Blog/DHW draw-off profiles: S, M, L and XL
Argile product

June 7, 2026

5 min read

Updated August 6, 2026

DHW tapping profile: the M, L, XL, XXL table from Regulation 814/2013

A tapping profile is a standardised draw-off sequence, not a marketing estimate. Regulation (EU) No 814/2013 defines ten of them, from 3XS to 4XL, each with its reference energy Qref and its maximum flow rate. The declared profile sets the water heating efficiency the appliance has to meet, and therefore what you can commit to on a quotation.

Contents

A tapping profile is a standardised draw-off sequence, defined in Annex III of Regulation (EU) No 814/2013, against which a water heater's energy efficiency is measured. Each profile carries a reference energy Qref: 2.100 kWh for S, 5.845 kWh for M, 11.655 kWh for L, 19.070 kWh for XL and 24.530 kWh for XXL. The measurement cycle runs for 24 hours with no draw-off between 00:00 and 06:59, then follows the declared profile's sequence from 07:00. The manufacturer declares either the maximum profile the appliance holds, or the one immediately below it.

What Regulation (EU) 814/2013 calls a tapping profile

The draw-off sequence, the 24-hour cycle and the declared profile

The profile is not a usage class, it is a test protocol. Annex III fixes the time of every draw, its useful energy Qtap, its flow rate f and the minimum useful temperature Tm, with a peak temperature Tp to be reached on certain draws. Measurements run over a 24-hour cycle with no draw before 07:00. An off-peak appliance receives energy over a maximum of 8 consecutive hours between 22:00 and 07:00. That framework is what makes two product fiches comparable.

The table of tapping profiles, from 3XS to 4XL

The ten profiles and their reference energy, as set out in Table 1 of Annex III. The maximum flow rate is the largest value of f found in the profile's sequence, and the heaviest draw its largest value of Qtap.

Profile Qref (kWh) Max. flow (l/min) Heaviest draw (kWh) Litres equivalent at 40°C
3XS 0.345 2 0.015 10
XXS 2.100 2 0.105 60
XS 2.100 3 1.05 60
S 2.100 5 0.525 60
M 5.845 6 1.4 168
L 11.655 10 3.605 334
XL 19.070 10 4.42 547
XXL 24.530 16 6.24 703
3XL 46.760 48 12.04 1,340
4XL 93.520 96 24.08 2,680

The last column is not in the regulation. It is a conversion, obtained by dividing Qref by 34.9 Wh, the energy needed to raise one litre of water from 10 to 40°C. It lets you talk in litres with a client without leaving the regulated value, provided the assumed cold water temperature is written on the calculation note.

What the profile does not say, and what the product fiche must

The profile gives neither the cylinder volume, nor the reheat time, nor the immersion or backup power. A 200-litre and a 300-litre appliance can carry the same declared profile if their heating dynamics differ. Storage volume is read separately on the product fiche, and the gap between stored litres and litres actually drawable is worked through in DHW storage volume.

Reading the profile on the energy label and the product fiche

Where the profile appears and what it drives

The declared tapping profile appears on the energy label and on the product fiche. It directly drives the water heating efficiency threshold the appliance has to meet: the requirements in Annex II of Regulation 814/2013 are indexed on the profile, not on the volume. The same measured efficiency can therefore be compliant in L and non-compliant in XXL.

Minimum water heating efficiency by profile

Since 26 September 2017, water heating energy efficiency may not fall below the following values.

Declared profile 3XS XXS XS S M L XL XXL 3XL 4XL
Minimum efficiency 32% 32% 32% 32% 36% 37% 37% 37% 37% 38%

These are market-entry minimums, not site targets. On a heat pump water heater the declared efficiency sits far above them, and that gap is what justifies the price difference against a cheaper direct electric cylinder.

The documents that carry weight in an inspection

Three documents are enough, provided they carry the exact commercial reference: the energy label, the product fiche with the declared profile and the measured efficiency, and the commissioning record with the settings taken. Brochures and sales material prove nothing. An appliance delivered under a reference close to but not identical to the quotation reopens the whole subject, including on the workmanship warranty covering the pipework.

Turning a declared profile into sizing on site

Survey the usage before inferring anything from the number of rooms

Room count does not predict demand. Record the number of occupants, the position of the draw-off points, whether the bath is genuinely used, and above all the morning simultaneity: two showers at once is not two showers in a row. Note the flow rate measured at the shower head, not the one printed on the box. The per-person consumption benchmark is worked through in DHW consumption per person.

Match the profile to the generator you have chosen

A direct electric cylinder recovers fast but costs a lot per kWh, so it is sized on volume. A heat pump water heater recovers slowly and only holds a high profile if the store absorbs the peak. A space heating heat pump with a DHW coil only holds its profile if DHW priority is actually configured and the available output at design temperature stays sufficient. On solar, the profile is held by the backup, never by the collector array.

Check the reheat time before adding volume

Adding litres costs in standing losses, in space and in price. Before moving up a profile, check the reheat time at the installation's real flow rate and the available backup power. An appliance that recharges in an hour covers a second peak that an oversized, slow-recovering appliance never will.

