Blog/R290 propane heat pumps: the rising natural refrigerant
Energy renovation

April 18, 2026

6 min read

Updated September 9, 2026

R290: the refrigerant that falls outside the F-gas rules

R290 is propane. It is not a fluorinated greenhouse gas, so it sits outside the quotas in Annex VII of EU Regulation 2024/573, outside the leak checks in its Article 5, and outside the placing-on-the-market bans in its Annex IV. Two trade-offs: safety class A3, whose charge allowed per room comes from the manual and not from a forum, and company certification, which the French order of 21 November 2025 extends to hydrocarbons from 1 January 2027.

Contents

R290 is propane, rated A3 for flammability. It is not a fluorinated greenhouse gas: it appears neither in Annex I nor in Section 1 of Annex II of EU Regulation 2024/573, which puts it outside the Annex VII quotas, outside the Article 5 leak checks and outside the Annex IV placing-on-the-market bans. On the French side, Article R543-75 of the environment code lists four families only, CFCs, HCFCs, HFCs excluding HFOs and PFCs, and propane is on none of them. What constrains an R290 job is therefore not the refrigerant regime: it is the charge allowed per room, which comes from the manufacturer's manual and nowhere else, and now the firm's certification, which the new certificate regime extends to hydrocarbons.

What EU Regulation 2024/573 requires, and what R290 sits outside of

The closed annex lists, the point everyone skips

Regulation (EU) 2024/573 entered into force on 11 March 2024 and repeals Regulation (EU) 517/2014. It does not apply to "every refrigerant", but to the substances listed in its Annexes I, II and III. Propane is not among them. In practice a monobloc R290 unit consumes no quota, triggers no leak check interval, and carries no placing-on-the-market cut-off date. That is a verifiable technical argument to set against sales sheets that claim "2035-proof" without citing an article.

The Annex IV timetable, worth keeping to hand when quoting

That timetable does not cover R290, but it covers everything you strip out and everything you benchmark against. Mind the wording used by the text: it says self-contained and split, not monobloc and split as the trade does.

Equipment (Annex IV) GWP banned Date
Split systems containing less than 3 kg of an Annex I gas ≥ 750 1 January 2025
Self-contained heat pumps and air conditioners ≤ 12 kW ≥ 150 (750 where safety requires) 1 January 2027
Self-contained units > 12 kW and ≤ 50 kW ≥ 150 (750 where safety requires) 1 January 2027
Split air-to-water ≤ 12 kW ≥ 150 1 January 2027
Split air-to-air ≤ 12 kW ≥ 150 1 January 2029
Split systems > 12 kW ≥ 750 1 January 2029
Self-contained units ≤ 12 kW any fluorinated gas 1 January 2032
Split systems > 12 kW ≥ 150 1 January 2033
Split systems ≤ 12 kW any fluorinated gas 1 January 2035

The 2035 date applies only to split systems of 12 kW and under. A split above 12 kW stops at a GWP of 150 in 2033, with no total cut-off. For a comparison of the refrigerants themselves, see refrigerants for heat pumps in 2026.

What the real squeeze on R410A and R32 means for your supply

The constraint that bites first is not a ban, it is the Annex VII quota. It drops to 42,874,410 tonnes of CO2 equivalent for 2025-2026, then 21,665,691 for 2027-2029, and 0 from 2050, against a 2015 baseline of 176,700,479 tonnes. Put plainly, fluorinated refrigerant does not become illegal, it becomes scarce and expensive. That is what pushes ranges towards R290, not a ban on recharging.

  • R410A can still be topped up: the servicing ban in Article 13(4) targets a GWP of 2,500 or above, and R410A sits below it.
  • Spare parts remain marketable under Article 11(1), with no increase in charge and no move to a higher GWP.
  • Commissioning stays possible where the unit was placed on the market before the ban date, under Article 13(19).

The regime that applies to a machine reads off three inputs, the refrigerant, the charge and whether the circuit is hermetic. R290 exits on the first; every other fluid is settled on all three.

Obligation

Leak checks: is this job covered?

The obligation is not triggered by the kilograms of refrigerant but by tonnes of CO₂ equivalent: the charge times the fluid’s global warming potential. Hence different answers for the same charge depending on the fluid.

Refrigerant
Total charge

3.0 kg

Hermetically sealed equipment
Permanent leak detection

Equivalent charge

2.0 t CO₂e

GWP 675

Leak check

Not required

Trigger threshold

5 t CO₂e

that is 7.4 kg of this fluid

Below the threshold: no periodic check

This is the usual case for a residential R32 multi-split. What still applies: the company’s certification, the tightness test and evacuation at commissioning, the intervention record and the logbook.

Regulation (EU) 2024/573, article 5. Periodic checks are one thing; the company’s certification, the tightness test at commissioning and the record keeping apply whatever the charge.

An Argile tool

What changes on 1 January 2027: certification, not the refrigerant

One point has turned around, and it comes from certification rather than from the annexes. Article 10 of Regulation (EU) 2024/573 covers activities on fluorinated gases and relevant alternatives, including natural refrigerants. Implementing Regulation (EU) 2024/2215 names them, ammonia, carbon dioxide and hydrocarbons, and the French order of 21 November 2025 repeats the wording: its category A1 covers fluorinated greenhouse gases and hydrocarbons. Fitting a propane heat pump therefore calls for a company certificate carrying the hydrocarbon endorsement, mandatory from 1 January 2027.

The R290 regime is not tightening; the scope of certification is widening. Propane stays outside quotas, outside leak checks and free of any placing-on-the-market cut-off: what changes is who may open the circuit. The timetable, the six categories and the 12 March 2029 validity cap are set out in the company certificate, categories A1 to E.

