Blog/Multi-split air-to-air heat pump: how many splits per home?
Contractors

March 28, 2026

5 min read

Updated August 6, 2026

Multi-split: how many indoor units per home?

With a multi-split system, the right number of indoor units is the one that matches the living spaces and usage patterns, not a one-size-fits-all rule. As a tradesperson, the challenge is simple: cover the right volumes without oversizing, while keeping the installation tidy, accessible and easy to balance. Starting from the floor plan, the gains and the installation constraints, you produce a clear quote and avoid callbacks.

Contents

The number of splits does not come from a watts-per-square-metre ratio but from a room-by-room heat-loss calculation, corrected for how the rooms are used: a bedroom closed off at night and an open-plan living space do not call for the same unit. In the field, a three or four-room home is usually handled with two indoor units, one per day and night zone, and a two-storey house with at least one unit per floor. Two ceilings then frame the project, both set by the manufacturer rather than by any regulation: the maximum number of indoor units per outdoor group, and the acceptable connection ratio. The SCOP thresholds, on the other hand, are regulatory: 3.9 for the French BAR-TH-129 certificate sheet, 4.00 for the A+ class that unlocks the 5.5% VAT rate in multi-split.

What determines the number of splits in a home

Floor area, volumes and insulation level: the basis of heat pump sizing

The number of splits starts from a heat-loss assessment. Even with an efficient heat pump, a high ceiling or average insulation increases the power to cover. You look at floor area, heated volumes, walls, windows and ventilation. The better the envelope is treated, the more you can reduce the number of units or choose smaller power ratings.

Living areas, bedrooms, closed-off rooms: sizing the need without over-equipping

Next, you break the need down by usage. An open living room can often be handled by a single well-placed split, while bedrooms with closed doors need dedicated diffusion or a small grouping. The goal is to avoid unnecessary over-equipping, which is costly and performs poorly in mid-season. When a zone is only heated occasionally, a different solution may be enough.

Quick answer

How many indoor units for this home?

The rules of thumb from the section above, applied to your case. The number moves with the partitioning and the number of floors, not with floor area alone.

Layout
Partitioning
Heated floors
Bedroom doors shut at night

Indoor units advised

2 units

Why that number

  • The baseline for the layout: one unit for the living space, and one on the sleeping side from two bedrooms up.

Refine it room by room with the configurator further down the article.

A first estimate, to be confirmed by a room-by-room heat-loss calculation.

An Argile tool

Installation constraints: line lengths, routing, condensate drainage

Finally, installation constraints settle the matter. Manufacturers set limits on the length and height difference of refrigerant lines. Attic runs, penetrations, the outdoor unit's location and condensate drainage determine how many splits are possible. Simple rule: the shorter and more accessible the path, the more robust the installation.

Sizing rules for a multi-split air-to-air heat pump (and mistakes to avoid)

Power per room: gains, heat loss and occupancy patterns

For an air-to-air heat pump, start room by room: that breakdown is what lets you place the indoor units on the plan and work out a coverage rate for each room. The right power depends on heat loss (insulation, air leaks, ventilation), but also on free gains (sun, cooking, occupants). Avoid the "so many W per m²" rule without checking actual occupancy. Doors closed at night, remote work during the day, a bedroom that's rarely heated. These patterns change the need.

Configurator

Sizing the multi-split, room by room

Describe the home room by room: the model derives the power of each indoor unit, the power of the outdoor unit, and checks the connection ratio between the two.

Start from an example
Insulation
Climate zone

Design temperature -7 °C

Ceiling height

2.50 m

The rooms

Floor area

32 m²

Exposure

2,246 W of heat loss

2.5 kW unit

Floor area

12 m²

Exposure

749 W of heat loss

2 kW unit

Floor area

11 m²

Exposure

824 W of heat loss

Heated by transfer

Indoor units

2

Connected power

4.5 kW

Design heat load

3.4 kW

Outdoor unit

4 kW

Connection ratio

113 %

Target 100 to 150 %

Oversized indoor units

A bedroom often asks less than the smallest unit in the catalogue. That is not a fault in itself, but do not count those extra kW as useful power: all they do is make the unit cycle.