What the tapping profile does not cover

Multi-occupancy buildings, secondary return and distribution losses

Tapping profiles describe an appliance, not an installation. As soon as there is a secondary return, distribution losses add to the draw-off demand and are counted nowhere in Qref. In multi-occupancy buildings those losses are costed separately, and the orders of magnitude and reduction levers are covered in DHW secondary return.

The temperatures imposed outside the ecodesign framework

Approved Document G caps bath outlets at 48°C in new dwellings, while legionella control under HSE guidance L8 pulls the other way with storage at 60°C and 50°C reached at outlets within a minute. The two are reconciled by thermostatic mixing at the outlet, not by lowering the store. None of this is measured by the tapping profile, and it connects directly to legionella safety devices.

Profiles 3XL and 4XL, and peak flow rates

Profiles 3XL and 4XL reach 48 and 96 l/min of maximum flow, with single draws of 12.04 and 24.08 kWh. These are not domestic profiles: they describe appliances aimed at communal or commercial demand. An installer who sees them on a product fiche for a single dwelling should check they are not reading the documentation for a neighbouring range.

What you write on the quotation and at commissioning

Quotation lines and the wording that commits you

Put the exact commercial reference on the quotation, together with the declared tapping profile, the water heating efficiency and the storage volume, four values the product fiche carries and that a catalogue built on verified manufacturer specifications already holds. Add the thermostatic mixing valve, the safety group, the expansion vessel and, on a heat pump water heater, the condensate drain. A line reading "200 L cylinder" with no declared profile proves nothing and cannot be defended.

The settings recorded in the commissioning sheet

At commissioning, record the measured storage setpoint, the temperature at the least favourable outlet after mixing, the programmed thermal treatment cycle and its frequency, then the pressure at the reducing valve. Date it and have it signed. That document is what separates a setting you argue about from a setting you can prove, and it also limits how far a comfort complaint can go.

Framing the profile at the pre-visit stage with Argile

With Argile you qualify the dwelling before travelling: occupants, draw-off points, existing generator, siting constraints. You arrive on site with a tapping profile already set and costed work plans, then move to the quotation with the funding rules applied automatically. The time saved shows up in the number of visits converted, not in the length of the quotation.

Key figures

5.845 kWh

Qref of profile M

11.655 kWh

Qref of profile L

19.070 kWh

Qref of profile XL

Frequently asked questions

Not necessarily. Annex III of Regulation (EU) No 814/2013 lets the manufacturer declare either the maximum tapping profile or the one immediately below it. A cylinder sold as L may therefore hold XL without XL being declared, and a cylinder sold as L may equally be an appliance that holds nothing more. The only document that settles it is the product fiche, which carries the declared profile and the water heating efficiency measured with that profile.

Share this article

Louis Airy

Louis is COO of Argile. After four years in strategy consulting and close to two as chief of staff in home adaptation and reuse, he joined Argile in March 2024. In daily contact with certified renovation companies, he follows French energy saving certificates, renovation subsidies and reduced VAT, and revises the affected articles whenever a rate changes. What he writes is what he then checks against real quotes.

Further reading

Catalogues

/

Argile catalogue

/

Air-to-water heat pump

Argile catalogue

Add a product

Article base

Central articles, shared across all your equipment

Careful, this article is shared

This article is used in 14 products; any change will apply everywhere.

Name / Reference

Brand

Purchase cost

Selling price

VAT

Unit

Used in

Liaison frigorifique 5 m

ATL-LF05

Atlantic

68,00 €

119,00 €

5,5 %

Unit

14 products

Ballon tampon 25 L

ATL-BT25

Atlantic

142,00 €

245,00 €

5,5 %

Unit

9 products

Câble d’alimentation 3G2,5

GEN-C3G25

3,10 €

5,80 €

5,5 %

Linear metre

37 products

Support antivibratile

GEN-SAV

24,00 €

42,00 €

5,5 %

Unit

22 products

Kit hydraulique 3 voies

ATL-KH3V-08

Atlantic

186,00 €

312,00 €

5,5 %

Unit

6 products

Vase d’expansion 12 L

GEN-VE12

31,00 €

58,00 €

5,5 %

Unit

41 products

Tube PER pré-gainé Ø16

GEN-PER16

2,40 €

4,60 €

5,5 %

Linear metre

28 products

Filtre magnétique

GEN-FM22

54,00 €

96,00 €

5,5 %

Unit

33 products

With argile

Your building price library, checked and kept up to date

Argile builds your price library from the catalogues of the brands you distribute: every product carries its price breakdown, equipment, labour and accessories, with technical specifications checked one by one and tariffs carried through at every range change.

ContractorsMarch 31, 2026
Instant DHW heat exchanger system

When the goal is fast, stable hot water with no tank, installation quality makes all the difference. As a tradesperson, you control the points that prevent temperature swings and callbacks: real flow rate, pressure drop, scaling, settings. Here we go straight to practice, so you can size accurately and install cleanly on the first visit.

5 min read

ContractorsJuly 24, 2026
Smart thermostat and algorithmic learning

Good heating control is no longer just a fixed setpoint. On the job site, you can offer settings that adapt to the household's rhythms, free heat gains and weather variations, improving comfort without overconsuming. Understanding how the device "learns" and what data it uses helps you avoid vague promises, ask the right questions to the client and secure the commissioning.

5 min read

Reveal your expertise

One demo, and you see your expertise proven.

Contact us