Blog/DHW storage volume: sizing it tightly
Contractors

May 12, 2026

6 min read

Updated August 6, 2026

DHW cylinder volume: what the assessment method assumes and what it leaves out

The hot water demand used by the French EPC calculation method is not derived from the number of occupants but from the floor area, at 56 litres at 40 °C per equivalent adult per day. Regulation (EU) No 814/2013 separately sets minimum mixed water volumes by load profile. Here are both tables, the gap between conventional demand and real peak, and what oversizing costs in losses.

Contents

The French EPC calculation method does not derive hot water demand from the number of occupants. It works through a number of equivalent adults derived from the habitable floor area, then applies 56 litres at 40 °C per equivalent adult per day for conventional behaviour and 79 litres for high-consumption behaviour. Above 70 m², the occupancy coefficient is 0.025 times the floor area, which makes the demand saturate: a 140 m² house is credited with 2.275 equivalent adults, that is 127 litres a day at 40 °C. That figure exists to calculate a consumption, not to size a cylinder, and confusing the two is the most common error on this item.

What the assessment method takes as demand

Conventional demand is derived from floor area

The method first defines a maximum occupancy coefficient, equal to 1 below 30 m², to 1.75 − 0.01875 × (70 − area) between 30 and 70 m², and to 0.025 × area above that. The number of equivalent adults follows: it equals the occupancy coefficient while that stays below 1.75, and then becomes 1.75 + 0.3 × (coefficient − 1.75). The progression is therefore deliberately damped on large floor areas.

The resulting daily demand

Values calculated for a detached house, in litres of water at 40 °C per day.

Habitable floor area Occupancy coefficient Equivalent adults Conventional behaviour High consumption
40 m² 1.188 1.188 66 L 94 L
60 m² 1.563 1.563 88 L 123 L
80 m² 2.000 1.825 102 L 144 L
100 m² 2.500 1.975 111 L 156 L
120 m² 3.000 2.125 119 L 168 L
140 m² 3.500 2.275 127 L 180 L

The gap between the last two columns is 41 %, which gives the order of magnitude of the uncertainty the method itself accepts on this item.

What that demand is not

It is a daily average, spread over a year in which seven days are conventionally unoccupied. It is not a peak, nor a flow rate, nor a simultaneity. No cylinder is sized on that figure alone, and an assessor using it to validate a volume is working outside the method's intended use.

From demand to cylinder volume

Mixed water volume at 40 °C is not nominal volume

A cylinder advertised at 200 litres does not deliver 200 litres at 40 °C. Since the store runs hotter than the temperature in use, the mixing valve reconstitutes a volume larger than the nominal one by blending with cold water. The heat balance gives mixed volume equal to nominal volume times the ratio of the two temperature differences, with the cold water temperature being a monthly climate figure in the assessment method. That is a calculation identity, not a regulatory value: the figure that counts is the one the manufacturer declares.

The floors ecodesign sets

Point 1.3 of Annex II to Regulation (EU) No 814/2013 has imposed, since 26 September 2015, a minimum volume of mixed water at 40 °C according to the declared load profile.

Declared profile M L XL XXL 3XL 4XL
Minimum mixed water at 40 °C 65 L 130 L 210 L 300 L 520 L 1,040 L

These are a regulatory floor, not a sizing target. Their main use is comparing two units of the same profile, by reading the declared figure rather than the nominal volume.

The upper bounds on small profiles

Point 1.2 of the same annex caps the storage volume of the small profiles the other way: 7 litres at most in profile 3XS, 15 litres in XXS and XS, 36 litres in S. Those bounds concern isolated draw-off points, a sink or a hand basin, not a dwelling's main cylinder. The corresponding test cycles are covered in the article on DHW load profiles.

Sizing on the peak, not on the average

The peak is recorded, not deduced

The sizing parameter is the volume drawn during the peak, not the daily consumption. What gets noted during the survey comes down to four lines, recorded on the phone as the technician works through the visit.

  • Number of draws following one another with no recovery interval, morning and evening.
  • Simultaneous draws possible given the number of wet rooms.
  • Presence of a bath and how often it is actually used.
  • Acceptable delay for recovery between two peaks.

