Blog/Refrigerant charge: calculation and precautions
Contractors

July 22, 2026

5 min read

Updated September 9, 2026

Refrigerant charge: from kilos to tonnes of CO2 equivalent

The refrigerant charge commands two things: how the machine performs and what you owe the regulator. The second is not read in kilos but in tonnes of CO2 equivalent, and the conversion is one multiplication by the GWP. Here is the conversion table by refrigerant, the leak check interval table, and what gets logged after every job.

Contents

The refrigerant charge is read in kilos on the nameplate, but your obligations are counted in tonnes of CO2 equivalent. The conversion is one multiplication: charge in kilos times the refrigerant GWP, divided by 1,000. The threshold that triggers periodic leak checking is 5 tonnes of CO2 equivalent under Article 5 of EU Regulation 2024/573, carried over by Article R543-79 of the French environment code, with intervals set by Article 4 of the order of 29 February 2016. On a residential heat pump holding 1 to 2 kg, none of those thresholds is reached, and the exemption is even explicit below 3 kg for labelled hermetically sealed equipment.

Turning a charge into an obligation

The conversion table by refrigerant

GWP values come from Annex I of EU Regulation 2024/573, on the fourth IPCC assessment report. Blends are not listed there: their GWP is worked out through the Annex VI method, a mass-fraction weighted average. The R410A and R407C figures below are therefore calculated values, and should be presented as such.

Refrigerant GWP used 5 t CO2e 50 t CO2e 500 t CO2e
R32 675 (Annex I) 7.41 kg 74.1 kg 741 kg
R410A 2,088 (calculated, Annex VI) 2.39 kg 23.9 kg 239 kg
R407C 1,774 (calculated, Annex VI) 2.82 kg 28.2 kg 282 kg
R134a 1,430 (Annex I) 3.50 kg 35.0 kg 350 kg
R290, R744, R717 outside the annexes not applicable not applicable not applicable

The leak check interval table

These intervals are set identically by Article 5(6) of EU Regulation 2024/573 and by Article 4 of the French order of 29 February 2016. They double as soon as a leak detection system is fitted.

Equipment charge Without leak detection With a detection system
Under 5 t CO2e No periodic check required Not applicable
5 to under 50 t CO2e 12 months 24 months
50 to under 500 t CO2e 6 months 12 months
500 t CO2e and above 3 months 6 months

Obligation

Leak checks: is this job covered?

The obligation is not triggered by the kilograms of refrigerant but by tonnes of CO₂ equivalent: the charge times the fluid’s global warming potential. Hence different answers for the same charge depending on the fluid.

Refrigerant
Total charge

3.0 kg

Hermetically sealed equipment
Permanent leak detection

Equivalent charge

2.0 t CO₂e

GWP 675

Leak check

Not required

Trigger threshold

5 t CO₂e

that is 7.4 kg of this fluid

Below the threshold: no periodic check

This is the usual case for a residential R32 multi-split. What still applies: the company’s certification, the tightness test and evacuation at commissioning, the intervention record and the logbook.

Regulation (EU) 2024/573, article 5. Periodic checks are one thing; the company’s certification, the tightness test at commissioning and the record keeping apply whatever the charge.

An Argile tool

The scope of the regime, narrower than commonly stated

Article R543-75 of the French environment code, as written by decree 2015-1790, lists four families and only four: CFCs, HCFCs, HFCs excluding HFOs, and PFCs. An R290, R744 or R717 circuit falls outside that scope: neither the leak check of Article R543-79 nor the tonnes-of-CO2-equivalent calculation is triggered by the refrigerant. One important caveat since 2025: the company certificate no longer follows that perimeter. Implementing Regulation (EU) 2024/2215 extended certification to natural refrigerants, and the French order of 21 November 2025 attaches hydrocarbons to categories A1 and A2, carbon dioxide to a category B and ammonia to a category C, all mandatory from 1 January 2027: see the A1 to E certificate categories. Nor does that take anything away from the safety requirements specific to those fluids, or from the manufacturer's warranty conditions. For an overview of refrigerants and their deadlines, see refrigerants for heat pumps in 2026.

What you meet on site, and what is wrong about it

R410A is not a banned refrigerant

This is the commonest confusion, and it turns against you in front of a client. Article 13(4) of EU Regulation 2024/573 bans, from 1 January 2026, the use of virgin fluorinated gases with a GWP of 2,500 or above for servicing air conditioning and heat pump equipment.

What tightens is the placing on the market of new machines, with the ban on a GWP of 750 or above for split systems under 3 kg since 1 January 2025.

R32 and its A2L classification

R32 is classed A2L, mildly flammable, which calls for ventilation, no ignition sources and compatible tooling during charging and recovery. The maximum charge allowed in a room comes from the manufacturer's manual, which applies EN 378-1+A1 and IEC 60335-2-40, two paid standards from which no figure is publicly quotable. Do not write a maximum charge found online onto a quote: use the one in the manual for the model fitted.

The four prohibitions that depend on no threshold

  • Intentional release of fluorinated gases to atmosphere, banned by Article 4 of the regulation where it is not technically necessary.
  • Failing to recover before opening the circuit, recovery being required by Article 8.
  • Mixing two refrigerants in one circuit, which makes any superheat reading uninterpretable.
  • Topping up a circuit whose leak has not been searched for and repaired.