A room without a unit loses more than a room with one

Transfer through the door does not close that gap. Either you equip it, or you accept a supplementary heater for that room.

Rounded teaching model, non-contractual. The final choice of outdoor unit and indoor units goes through the manufacturer’s technical data and selection software.

An Argile tool

Outdoor unit: limiting oversizing and undersizing in a multi-split system

In a multi-split system, the outdoor unit must cover the need at the coldest point, without falling into short cycling when demand is low. Too big, and the unit starts and stops, consumes more and wears out. Too small, and the setpoint isn't held and defrost cycles are noticeable. Respect the minimum and maximum ranges, and the connection ratio recommended by the manufacturer. For more, see the most common sizing mistakes.

Counter-intuitive

Why an oversized outdoor unit heats worse

The outdoor unit is sized for the coldest night of the year — a few hours. For the rest of the season it has to turn right down. Below its modulation floor it has one option left: start and stop.

Design heat load

4.0 kW

Outdoor unit

8 kW

Modulation floor

30 % of nominal

Indoor setpoint

19 °C

Climate zone
-10-5051015Outdoor temperature (°C)Outdoor unit

Season short-cycling

69 %

4,012 h a year below the floor

Season in deficit

0 %

0 h a year above the outdoor unit

Load

Modulation floor

Hours in the season

The outdoor unit spends most of the season below its floor

This is where the wasted energy and the wear come from: repeated starts for a load the machine cannot produce that small. Go down one size.

The heating season is modelled as a temperature distribution, not read from a real weather file. The order of magnitude holds; the individual hour does not.

An Argile tool

Balancing the splits: simultaneity, control and real comfort

The sum of the splits' power ratings isn't a simple "adder," and each indoor unit is set first against the cooling capacity worked out room by room. Think about simultaneity. The living room and bedrooms rarely demand 100% at the same time, but a peak is possible. Pay attention to controls, sensors, and per-zone setpoints to maintain real comfort without overheating one room while leaving another under-served.

Check

The connection ratio, live

The sum of the indoor units is not an adder: the outdoor unit is deliberately smaller, because the rooms never all call for 100 % at the same moment. The question is by how much.

Indoor units

Unit 1

3.5 kW

Unit 2

2 kW

Unit 3

2 kW

Outdoor unit

5.3 kW

Connected power

7.5 kW

Connection ratio

142 %

100 %150 %

Between 100 and 150 %: the working range

Real-world simultaneity is what makes that overshoot possible. The outdoor unit covers the whole-home load without being sized on the sum of every room’s peak.

Indicative range. Every manufacturer publishes its own in the technical data, and varies it by product line.

An Argile tool

How many splits by home type: field benchmarks

Studio and 2-room apartments: prioritize the main areas with a well-placed split

In a studio, a single split often suffices if the space is open. Place it to blow toward the living area, without aiming directly at the sofa. In a 2-room apartment, if the bedroom is closed off, a second split can avoid overheating the living room to gain comfort. With an air-to-air heat pump, insulation and solar gains quickly shift the need.

3- and 4-room apartments/houses: aim for the right compromise between comfort and budget

The most common field benchmark is 2 splits: one in the living area, one on the night side. You move to 3 if the home is a through-layout, heavily partitioned, or if a west-facing bedroom struggles in summer. The goal is a good balance without multiplying units unnecessarily.

Multi-story houses: managing temperature differences and air circulation

Upstairs, heat accumulates. Plan for at least one split per level, and pay attention to placement. A split in a landing helps, but doesn't replace diffusion in closed bedrooms. Also check for air leaks and ventilation. This is often where consistency is decided.

Choosing the right configuration: multi-split, mono-split or ducted

When a multi-split makes sense (and when it doesn't)

A multi-split is practical if you want to heat or cool several rooms with a single outdoor unit. It's often a good compromise in renovation, when each room has a different need. On the other hand, for a small home or rarely used bedrooms, the extra cost and line lengths can reduce the benefit.

