.34 Wh/(m³.K) as the volumetric heat capacity of air used by the 3CL-DPE 2021 method. At the minimum modulated total flow rate of a four-room home, that is 90 m³/h under article 4 of the decree of 24 March 1982, with supply air 20 K above the room, you carry roughly 610 W. It is a supplement, not a generator, and the quote must say so.

Share this article

Louis Airy

Louis is COO of Argile. After four years in strategy consulting and close to two as chief of staff in home adaptation and reuse, he joined Argile in March 2024. In daily contact with certified renovation companies, he follows French energy saving certificates, renovation subsidies and reduced VAT, and revises the affected articles whenever a rate changes. What he writes is what he then checks against real quotes.

Further reading

With argile

The site visit that fills in the file for you

On a phone, the technician documents the home and the project job by job: surveys, photos, equipment positions and sizing confirmed on the spot, with nothing to re-enter back at the office.

Camille Martin

/

Works plan

/

Extract ventilation

Back

Extract ventilation

Save the job

Equipment choice

Works projections

Equipment

Change the equipment

Equipment selected

Aldes

EasyHOME Hygro Premium

Default

x1

Installation type

Individual

Ventilation type

Type B

Unit type

Low consumption

Quantity

1

Price excl. VAT

1 749,76 €

VAT

5,5 %

Price incl. VAT

1 846,00 €

Add equipment from your catalogue

Services

Extract ventilation installation

x1

1 000,00 €

Add a service

Accessories

Humidity-sensitive extract terminal

x3

120,27 €

Humidity-sensitive air inlet

x6

538,05 €

Insulated duct Ø 125

x1

65,41 €

Add an accessory

Total cost

Equipment cost

1 846,00 €

Services cost

1 000,00 €

Accessories cost

723,73 €

Total incl. VAT

3 569,73 €

With argile

Document the ventilation, price the job in one visit

Existing ventilation type, combustion safety checks, wet rooms, units to fit: Argile records everything during the visit, then configures the ventilation job with the equipment from your catalogues, with no re-entry.

ContractorsMay 30, 2026
Air Inlets and Extract Vents: Sizing Your MVHR System

When an MVHR system is properly sized, you notice it right away, less lingering humidity, odours that don't come back, and clients who breathe easier. But it all comes down to job-site details, air inlets, extract vents, and room-by-room airflow balance. Get these right at installation and you avoid callbacks while securing the home's performance, without the headache.

5 min read

Reveal your expertise

One demo, and you see your expertise proven.

Contact us