Calculating and setting the right charge

Start from the nameplate, then the manufacturer's table

The nameplate carries the refrigerant type and the nominal charge, usually the factory charge for a reference line length. Beyond that length the manufacturer publishes an additional charge in grams per metre by diameter. No generic value is published by any primary source: a figure borrowed from another model produces a wrong charge, and a wrong charge invalidates every later diagnosis. Those manufacturer figures sit in the catalogue rather than in a mislaid manual: Argile keeps the technical data of every reference verified and up to date.

The sequence for putting the circuit in clean condition

  • Pressure test and leak search with nitrogen, then a nitrogen purge during brazing to limit internal oxidation.
  • Vacuum pull-down with a hold check, the only proof that air and moisture have gone.
  • On the associated water circuits, pressure test before filling, logged in the same way.

Charge by weight, then verify by measurement

The charge is set on a scale, to the manufacturer's value, and then verified through superheat and subcooling at steady state. For blends, charging is done in liquid phase to avoid fractionation. A top-up decided from pressures alone, without stabilisation or temperature readings, is the leading cause of overcharging seen on service calls. On handover checks, see heat pump commissioning.

What stays in the file after you leave

The intervention record, and who signs it

The intervention record of Article R543-82 states the nature of the work, the refrigerant type and the quantities recovered and added. Above 3 kg of HCFCs or 5 tonnes of CO2 equivalent of HFCs or PFCs, it is signed jointly by the operator and the equipment holder. Below the thresholds it is not mandatory, but it remains the only written proof of the circuit's condition when you left. That record stays attached to the job rather than to a binder: Argile keeps progress, photos and documents tied to the file, from the signed quote to handover.

Retention periods and the check marking

Article R543-80 requires leak check records to be kept for five years. Article R543-79-1 provides for a check marking to be applied to the equipment, and a leak-fault marking where a leak found cannot be repaired immediately. Those markings are the first thing an inspector looks at, before your register.

The certificate of competence, per establishment

The certificate of competence of Article R543-99 is issued by an approved body, for a maximum of five years, and attaches to an establishment rather than to the company as a whole. It states the equipment types and activities covered. The French order of 21 November 2025 replaces the issuing scheme from the order of 30 June 2008 and becomes mandatory on 1 January 2027: it substitutes categories A1, A2, B, C, D and E for categories I to IV, and brings natural refrigerants into scope. Two things to check before that date, then: the renewal calendar for your establishments, and the endorsement you apply for, hydrocarbons included if you fit R290 units.

Key figures

5 t CO2e

Leak check threshold

2.39 kg

R410A charge reaching it

5 years

Record retention

Frequently asked questions

From 5 tonnes of CO2 equivalent of an Annex I gas, or 1 kilogram of a gas listed in Section 1 of Annex II, under Article 5 of EU Regulation 2024/573. Two exemptions matter in housing: hermetically sealed equipment labelled as such is out of scope below 10 tonnes of CO2 equivalent, and in residential buildings as soon as it holds less than 3 kg. The conversion is done by multiplying the charge in kg by the refrigerant GWP and dividing by 1,000.

Share this article

Louis Airy

Louis is COO of Argile. After four years in strategy consulting and close to two as chief of staff in home adaptation and reuse, he joined Argile in March 2024. In daily contact with certified renovation companies, he follows French energy saving certificates, renovation subsidies and reduced VAT, and revises the affected articles whenever a rate changes. What he writes is what he then checks against real quotes.

Further reading

Catalogues

/

Argile catalogue

/

Air-to-water heat pump

Argile catalogue

Add a product

Article base

Central articles, shared across all your equipment

Careful, this article is shared

This article is used in 14 products; any change will apply everywhere.

Name / Reference

Brand

Purchase cost

Selling price

VAT

Unit

Used in

Liaison frigorifique 5 m

ATL-LF05

Atlantic

68,00 €

119,00 €

5,5 %

Unit

14 products

Ballon tampon 25 L

ATL-BT25

Atlantic

142,00 €

245,00 €

5,5 %

Unit

9 products

Câble d’alimentation 3G2,5

GEN-C3G25

3,10 €

5,80 €

5,5 %

Linear metre

37 products

Support antivibratile

GEN-SAV

24,00 €

42,00 €

5,5 %

Unit

22 products

Kit hydraulique 3 voies

ATL-KH3V-08

Atlantic

186,00 €

312,00 €

5,5 %

Unit

6 products

Vase d’expansion 12 L

GEN-VE12

31,00 €

58,00 €

5,5 %

Unit

41 products

Tube PER pré-gainé Ø16

GEN-PER16

2,40 €

4,60 €

5,5 %

Linear metre

28 products

Filtre magnétique

GEN-FM22

54,00 €

96,00 €

5,5 %

Unit

33 products

With argile

Your building price library, checked and kept up to date

Argile builds your price library from the catalogues of the brands you distribute: every product carries its price breakdown, equipment, labour and accessories, with technical specifications checked one by one and tariffs carried through at every range change.

Site tracking and site reports

With argile

The site report, filled in on site and exported as a PDF

Scheduling, progress, dated photos and snag clearing all feed the site report, exported as a PDF and attached to the customer record, while the end customer follows the same information from their own dedicated space.

ContractorsMay 22, 2026
Automatic air vent: avoiding air pockets in the network

An air pocket in a heating circuit costs you time on site. The right move is to plan ahead from the initial fill and to secure the venting to avoid noise, cold spots and customer callbacks. By mastering the high points and the simple gestures, you make the installation reliable without spending a whole day on it.

5 min read

Reveal your expertise

One demo, and you see your expertise proven.

Contact us