Blog/Underfloor Heating System Sludge Removal: Diagnosis and Treatment
Contractors

September 30, 2026

•

7 min read

•

Updated November 14, 2026

Underfloor heating sludge removal: diagnose at the manifold, treat loop by loop, prove the result

Underfloor heating is cleaned at the manifold, loop by loop: a water rinse, a sludge-removal chemical driven by a power flushing pump in both directions, a clean-water rinse, then a filter or sludge separator on the return and an inhibitor. It is also the four-step protocol of the French energy saving certificate sheet BAR-SE-108, which pays 23,600 kWh cumac for a house in climate zone H1 but excludes any loop heated wholly or partly by a heat pump and any installation above 70 kW.

Contents

Underfloor heating is cleaned at the manifold, loop by loop, in four successive steps: a water rinse, a sludge-removal chemical driven by a power flushing pump in both directions of flow, a clean-water rinse, then a filter or sludge separator on the return to the boiler and an inhibitor. In France this is the protocol that the energy saving certificate sheet BAR-SE-108 has ticked off step by step, with a flat rate of 23,600 kWh cumac for a house in climate zone H1. Two cases fall outside it: an installation above 70 kW, and any loop heated wholly or partly by a heat pump, which rules out a large share of recent underfloor systems.

Air or sludge: making the diagnosis at the manifold

An air lock is cured by bleeding

A cold loop with flow noise and a fluctuating flow meter at the manifold often means air. Isolate the other loops, open the manifold air vent and let the air out until the jet runs steady, then restore the working pressure. If the flow comes back and the loop heats up again, the diagnosis is made and there is no case for a flush. Repeated air ingress is dealt with by an automatic air vent at the high point and by finding the cause, often a cold pressure set too low.

A sludged system shows in the water and in the gaps between loops

A sludged system gives blackish bleed water, sometimes drawn to a magnet (magnetite), loops with a low flow despite open valves and a running pump, and return temperatures that drift apart from one loop to the next. Before concluding, rule out setting faults: a closed thermal actuator, a regulating valve that has been turned, a mixing valve or bypass set wrongly. Record the values loop by loop: they are your starting point.

Indicator read at the manifold Unit Air lock Sludged system
Loop flow rate on the flow meter L/min Fluctuates, recovers after bleeding Stays low after bleeding
Return temperature gap between loops K Limited to the bled loop On several loops, persistent
Appearance of the bleed water no unit Clear, with bubbles Blackish, magnetic particles

Flushing loop by loop at the manifold

Preparing: isolate the boiler and identify the loops

Stop the heat source and switch the pump off. Identify flow and return, label each loop (room, length if known) and note the setting of each flow meter before touching it, so that you can return to the balancing setting. Connect the power flushing pump to the manifold fill and drain valves, with an outlet ready for the effluent. How the manifold and its components work is covered in our article on the underfloor heating manifold.

Rinse, treat, rinse: the first three steps

First rinse with water, the whole system then each loop in isolation. Then inject the sludge-removal chemical, compatible with the pipes (PEX, multilayer) and the metals present (copper, brass, steel, the aluminium of a heat exchanger), and circulate it with the power flushing pump in both directions, whole system then loop by loop, at the dose and contact time on the product sheet. Finish with a clean-water rinse, loop by loop, until the water comes out clear. A rinse alone, or a chemical left in the circuit without a flushing pump, does not meet the BAR-SE-108 protocol.

Hydrodynamic or chemical: when to combine

The hydrodynamic route, water and air pulsed by the machine, quickly gets mobile sludge moving and is enough on a lightly loaded system. The chemical route loosens stubborn deposits and caked magnetite, at the cost of a longer rinse and effluent to dispose of. On a heavily fouled system the combination is the safest: hydrodynamic to clear, chemical to loosen what remains.

Situation found Preferred route Point to watch
Flow rates down, cloudy water but system responsive Hydrodynamic Check the flow holds after refilling
Blackish water, magnetite, gaps that come back quickly Chemical, then rinse Chemical compatibility with every metal
Heavily loaded system, loops almost blocked Hydrodynamic then chemical Temporary filtration during recommissioning

Refilling and proving the result

Filtration, sludge separator and inhibitor

Check the existing filter or sludge separator, or fit one on the return to the boiler where it can be reached for cleaning. Fill, bleed, then inject a corrosion inhibitor compatible with every material in the system, at the product manufacturer's dose. It is the fourth step of BAR-SE-108, and the one that stops the system reloading: a flush without inhibitor gets done again.

Reading the loops before and after

Bring the circuit back up to temperature and record, loop by loop, the flow rate and the return temperature, to compare with the starting values. Then rebalance at the flow meters, since unblocked loops do not go back to their design flow on their own: the method is in our article on balancing the heating system. These readings, photos of the sludge separator and the chemical references are the proof of the result and, where it applies, the certificate file.

Bringing it back up to temperature without exceeding 28 °C at the floor

A floor that heated poorly has often had its flow temperature raised to compensate. After the flush, go back to the original weather compensation curve: the French arrêté of 23 June 1978 caps the surface temperature of a heated floor at 28 °C at any point under design conditions (art. 35). A loop that still does not heat at a normal flow temperature has a problem other than sludge: design flow rate, loop length, controls.

