The gauge on a wall-hung boiler shows the gauge pressure of the heating circuit, in bar, to be read with the system cold and the pump off. Wall-hung boiler manuals generally ask for at least 1 bar cold, a fill pressure between 1 and 2 bar, and a relief valve that opens at about 3 bar: these are manufacturer values, to be read on the appliance. French regulation sets no pressure for a hot-water heating circuit: the arrêté of 23 June 1978 caps the water temperature at 100 °C (art. 33) and requires fail-safe limit devices, independent of the controls and reset by hand only (art. 37).
What a boiler pressure gauge reads
Gauge pressure, read cold
The gauge measures the difference between circuit pressure and atmospheric pressure: 0 bar on the dial means a circuit open to the air. The reference reading is taken with the system cold, the pump stopped and the circuit bled. When hot, thermal expansion adds several tenths of a bar, and a running pump skews the reading depending on whether the gauge sits on its suction or its discharge side.
| Gauge reading | Value | Where the value comes from |
|---|---|---|
| Minimum pressure, system cold | 1 bar | Wall-hung boiler manuals |
| Fill pressure | 1 to 2 bar | Wall-hung boiler manuals |
| Maximum pressure when hot, relief valve opening | about 3 bar | Factory setting of the valve, plate and manual |
| Maximum heating water temperature | 100 °C | Arrêté of 23 June 1978, art. 33 |
These figures apply to a wall-hung boiler in a single house. A floor-standing boiler, a communal plant room or a wood boiler may carry a valve set differently: the plate on the valve is what counts, not habit.
Two pointers: the reading and the marker
On a two-pointer dial only one pointer is connected to the sensor, the one that moves when filling and heating. The other is moved by hand, with a bezel ring or a central knob, and measures nothing. Depending on the manufacturer, the marker is red and the reading black, or the other way round. Set the marker on the value read cold once the circuit is filled and bled: at the next visit, the gap between the two pointers shows whether the circuit has lost water without digging out the job sheet.
Fill pressure depends on the head of water
A tenth of a bar per metre
A 10 m column of water exerts 0.98 bar (ρ × g × h, with ρ = 1,000 kg/m³ and g = 9.81 m/s²). The height to use is between the gauge and the highest emitter. It is recorded during the site survey, together with the water volume of the system, since these are the two figures that size the vessel.
| Static head above the boiler | Pressure of the water column | What sets the fill pressure |
|---|---|---|
| 3 m (single storey, loft) | 0.3 bar | The 1 bar minimum in the manual |
| 5 m (one upper floor) | 0.5 bar | The 1 bar minimum in the manual |
| 8 m (two upper floors) | 0.8 bar | The height, with a margin above the vessel precharge |
| 12 m (block of flats, boiler on the ground floor) | 1.2 bar | The height; check there is still headroom below the 3 bar valve |
The expansion vessel follows the same height
Manuals set the vessel precharge to the static head of the installation above the appliance. A vessel factory-set for a two-storey house, fitted under a taller installation, stays pressed against its membrane and no longer does its job: pressure climbs to the valve when heating. The method for sizing the volume and the final pressure is covered in our article on sizing the expansion vessel.
Diagnosing from how the needle behaves
Always record the cold value, then the value at steady operation, and note the difference. It is that pair of values, not a single reading, that points to the diagnosis.
| Behaviour | Most frequent cause | Check to carry out |
|---|---|---|
| Climbs towards 3 bar when heating | Vessel undercharged, too small or membrane punctured | Vessel precharge, circuit at zero pressure |
| Falls slowly over several days | Leak at a fitting, air vent, valve or membrane | Traces at the valve tundish, air vents, tightness test |
| Climbs with the boiler off | Filling valve passing, punctured DHW heat exchanger | Filling valve closed and hose removed, then cold water isolated |
| Sudden drop after a heating cycle | Relief valve has discharged | Cause of the overpressure, state of the valve seat |
Pressure rises when heating
A rise of a few tenths of a bar between cold and hot is normal: it is the expansion of the water taken up by the vessel. When the needle approaches the valve, the vessel is no longer absorbing it: precharge too low, volume too small for the water content, or a punctured membrane. A system filled to 2 bar cold under a low head also leaves too little headroom.
Pressure falls slowly
A loss spread over hours or days points to a small leak: a fitting, an air vent with a leaking float, a valve dripping into its tundish, or a punctured vessel membrane (water at the valve). If nothing is visible, isolate the boiler and watch the pressure of the pipework alone, then carry out a system pressure test before looking for the leak in a chase or under the screed.
Pressure rises with the boiler off
With no heating, pressure can only rise if water is getting in. Close the filling valve, remove the filling loop or close the backflow preventer, and watch the pressure for thirty minutes. If it keeps rising, isolate the boiler's cold water supply: if it stabilises, the culprit is the DHW heat exchanger of a combi boiler, which lets mains water into the heating circuit.
Site checks and record keeping
Check the vessel with the circuit at zero pressure
The precharge is measured on the gas side, at the valve, with the water side at 0 bar. Isolate the vessel if it has a service valve, otherwise drain the boiler. A reading taken with the circuit full reads the water pressure through the membrane, and a vessel with no gas left looks correctly charged. Recharge to the static head, refill to the fill pressure, bleed, then confirm the rise when heating.
After the relief valve has discharged
A valve that has opened empties part of the circuit and may keep debris on its seat. Check that it closes and stops dripping into the tundish, find the cause of the overpressure (vessel, fill pressure, filling valve left open), then set the precharge and the cold pressure before restarting. If air got in during the drop, bleed the high points: the automatic air vents on manifolds and on the highest emitters are the first to check.
What to record
On the job sheet, note the cold pressure before and after, the operating pressure, the precharge measured and the precharge set, and the static head used. These are the values that let you tell a leak from a vessel losing its charge at the next visit or on a call-back. For monitoring over time, see our article on the gauge and circuit pressure.
The most common setting mistakes
Setting the pressure when hot
A pressure adjusted while heating includes the expansion. As the system cools, it drops below the intended value, sometimes below the static head: the high point goes into negative pressure, draws air through the vents and the pump cavitates. Always set it cold, after bleeding, then check the variation when hot to judge the vessel.
Mixing up pressures
Heating circuit pressure is that of a sealed circuit, read on the boiler gauge. Cold water pressure is that of the mains, often much higher and held by a pressure reducer. A combi boiler carries both circuits: before opening a valve, identify which circuit the gauge is on and which component you are turning, as one wrong quarter turn is enough to make the relief valve discharge.