One costing point not to miss: at equal performance, multi-split is treated more favourably than mono-split by French tax rules. The reduced VAT rate asks for class A++ in mono-split and only A+ in multi-split, for the same refrigerant and connectivity requirements.

Ducted: to treat several rooms without multiplying indoor units

A ducted system distributes air via ducts and diffusers, with a single indoor unit. The result is a discreet and even outcome. It makes sense if you have dropped ceilings or accessible attics. Plan for a well-insulated network and easy access for maintenance: on this point, see also insulating ventilation ducts in unheated attics.

Combining with a backup: stove, radiators, or another solution depending on the home

An air-to-air heat pump can cover most needs, but a backup secures very cold days or fast reheating. Depending on the building, keep a stove, a few controlled electric radiators, or another existing generator. The right choice comes after sizing and looking at actual room usage.

Points of attention in 2026: regulation, grants and site requirements

SCOP decides everything: the class scale and the thresholds

On a multi-split, a single figure drives the sales pitch, the energy certificates and the VAT rate at once: the SCOP for the average heating season, declared under Commission Delegated Regulation (EU) No 626/2011. Here is the official scale, together with the SEER that mirrors it on the cooling side.

Class SCOP (average season) SEER
A+++ ≥ 5.10 ≥ 8.50
A++ 4.60 to 5.10 6.10 to 8.50
A+ 4.00 to 4.60 5.60 to 6.10
A 3.40 to 4.00 5.10 to 5.60
B 3.10 to 3.40 4.60 to 5.10
C 2.80 to 3.10 4.10 to 4.60
D 2.50 to 2.80 3.60 to 4.10

Lower bounds included, upper bounds excluded. Classes E, F and G sit below a SCOP of 2.50.

Grants in 2026: energy certificates through BAR-TH-129 and 5.5% VAT

Air-to-air heat pumps are not on the list of equipment eligible for MaPrimeRénov'. They do have their own certificate sheet, BAR-TH-129, which requires no RGE quality mark: rated output of 12 kW or less, SCOP of at least 3.9, residential building more than two years old. And since 18 July 2026, the order of 13 July 2026 brings air-to-air heat pumps into the reduced rate set out in article 278-0 bis A of the French tax code, on supply-and-install. The criteria are detailed in our article on the 5.5% VAT rate applied to air-to-air heat pumps.

Requirement BAR-TH-129 certificates 5.5% VAT (≤ 12 kW)
Mono-split SCOP ≥ 3.9 class A++ (SCOP ≥ 4.60 and SEER ≥ 6.10)
Multi-split SCOP ≥ 3.9 class A+ (SCOP ≥ 4.00 and SEER ≥ 5.60)
Refrigerant not covered by the sheet compliant with Regulation (EU) 2024/573
Controls not covered by the sheet connection to a digital network required
Qualification "a professional" not covered by the order

F-Gas and competency certificate: what commits you on site

Working on the refrigerant circuit requires the competency certificate of article R. 543-99 of the French environmental code, issued for five years at most and per establishment. On the operating side, Regulation (EU) 2024/573 triggers leak checks from 5 tonnes of CO2 equivalent for Annex I gases, or 1 kg for those in section 1 of Annex II. In residential buildings, hermetically sealed equipment holding less than 3 kg is exempt, which takes a good share of domestic multi-splits out of scope. Above that, the frequency depends on the charge.

Equipment charge Without leak detection With a detection system
5 to 50 t CO2 eq. every 12 months every 24 months
50 to 500 t CO2 eq. every 6 months every 12 months
≥ 500 t CO2 eq. every 3 months every 6 months

Obligation

Leak checks: is this job covered?

The obligation is not triggered by the kilograms of refrigerant but by tonnes of CO₂ equivalent: the charge times the fluid’s global warming potential. Hence different answers for the same charge depending on the fluid.

Refrigerant
Total charge

3.0 kg

Hermetically sealed equipment
Permanent leak detection

Equivalent charge

2.0 t CO₂e

GWP 675

Leak check

Not required

Trigger threshold

5 t CO₂e

that is 7.4 kg of this fluid

Below the threshold: no periodic check

This is the usual case for a residential R32 multi-split. What still applies: the company’s certification, the tightness test and evacuation at commissioning, the intervention record and the logbook.