Sludge removal and the French certificate sheet BAR-SE-108

What the sheet requires

BAR-SE-108 covers flushing the whole distribution system of an individual heating installation, in an existing residential building in mainland France, with a heat source of at most 70 kW. The four steps are successive and ticked on the certificate, and the installer issues a dated and signed document describing the steps, the heat source and its output, the number of emitters, the pipe material, the water volume and the chemicals used. The installer must hold a qualification covering the servicing, maintenance or operation of hydronic heating installations, from a list published by the ministry. These items are prepared from the power flush quote onwards, since the quote is what commits the operation.

Climate zone Single house Flat
H1 23,600 kWh cumac 12,200 kWh cumac
H2 19,700 kWh cumac 10,200 kWh cumac
H3 14,100 kWh cumac 7,300 kWh cumac

The flat rate is per dwelling: it depends neither on the floor area, nor on the number of loops, nor on the water volume. The conventional lifetime is 12 years, and the sheet applies to operations committed before 1 August 2030.

Excluded cases: heat pumps and communal systems

Since 1 August 2025, loops heated wholly or partly by an air-to-water, water-to-water, ground-to-water or hybrid heat pump are excluded. Underfloor heating on a heat pump is therefore flushed with the same protocol, but without certificates: say so on the quote rather than letting the client count on a grant. For communal systems, BAR-SE-109 was withdrawn by the arrêté of 5 February 2026, effective 9 February 2026, with no replacement sheet.

Key figures

23,600 kWh cumac

BAR-SE-108 flat rate for a house in climate zone H1

70 kW

Maximum rated output of the installation for BAR-SE-108

28 °C

Maximum floor surface temperature at any point (arrêté of 23 June 1978, art. 35)

Frequently asked questions

At the manifold, loop by loop, in four stages: a water rinse, of the whole system then loop by loop; a sludge-removal chemical compatible with the pipes and metals in the system, circulated by a power flushing pump in both directions, at the dose and contact time given on the product sheet; a clean-water rinse until the water runs clear; then checking or fitting a filter or sludge separator on the return to the boiler and injecting an inhibitor. Record flow rates and return temperatures per loop before and after to prove the result.

Share this article

Pierre-Louis Guhur

Pierre-Louis is CEO and co-founder of Argile. He holds a PhD in machine learning, written at Inria, and renovated a house with his own hands in 2017 before founding the company. On the blog he writes about what he implements in the software: the 3CL-DPE 2021 method, NF EN 12831 and building physics as a calculation engine has to handle them, assumption by assumption.

Further reading

Customers

/

Camille Martin

Details

Dwelling

Works plans

Quotes

Admin & finance

Quote no. D2026-0042

History

Analysis

Preview

Save

The property

Energy renovation

Information

4

The quote

5

Terms

Next step

The quote

No.

Description

Qty

Unit

Unit price excl.

Total excl.

VAT

Price incl.

1

Installing an air-to-water heat pump

Technical specifications of the heat pump (mandatory)

3 STILL TO FILL IN

Area heated by the heat pump (m²)

e.g. 120

Seasonal energy efficiency ηs (%)

e.g. 126

Controller class

I

II

III

IV

V

VI

VII

VIII

1.1

Installing an air-to-water heat pump

10 600,00 €

11 183,00 €

1.1.1

Air-to-water heat pump 14 kW

1,00

U

3600,00

3 600,00 €

5,5%

3798,00

B

I

U

Heat output +7 °C / +35 °C: 13.00 kW. Heat output -7 °C / +60 °C: 10.10 kW. Seasonal space heating efficiency (35 °C / 55 °C): 150 % / 117 %.

1.1.2

Heat pump fitting and commissioning

1,00

U

7000,00

7 000,00 €

5,5%

7385,00

Add a line

2

External wall insulation (EWI)

2.1

External wall insulation (EWI)

22 500,00 €

23 737,50 €

2.1.1

Polystyrene insulation, R of 3.7 m².K/W or above

120,00

M2

120,00

14 400,00 €

5,5%

15192,00

2.1.2

Insulation labour package

120,00

M2

75,00

9 000,00 €

5,5%

9495,00

Discount

-900,00 €

8 545,50 €

With argile

Flawless quotes, straight from the works plan

Equipment, labour and accessories come from the works plan, VAT applies line by line, grants are deducted from the amount due and the mandatory wording is already written: the quote goes out for signature without a proofread.

ContractorsMay 19, 2026
Underfloor heating screed: dry, flowing or cement screed

A screed over underfloor heating comes in three families: cement screed, flowing screed (calcium sulphate or cement) and dry screed with heat-spreader plates. Wet screeds cover the pipes by at least 30 mm for a flowing screed (CSTB, guide 3578_V4) and fall under traditional texts. Dry screed is covered by no traditional code and goes through the system's technical approval, which changes your insurance and your quotation. Here are the thicknesses, drying and heat-up times, the timber floor case and a typical cross-section layer by layer.

8 min read

ContractorsJune 11, 2026
Dual heating core radiators: premium electric heating

When a client wants fast, stable comfort without swings, you have every interest in proposing an emitter that combines a quick temperature rise with sustained gentle heat. On site, it also comes down to very concrete details, controls, thermal mass, noise, and ease of installation, the ones that avoid callbacks. With the right criteria in mind, you can steer clients towards a genuinely premium solution, suited to the room and the household's routine.

6 min read

Reveal your expertise

One demo, and you see your expertise proven.

Contact us