Blog/Antifreeze and heat transfer fluid: solar circuit maintenance
Contractors

May 24, 2026

5 min read

Updated August 7, 2026

Solar heat transfer fluid: how to test it, dose it and decide on replacement

Solar heat transfer fluid is not a consumable you swap on a calendar: it is a product whose antifreeze concentration is capped at 50 % by the solar thermal reference standard, whose fresh pH sits between 9.0 and 10.5, and which decomposes above 200 °C while a stagnating collector can exceed that figure. Here are the four values to record on a service visit, the thresholds that trigger a drain, and what goes on the service record.

Contents

Solar heat transfer fluid is a mix of water and monopropylene glycol whose concentration must not exceed 50 %, a ceiling set by NF DTU 65.12 P1-2. Fresh, it shows a pH of 9.0 to 10.5 at 20 °C and a reserve alkalinity of at least 20 ml of 0.1 n HCl on manufacturer data sheets, and it is that reserve, not the colour of the liquid, which protects copper and stainless steel. It must not be exposed to sustained temperatures above 170 °C, and above 200 °C propylene glycol decomposes slowly, which shows as a darkening of the fluid. Collector stagnation temperature, as defined in EN 12975-2, can exceed 200 °C. What matters on a service visit is therefore not the age of the fluid but what it has been through.

What the reference standard actually demands of the fluid

Material compatibility and potable water classification

NF DTU 65.12 P1-2 treats the heat transfer liquid as a component in its own right. The fluid has to be compatible with the materials of the collectors and of the whole hydraulic circuit in order to limit corrosion risk, and to meet the requirements of guide ISO/TR 10217 on the pairing of fluids and materials in aerated and non-aerated circuits. Where an indirect circuit produces domestic hot water through a single heat exchange, the product introduced, neat or diluted, must carry the national health authority approval for use in thermal treatment installations for water intended for human consumption. That approval is evidenced on paper: it is a supply acceptance criterion, not a marketing claim.

An antifreeze concentration capped at 50 %

The wording is explicit: antifreeze concentrations must not exceed 50 %. The standard gives the technical reason, and it is worth repeating to a client. The higher the glycol content, the lower the heat transfer capacity of the exchanger and the higher the pressure drops. Overdosing buys freeze protection nobody needs while paying for permanently degraded solar output. The antifreeze fluid and its additives must also remain stable at the temperatures reachable in the installation, which points at stagnation rather than at rated operation.

The concentration is therefore not chosen at the permitted maximum, it is chosen against the site's design temperature. The freezing points below apply to a monopropylene glycol and water mix, read on a refractometer by volume.

Concentration by volume Freezing point What it means on site
25 % -10 °C Floor for the inhibitors to stay effective, sheltered mild locations
30 % -13 °C Mediterranean and Atlantic coastal exposure
35 % -17 °C Most temperate inland locations
40 % -21 °C Continental locations below altitude, the common reference value
45 % -26 °C Altitude and continental east
50 % -32 °C The NF DTU 65.12 ceiling, nothing is gained beyond it

The floor matters as much as the ceiling: below 25 %, the corrosion inhibitors are no longer concentrated enough to protect copper and stainless steel, even where the freezing point still looks sufficient. An off-the-shelf ready mix sits around 45 %, so roughly -28 °C, and that is the figure you record at commissioning as the reference for every later visit.

The temperatures each component has to survive

This is the point commercial literature glosses over, and the one that explains most of the degraded fluid you find on site. The ranges in NF DTU 65.12 P1-2 are not uniform across the circuit.

Component Operating range applied Watch point
Collector loop (pipework, fittings, pump, exchanger) -10 °C to +120 °C Maximum pressure tied to the safety valve setting
Expansion vessel membrane or bladder 70 °C in general Dictates vessel location and any upstream buffer volume
Air vent at collector level -10 °C to at least 150 °C 110 °C accepted where isolating valves are shut after venting
Collector in stagnation Can exceed 200 °C Value and working pressure (up to 10 bar) on the rating plate
EPDM type elastomeric insulation Up to 150 °C Mineral wool above, to the relevant insulation standard

Recording the fluid on site: four values, one decision

Freeze point: refractometer or hydrometer, never an estimate

The sample is drawn from the circulating liquid, and its first purpose is to confirm that the freezing point has held. Read it on a hand refractometer or on a hydrometer calibrated for propylene glycol and water. The raw figure says nothing on its own: it is compared with the commissioning record. A freeze point that has risen points to water make-up, so to a leak or a botched vent, not to ageing.

pH and reserve alkalinity: what really protects the circuit

pH is a late indicator. What neutralises the acids of degradation is the reserve alkalinity, measured in millilitres of 0.1 n hydrochloric acid to ASTM D 1121. While it holds, pH stays within the fresh product range. Once pH drops, the reserve is already spent and the circuit is running unprotected. That is why a pH read well below the quoted range is not corrected by a top-up: it is dealt with by a full drain.