Regulation (EU) 2024/573, article 5. Periodic checks are one thing; the company’s certification, the tightness test at commissioning and the record keeping apply whatever the charge.

An Argile tool

Commissioning and settings: limiting callbacks (noise, condensate, comfort)

Most callbacks come from settings. Pay attention to anti-vibration mounts and clearances for noise: the French order of 30 June 1999 caps the normalised sound pressure level of individual heating or air-conditioning equipment at 35 dB(A) in main rooms and 50 dB(A) in the kitchen, a useful benchmark when arbitrating a location even where it does not strictly apply in renovation. Check condensate drainage, charge and tightness, then configure setpoints and time schedules. A simple client handover reduces calls and improves comfort.

Key figures

≥ 3.9

Minimum SCOP for energy certificates

A+

Class required in multi-split for 5.5% VAT

Frequently asked questions

Check the manufacturer's limits: total length, maximum length per circuit, and maximum height difference between units (values vary by brand and range). Beyond these, you risk performance loss, poor oil return and recurring failures. Also plan for accessible routing and condensate drainage with a slope or lift pump if needed.

Share this article

Pierre-Louis Guhur

Pierre-Louis is CEO and co-founder of Argile. He holds a PhD in machine learning, written at Inria, and renovated a house with his own hands in 2017 before founding the company. On the blog he writes about what he implements in the software: the 3CL-DPE 2021 method, NF EN 12831 and building physics as a calculation engine has to handle them, assumption by assumption.

Further reading

Camille Martin

/

Renovation plan

/

Air-to-air heat pump and solar PV

/

Air-to-air heat pump installation

Back

Air-to-air heat pump installation

Save this job

Home information

The works

3

Choosing the equipment

4

Works projections

Next step

Output required in winter

5,2 kW

Output in summer

4,1 kW

Details

Volume

163 m³

Winter design temp.

−7 °C

Summer design temp.

32 °C

Equipment

Switch to a kit

1 outdoor unit

Daikin

4MXM68A

Default

Output

6,8 kW

COP

4,10

SEER (cooling)

8,50

SCOP (heating)

4,60

Splits

4

Winter coverage

103%

Summer coverage

108%

Price excl. VAT

2 340 €

VAT

5,5 %

Price incl. VAT

2 468,70 €

4 indoor units

Daikin

FTXM25R

Located in the

Living room

Output

2,5 kW

Winter coverage

104%

Summer coverage

109%

Daikin

FTXM20R

Located in the

Home office

Output

2,0 kW

Winter coverage

101%

Summer coverage

106%

Daikin

FTXM20R

Located in the

Main bedroom

Output

2,0 kW

Winter coverage

98%

Summer coverage

104%

Add a unit

Labour

1 200,00 € TTC

1 item selected

Commissioning the air-to-air heat pump

Add labour

Accessories

486,30 € TTC

3 accessories selected

Wall bracket

Refrigerant line set

Power cable

Add an accessory

With argile

Size your air-to-air heat pumps room by room

Indoor units placed on the floor plan, coverage rate calculated for every room, equipment picked from up-to-date catalogues: Argile industrialises your reversible air conditioning projects.

ContractorsMarch 18, 2026
How to choose between an air-to-air heat pump and an air-to-water heat pump?

On a job site, the right heating choice often comes down to two simple questions. What level of comfort does your client expect, and what network already exists in the home, radiators, underfloor heating, or nothing at all. By asking the right questions from the site visit, you avoid bad surprises and protect your margin.

5 min read

ContractorsMay 8, 2026
Ducted air-to-air heat pump: heating and cooling the whole house

A ducted system comes down to three things the client never sees: the room-by-room heat-loss calculation that sets the flow rates, the acoustics at the diffuser, and access in the roof space or dropped ceiling for maintenance. Miss one of the three and handover turns into callbacks. Here is what you record on the technical visit, what you write on the quote, and what you log in the commissioning report.

5 min read

Reveal your expertise

One demo, and you see your expertise proven.

Contact us