Recovery power is part of the equation

Two cylinders of the same volume are not equivalent if one recovers in two hours and the other in eight. The pair to record is volume and recovery time, taken from the unit's documentation across the room's temperature range. A generous volume compensates for slow recovery, and the reverse holds too; it is that trade-off which gets documented on the estimate.

The heat pump case

On a heat pump water heater, the available power varies with the temperature of the air drawn in. In an unheated room and in cold weather, recovery lengthens and the electric backup takes over, which cancels part of the benefit. The volume is then set to cover two closely spaced peaks without a restart, and the location is validated before the capacity is chosen.

What an oversized cylinder costs

Losses grow with volume

Annual storage losses from the assessment method, for a class C vertical unit, rounded to the nearest kWh.

Volume 100 L 150 L 200 L 250 L 300 L
Annual losses 403 483 644 725 870

Going from 200 to 300 litres "to be on the safe side" costs 226 kWh a year, every year, and it shows up in the assessment. That is the price of a margin that was never measured.

Format weighs as much as capacity

At equal volume, a horizontal cylinder is calculated with a markedly higher loss coefficient than a vertical one, which can cancel out the benefit of a well-chosen capacity. The quantified comparison appears in the article on the assessment storage-loss table, and the installation trade-off in the one on choosing between a vertical and a horizontal cylinder.

Footprint and maintenance

A larger volume increases the footprint, the weight when full and therefore the fixing requirements, and it sometimes pushes the cylinder further from the draw-off points. Each of those effects is paid for once at installation and again at every visit. Oversizing is not free insurance.

Validating the volume and documenting it

Handover tests

  • Extended draw-off test, volume delivered before the outlet falls below the target useful temperature.
  • Temperature measured at the cylinder outlet and at the furthest draw-off point.
  • Recovery time after a peak, timed.

The temperature limits that apply

National safety rules cap hot water at the outlets, in France at 50 °C in rooms intended for washing and 60 °C in other rooms, which makes a thermostatic mixing valve necessary as soon as the store runs hotter. The requirement to hold 55 °C permanently at the outlet only applies where total storage reaches 400 litres, which is rare in a single dwelling.

What goes on the estimate

Nominal volume, declared mixed water volume at 40 °C, load profile, cylinder format and stated recovery time. An estimate carrying only the capacity leaves the argument open at handover, whereas those five items close it. On the expected wording, see the mandatory information on a renovation works quote.

Key figures

56 L at 40 °C

Conventional demand per equivalent adult per day

130 L

Minimum mixed water at 40 °C in profile L

0.025 × area

Occupancy coefficient above 70 m²

Frequently asked questions

Because an assessment has to stay independent of who lives there. The French EPC calculation method works through a number of equivalent adults derived from the habitable floor area, then applies 56 litres at 40 °C per equivalent adult per day for conventional behaviour and 79 litres for high-consumption behaviour. That demand is there to calculate a consumption, and it does not replace a survey of real draws when sizing a cylinder.

Share this article

Louis Meneteau

Louis is CPO of Argile. An engineer by training, he spent four years validating calculation software in systems engineering, then three years in software product. He turns the installer's daily reality into product workflows: technical survey, sizing, quotes and subsidy files. His articles describe field gestures rather than principles, because he watches them on site before specifying them.

Further reading

With argile

The site visit that fills in the file for you

On a phone, the technician documents the home and the project job by job: surveys, photos, equipment positions and sizing confirmed on the spot, with nothing to re-enter back at the office.

ContractorsMay 30, 2026
Air Inlets and Extract Vents: Sizing Your MVHR System

When an MVHR system is properly sized, you notice it right away, less lingering humidity, odours that don't come back, and clients who breathe easier. But it all comes down to job-site details, air inlets, extract vents, and room-by-room airflow balance. Get these right at installation and you avoid callbacks while securing the home's performance, without the headache.

5 min read

ContractorsApril 19, 2026
Pellet silo: sizing and layout

Between available space, truck access and dust you'd rather avoid, fuel storage is often decided down to the centimetre. As a tradesperson, planning the usable volume, the flow slope and the feed path to the boiler from the start saves you time and callbacks. A few simple choices in the right place, and the installation becomes reliable, clean and easy to maintain.

5 min read

Reveal your expertise

One demo, and you see your expertise proven.

Contact us