Colour and deposits: reading darkening as a thermal record

A fluid that has gone dark is not dirty, it has been cooked. Manufacturer data sheets tie darkening explicitly to the slow thermal decomposition of propylene glycol above 200 °C. A brown liquid, together with sticky deposits on the strainer and flow meter, tells you the installation has stagnated repeatedly. Replacing the fluid alone will fix nothing: the cause has to be dealt with on the expansion vessel, the controls or the dissipation strategy.

Value Fresh product figure Method Decision
Freeze point Around -28 °C on a typical ready-to-use fluid Refractometer or propylene glycol hydrometer Drift from the commissioning record, look for a leak or water make-up
pH at 20 °C 9.0 to 10.5 Sample from circulation, pH meter Below the fresh product range, full drain
Reserve alkalinity At least 20 ml 0.1 n HCl (ASTM D 1121) Laboratory analysis on a sample The only measure that quantifies remaining corrosion protection
Antifreeze concentration 50 % maximum Refractometer Above that, degraded transfer and higher pressure drops
Appearance Clear, coloured by the tracer Visual on the sample Darkening, deal with the stagnation cause before refilling

Replacing the fluid: the trigger is not an interval

Why no defensible "every X years" exists

No scheme sets a replacement interval for heat transfer fluid. The servicing rule bears on the maintenance of the fluid characteristics, verified by sampling, not on an age. Two installations of the same vintage can be in opposite states depending on whether they have stagnated. Announcing a fixed interval exposes you twice: you invoice a pointless drain on a healthy system, and you let a system that needed attention in its second season run on.

The three triggers that hold up with a client

A decision to drain is defended on measurements, not on a calendar. A freeze point that has drifted from the commissioning record, a pH outside the fresh product range, a darkened liquid in the sample. Each of those three findings can be photographed, dated and filed. That file is what turns a drain into a justified job rather than a contested line on a quotation.

The inspection cadence to work to

Sensible practice, and the cadence published by the French energy agency, is a professional inspection every two years, with a useful annual collector check covering in particular the condition of the heat transfer fluid, and a cylinder clean recommended every three years to remove scale. There is no legal servicing obligation on collectors or cylinder. The case for the visit is therefore yours to build, and it stands better on circuit protection than on an imaginary obligation.

The job itself, from sample to recommissioning

Preparation: collectors covered, circuit cold, fluid recovered

The job is set up with cold collectors, early in the morning or under cover, controls off. Spent fluid is recovered in a sealed container, with no discharge to drain. The standard requires a filling device and forbids any direct connection between the heat transfer loop and the mains water supply. Bring the charging pump, a gauge, a refractometer, sampling kit, and label the valves before anything is stripped.

Draining, flushing, filling: the mistakes that earn a callback

Unless the collector data sheet says otherwise, the circuit is flushed several times before filling, and filling is done cold. The circuit must stay closed: contact with atmospheric oxygen accelerates the consumption of inhibitors. Two points come back in service calls. Internally galvanised exchangers, cylinders or pipes are ruled out, because zinc is attacked by propylene glycol and water mixtures. And chloride flux residues from soft soldering have to be flushed out, or you invite pitting corrosion on stainless steel. For residual air, work to the logic set out for the automatic air vent.

Top-up: demineralised water or original fluid, never the other way round

The rule is simple and routinely inverted on site. A loss through evaporation is made up with demineralised water, because only water evaporated. A loss through leakage or removal is made up with the original fluid, like for like, because the whole mixture left. Topping up a leak with water dilutes the antifreeze and the inhibitors at the same time. Once filled, repressurising follows the static height and the vessel precharge, which is covered in checking solar circuit pressure.

Recording the work and defending it on the quotation

What goes on the service record

The standard places servicing with the building owner and the work itself with the installer, the contract setting out what is covered. Your service record therefore carries the date, the values recorded (freeze point, pH, concentration, cold pressure), the exact fluid reference used, volumes added, the reason for the top-up, the condition of the air vents, vessel and safety valve, and photographs of the sample. It is the document that makes the next visit quick, and the only one that makes drift readable over time.