Class A3 safety: what replaces the statutory leak check

Maximum charge per room: the manual is the only quotable source

This is where online material is most often wrong. Charge limits for A3 refrigerants come from EN 378-1+A1 of October 2020, whose Annex C is normative, and from IEC 60335-2-40, whose 2022 edition was withdrawn on 11 December 2024 in favour of the 2024 edition. Both are paid standards and no figure from them is publicly quotable. The 150 g figure repeated by most pages rests on no consultable text: keep it off quotes and off calculation notes. What goes into the file is the manual reference and the minimum room area it imposes for the model fitted.

Siting the outdoor unit: ventilation, low points, ignition sources

For the outdoor unit, look for open air. Avoid recesses, narrow walkways and any poorly ventilated volume. Respect the manual's distances from openings, basement windows, grilles and ignition sources. The commonest fault on a survey record: siting above a gully, a manhole or a pit, where a propane layer can settle since it is heavier than air. Photograph and date that point like the rest of the survey record, equipment positions included: it is on your liability.

Transport, storage and service calls: what gets logged

For handling and storage, keep recovery cylinders secured, upright, shaded and in a ventilated area. On service calls, use A3-compatible tools, work with doors open where possible, recover into a certified cylinder, then check tightness before returning the unit to service. The leak check is not statutory here, it is contractual: you decide to log it, and that log is what covers you in a dispute.

Sizing and commissioning an R290 heat pump

Start from heat loss, not from the advertised flow temperature

The target is the right output at the design temperature, not the machine with the highest headline flow temperature. On low water volume circuits, head off short cycling by working on usable volume and settings rather than by oversizing. The standardised figure for comparing two models is the seasonal space heating energy efficiency under Regulation (EU) 813/2013: at least 110% for medium and high temperature units and 125% for low temperature units since 26 September 2017.

Hydraulics and settings: balancing, heating curve, backup, frost protection

Clean hydraulics first. Degassing, filter, compliant flow rate, balancing valves and a properly sized circulator. Then the fine settings. Calibrate the heating curve against the emitters you recorded, cap the flow temperature, configure the backup as a last resort and secure frost protection to suit the configuration. On an outdoor monobloc, water-side frost protection is not a comfort option, it is a warranty clause.

Handover checks: what goes on the commissioning record

At commissioning, check the supply, protections, flow direction, delta T, flow rate, sound level, hot water and defrost cycles. Sound level is not cosmetic: Article R1336-7 of the French public health code caps the overall noise emergence at 5 dB(A) between 07:00 and 22:00 and 3 dB(A) between 22:00 and 07:00, with correction terms based on how long the noise runs. On attenuation methods, see heat pump noise and vibration.

What you put on the quote and in the grant file

Quote wording: what stops a file

On an R290 job the refrigerant is not an administrative argument, it is a technical characteristic to state on the quote like any other. Check eligibility for MaPrimeRénov' 2026 and the performance requirements attached to the measure, then the matching standardised operation sheet. Checks bear on consistency between the equipment fitted, its declared performance and the file: that is where refusals happen, not on the nature of the refrigerant.

Documents to supply: the minimum paper trail

  • Valid installer accreditation at the signing date.
  • Detailed quote and invoice: brand, reference, output, R290 refrigerant and charge in kg.
  • Grant and energy-saving certificates, bank details, tax notice, site address.
  • Proof of removal and commissioning record where required.

Justifying your price against a cheaper bid

An R290 job is priced on the siting constraint, not on the refrigerant. Any extra cost comes from the location the manual imposes, the hydraulic run that follows from it, and frost protection. That is what you put against a competitor who took the shortest route. On charge and its traceability, whatever the refrigerant, see refrigerant charge.

Key figures

A3

Safety class

1 January 2027

Split air-to-water ≤ 12 kW, GWP ≥ 150

0

HFC quota from 2050

Frequently asked questions

Yes, from 1 January 2027. The scope of certification no longer follows the closed list of Article R543-75 of the French environment code: Implementing Regulation (EU) 2024/2215 extended it to natural refrigerants, and category A1 in Annex I of the French order of 21 November 2025 covers fluorinated greenhouse gases and hydrocarbons. A firm that only fits propane monoblocs can apply for the hydrocarbon endorsement alone. Still binding alongside it: the manufacturer's manual, the safety rules attached to class A3, and the warranty conditions, which most manufacturers tie to commissioning by a trained operator.

Share this article

Louis Meneteau

Louis is CPO of Argile. An engineer by training, he spent four years validating calculation software in systems engineering, then three years in software product. He turns the installer's daily reality into product workflows: technical survey, sizing, quotes and subsidy files. His articles describe field gestures rather than principles, because he watches them on site before specifying them.

Further reading

With argile

The site visit that fills in the file for you

On a phone, the technician documents the home and the project job by job: surveys, photos, equipment positions and sizing confirmed on the spot, with nothing to re-enter back at the office.

ContractorsApril 14, 2026
Air-to-water heat pump defrosting: impact on winter performance

When the temperature drops, defrosting becomes the little pause that can make a client uneasy. As a tradesperson, you have everything to gain by simply explaining what's happening, when it's normal, and how to limit the loss of comfort and efficiency. With the right settings and a careful installation, winter stays a season of results, not surprises.

5 min read

ContractorsJune 20, 2026
Extract-air heat pump water heaters: available flow rate comes first

An extract-air heat pump water heater is the best credited of its family in the French EPC, on one condition that is rarely checked on the technical visit: that the ventilation supplies it with enough continuous air flow. The minima of the decree of 24 March 1982 are often below what the machine asks for. Here is the calculation to run before you specify.

5 min read

Reveal your expertise

One demo, and you see your expertise proven.

Contact us