Underfloor heating is cleaned at the manifold, loop by loop, in four successive steps: a water rinse, a sludge-removal chemical driven by a power flushing pump in both directions of flow, a clean-water rinse, then a filter or sludge separator on the return to the boiler and an inhibitor. In France this is the protocol that the energy saving certificate sheet BAR-SE-108 has ticked off step by step, with a flat rate of 23,600 kWh cumac for a house in climate zone H1. Two cases fall outside it: an installation above 70 kW, and any loop heated wholly or partly by a heat pump, which rules out a large share of recent underfloor systems.
Air or sludge: making the diagnosis at the manifold
An air lock is cured by bleeding
A cold loop with flow noise and a fluctuating flow meter at the manifold often means air. Isolate the other loops, open the manifold air vent and let the air out until the jet runs steady, then restore the working pressure. If the flow comes back and the loop heats up again, the diagnosis is made and there is no case for a flush. Repeated air ingress is dealt with by an automatic air vent at the high point and by finding the cause, often a cold pressure set too low.
A sludged system shows in the water and in the gaps between loops
A sludged system gives blackish bleed water, sometimes drawn to a magnet (magnetite), loops with a low flow despite open valves and a running pump, and return temperatures that drift apart from one loop to the next. Before concluding, rule out setting faults: a closed thermal actuator, a regulating valve that has been turned, a mixing valve or bypass set wrongly. Record the values loop by loop: they are your starting point.
| Indicator read at the manifold | Unit | Air lock | Sludged system |
|---|---|---|---|
| Loop flow rate on the flow meter | L/min | Fluctuates, recovers after bleeding | Stays low after bleeding |
| Return temperature gap between loops | K | Limited to the bled loop | On several loops, persistent |
| Appearance of the bleed water | no unit | Clear, with bubbles | Blackish, magnetic particles |
Flushing loop by loop at the manifold
Preparing: isolate the boiler and identify the loops
Stop the heat source and switch the pump off. Identify flow and return, label each loop (room, length if known) and note the setting of each flow meter before touching it, so that you can return to the balancing setting. Connect the power flushing pump to the manifold fill and drain valves, with an outlet ready for the effluent. How the manifold and its components work is covered in our article on the underfloor heating manifold.
Rinse, treat, rinse: the first three steps
First rinse with water, the whole system then each loop in isolation. Then inject the sludge-removal chemical, compatible with the pipes (PEX, multilayer) and the metals present (copper, brass, steel, the aluminium of a heat exchanger), and circulate it with the power flushing pump in both directions, whole system then loop by loop, at the dose and contact time on the product sheet. Finish with a clean-water rinse, loop by loop, until the water comes out clear. A rinse alone, or a chemical left in the circuit without a flushing pump, does not meet the BAR-SE-108 protocol.
Hydrodynamic or chemical: when to combine
The hydrodynamic route, water and air pulsed by the machine, quickly gets mobile sludge moving and is enough on a lightly loaded system. The chemical route loosens stubborn deposits and caked magnetite, at the cost of a longer rinse and effluent to dispose of. On a heavily fouled system the combination is the safest: hydrodynamic to clear, chemical to loosen what remains.
| Situation found | Preferred route | Point to watch |
|---|---|---|
| Flow rates down, cloudy water but system responsive | Hydrodynamic | Check the flow holds after refilling |
| Blackish water, magnetite, gaps that come back quickly | Chemical, then rinse | Chemical compatibility with every metal |
| Heavily loaded system, loops almost blocked | Hydrodynamic then chemical | Temporary filtration during recommissioning |
Refilling and proving the result
Filtration, sludge separator and inhibitor
Check the existing filter or sludge separator, or fit one on the return to the boiler where it can be reached for cleaning. Fill, bleed, then inject a corrosion inhibitor compatible with every material in the system, at the product manufacturer's dose. It is the fourth step of BAR-SE-108, and the one that stops the system reloading: a flush without inhibitor gets done again.
Reading the loops before and after
Bring the circuit back up to temperature and record, loop by loop, the flow rate and the return temperature, to compare with the starting values. Then rebalance at the flow meters, since unblocked loops do not go back to their design flow on their own: the method is in our article on balancing the heating system. These readings, photos of the sludge separator and the chemical references are the proof of the result and, where it applies, the certificate file.
Bringing it back up to temperature without exceeding 28 °C at the floor
A floor that heated poorly has often had its flow temperature raised to compensate. After the flush, go back to the original weather compensation curve: the French arrêté of 23 June 1978 caps the surface temperature of a heated floor at 28 °C at any point under design conditions (art. 35). A loop that still does not heat at a normal flow temperature has a problem other than sludge: design flow rate, loop length, controls.
Sludge removal and the French certificate sheet BAR-SE-108
What the sheet requires
BAR-SE-108 covers flushing the whole distribution system of an individual heating installation, in an existing residential building in mainland France, with a heat source of at most 70 kW. The four steps are successive and ticked on the certificate, and the installer issues a dated and signed document describing the steps, the heat source and its output, the number of emitters, the pipe material, the water volume and the chemicals used. The installer must hold a qualification covering the servicing, maintenance or operation of hydronic heating installations, from a list published by the ministry. These items are prepared from the power flush quote onwards, since the quote is what commits the operation.
| Climate zone | Single house | Flat |
|---|---|---|
| H1 | 23,600 kWh cumac | 12,200 kWh cumac |
| H2 | 19,700 kWh cumac | 10,200 kWh cumac |
| H3 | 14,100 kWh cumac | 7,300 kWh cumac |
The flat rate is per dwelling: it depends neither on the floor area, nor on the number of loops, nor on the water volume. The conventional lifetime is 12 years, and the sheet applies to operations committed before 1 August 2030.
Excluded cases: heat pumps and communal systems
Since 1 August 2025, loops heated wholly or partly by an air-to-water, water-to-water, ground-to-water or hybrid heat pump are excluded. Underfloor heating on a heat pump is therefore flushed with the same protocol, but without certificates: say so on the quote rather than letting the client count on a grant. For communal systems, BAR-SE-109 was withdrawn by the arrêté of 5 February 2026, effective 9 February 2026, with no replacement sheet.