Where your liability sits

Filling with a fluid that does not match the collector manual, exceeding 50 % concentration, or refitting an expansion vessel where the membrane sees more than its rated temperature are departures from the standard. They show up in an expert inspection, and they shift a claim from the manufacturer warranty onto your insurance. Keeping the fluid reference, its potable water classification where domestic hot water is produced through a single exchange, and the commissioning record is what protects you.

Justifying the price against a cheaper quote

A competitor quoting a flat-rate drain without a sample is not selling the same job. You invoice a measurement, a documented decision, an identified fluid and a calculated refill pressure; they invoice a fill. The argument fits in one sentence in front of the client: without a freeze point and a pH reading, nobody can say whether the fluid needed changing, or whether the system was stagnating. Across a portfolio, that traceability also drives the choice between simply treating the fluid and reworking the architecture, which is where an integrated or separate backup is decided. The quote still has to say so: Argile builds the quote from the services and equipment selected, and applies VAT line by line.

Key figures

50 % maximum

Antifreeze concentration allowed by the reference standard

170 °C

Sustained temperature the fluid must not exceed

9.0 to 10.5

pH of fresh solar fluid at 20 °C

Frequently asked questions

NF DTU 65.12 P1-2, the French reference standard for glazed solar thermal installations, sets a hard ceiling: antifreeze concentrations must not exceed 50 %. Above that, heat exchanger transfer capacity falls and pressure drops rise, with no useful gain in protection. The concentration you run is read on a refractometer once the system is up to temperature, and it follows the fluid reference given in the collector manual rather than a generic product.

Share this article

Pierre-Louis Guhur

Pierre-Louis is CEO and co-founder of Argile. He holds a PhD in machine learning, written at Inria, and renovated a house with his own hands in 2017 before founding the company. On the blog he writes about what he implements in the software: the 3CL-DPE 2021 method, NF EN 12831 and building physics as a calculation engine has to handle them, assumption by assumption.

Further reading

Customers

/

Camille Martin

Details

Dwelling

Works plans

Quotes

Admin & finance

Quote no. D2026-0042

History

Analysis

Preview

Save

The property

Energy renovation

Information

4

The quote

5

Terms

Next step

The quote

No.

Description

Qty

Unit

Unit price excl.

Total excl.

VAT

Price incl.

1

Installing an air-to-water heat pump

Technical specifications of the heat pump (mandatory)

3 STILL TO FILL IN

Area heated by the heat pump (m²)

e.g. 120

Seasonal energy efficiency ηs (%)

e.g. 126

Controller class

I

II

III

IV

V

VI

VII

VIII

1.1

Installing an air-to-water heat pump

10 600,00 €

11 183,00 €

1.1.1

Air-to-water heat pump 14 kW

1,00

U

3600,00

3 600,00 €

5,5%

3798,00

B

I

U

Heat output +7 °C / +35 °C: 13.00 kW. Heat output -7 °C / +60 °C: 10.10 kW. Seasonal space heating efficiency (35 °C / 55 °C): 150 % / 117 %.

1.1.2

Heat pump fitting and commissioning

1,00

U

7000,00

7 000,00 €

5,5%

7385,00

Add a line

2

External wall insulation (EWI)

2.1

External wall insulation (EWI)

22 500,00 €

23 737,50 €

2.1.1

Polystyrene insulation, R of 3.7 m².K/W or above

120,00

M2

120,00

14 400,00 €

5,5%

15192,00

2.1.2

Insulation labour package

120,00

M2

75,00

9 000,00 €

5,5%

9495,00

Discount

-900,00 €

8 545,50 €

With argile

Flawless quotes, straight from the works plan

Equipment, labour and accessories come from the works plan, VAT applies line by line, grants are deducted from the amount due and the mandatory wording is already written: the quote goes out for signature without a proofread.

Energy renovationMarch 26, 2026
CO₂ (R744) heat pumps: the next revolution?

R744 is not a fluorinated greenhouse gas. It sits outside EU Regulation 2024/573, and therefore outside the quotas, the Article 5 leak checks and the Annex IV bans. What constrains it lies elsewhere: the high pressure of the transcritical cycle, the hot water temperatures set by the French order of 23 June 1978 as amended, and, since the French order of 21 November 2025, a category B company certificate, carbon dioxide having entered the scope of certification.

5 min read

ContractorsMarch 23, 2026
Installing heat-recovery ventilation: the method and the proof

A heat-recovery ventilation installation is judged on three things: the flow rates achieved, the power input and the evidence you leave behind. The rest is commerce. Here are the binding values of the decree of 24 March 1982, the ecodesign requirements to check before ordering, and the contents of a handover record that stands up to inspection.

5 min read

Reveal your expertise

One demo, and you see your expertise proven.

Contact us