HHV and LHV: definitions, efficiencies and billing (HHV vs LHV)

HHV (higher heating value) includes the heat recovered by condensing the water vapour in flue gases, whereas LHV (lower heating value) excludes it, which is why HHV is always higher than LHV. For natural gas, the amended order of 22 December 1978 governs billing on the basis of HHV, while boiler efficiencies are most often quoted on an LHV basis in France. That is why a condensing boiler can show 105% on LHV without exceeding 100% on HHV. In practice, keep the trade rule of thumb in mind: HHV ≈ LHV + 10% for gas, to be checked against the gas quality certificate and the calculation basis used in the quote.

Contents

Understanding the HHV vs LHV difference: simple definitions and units

HHV: what you count when all the water vapour condenses

HHV, the higher heating value, corresponds to the energy released by combustion including the heat that can be recovered if the water formed in the flue gases is brought back to a liquid state. In plain terms, you add the latent heat of condensation. This is the basis used when you reason in terms of “total condensation”, typically to express the delivered energy of a fuel.

LHV: the basis most commonly used to talk about efficiency in France

LHV, the lower heating value, excludes that condensation heat. In the field, most boiler efficiencies are expressed on an LHV basis. That is why a condensing boiler can show > 100% on LHV without “creating” energy. When you are asked about the HHV vs LHV difference, the key issue is mainly to check which basis is used on the technical datasheet, the quote and the commissioning report.

Heating value, kWh, MJ: speaking the same language on site and on paper

Heating values are generally expressed in kWh/kg, kWh/Nm³ or MJ/kg. Remember the equivalence 1 kWh = 3.6 MJ. On documents, always specify the unit and the basis (HHV or LHV) to avoid distorted comparisons between calculations, gas bills and claimed efficiency. For more detail, see our article on fuel conversion ratios.

The physical HHV/LHV difference: latent heat and combustion flue gases

Where the gap comes from: water vapour in flue gases and latent heat of condensation

The HHV vs LHV difference comes from a simple physical point. Combustion produces CO2 and, above all, water vapour in the flue gases, formed from the hydrogen in the fuel and, depending on the case, its moisture content. HHV includes the energy that can be recovered if this vapour condenses and releases its latent heat. LHV does not include this recovery; it assumes the vapour is exhausted without condensation.

What a condensing boiler recovers, and what it does not create

A condensing boiler recovers part of that latent heat by lowering flue-gas temperature below the dew point, using a heat exchanger and a sufficiently cool heating return. It does not “create” energy. Efficiencies above 100% appear only when efficiency is expressed on an LHV basis, which is common practice in French technical data.

When the gap increases: hydrogen-rich fuels, moisture and operating conditions

The HHV/LHV gap increases with hydrogen-rich fuels (natural gas, LPG) and with moisture content (wood, pellets, biogas). On site, actual recovery also depends on operating conditions. If the return temperature is too high or excess air is significant, condensation becomes marginal: this is exactly what a combustion analysis helps you verify.

2026 table: HHV/LHV ratio for common fuels (benchmarks for your calculations)

Fuel HHV/LHV ratio Site benchmark
Natural gas 1.10 to 1.12 Billing often on HHV, efficiency often on LHV
Propane 1.08 to 1.09 Stable benchmark, useful for sizing calculations
Butane 1.08 to 1.09 Close to propane, pay attention to supplier units
Heating oil ≈ 1.06 Smaller gap, but basis still needs to be stated in your notes
Wood (dry) ≈ 1.08 Highly sensitive to the actual moisture content of the fuel

Natural gas: order of magnitude of the ratio and points to watch with supplier indexing

For gas, the HHV vs LHV difference becomes obvious as soon as you compare boiler performance and a bill. Note the basis used in the contract and in the kWh indexing. In the field, keep one reference basis in your statements and convert everything else.

Propane/butane: useful benchmarks for heating and domestic hot water

The ratio is less variable. In quotes and calculation notes, lock down the unit (kg, L, kWh) and the HHV or LHV basis. That is what avoids discrepancies in consumption estimates and supporting documents.

Heating oil and wood (logs/pellets): effect of moisture and cautions when interpreting data

For heating oil, the HHV/LHV gap is moderate. For wood, it is the opposite. As moisture rises, LHV drops. State the moisture assumption and avoid comparing efficiencies or energy costs without specifying the HHV/LHV basis. For more detail, see actual fuel moisture content.

Boiler efficiencies: why you sometimes see more than 100% (with no physical trick)

Efficiency expressed on LHV: the French convention and what it implies

In France, boiler efficiencies are often quoted on an LHV basis. This basis does not count the latent heat of the water vapour contained in the flue gases. A condensing boiler recovers part of it through the heat exchanger. The displayed efficiency can therefore exceed 100% on an LHV basis, without any energy being created. On an HHV basis, it remains mechanically below 100%.

Converting an efficiency from LHV to HHV: method and concrete condensing example

The conversion is straightforward. ηHHV = ηLHV × (LHV/HHV). For natural gas, the LHV/HHV ratio is around 0.90 depending on gas quality.

LHV (kWh/Nm³) HHV (kWh/Nm³) LHV/HHV (1) Efficiency on LHV (%) Efficiency on HHV (%)
10.35 11.65 0.89 108 96

Avoiding the sales mistake: explaining to the customer what “> 100%” means

In quotes, state the expression basis and keep it consistent between offers. If you compare against a gas bill, remember that delivered energy is on an HHV basis. When the discussion turns to the HHV vs LHV difference, translate it immediately into HHV versus LHV. It is a matter of convention and latent heat recovery, not a physical efficiency above 100%. To also frame the contractual side for the customer, you can rely on a clear boiler maintenance contract.

Billing and quotes: securing your HHV/LHV comparisons across documents

Gas bill in 2026: energy billed on HHV (coefficients, conversion to kWh)

In 2026, a gas bill expresses energy in kWh from a volume in m³, corrected and multiplied by a conversion coefficient based on HHV. Record the coefficient (kWh/m³) and its validity period. This is the reference when you cross-check with an audit or a consumption estimate.

Item Unit Where to find it
Consumed volume m³ Meter reading line
Conversion coefficient kWh/m³ Calculation breakdown
Billed energy kWh Total energy

Quotes, manufacturer manuals, audits: spotting whether values are on HHV or LHV

In quotes, manuals and audits, look for the calculation basis. Mentions “on LHV” or “on HHV”, or the notations Hi (LHV) and Hs (HHV). Quoted efficiencies can exceed 100 only on LHV. Without a written basis, the HHV vs LHV difference can trip you up between documents.

  • Write the basis in the line item title, not in a footnote.
  • Align the units in your work schedule, kWh LHV or kWh HHV, and then keep the same basis everywhere.

Practical case: comparing an estimated consumption (LHV) with an actual bill (HHV)

Audit at 12,000 kWh LHV, bill at 13,300 kWh HHV. Before drawing conclusions, bring everything onto the same basis. For natural gas, an HHV/LHV ratio of around 1.11 gives a quick conversion. Simple conversion: 12,000 × 1.11 = 13,320 kWh HHV. You can then compare properly with the bill.

Key figures

1 kWh = 3.6 MJ

Energy equivalence

> 100% (on LHV)

Displayable efficiency

2

HHV and LHV: calculation bases

Frequently asked questions

Look for the explicit wording “on LHV” or “on HHV”, sometimes abbreviated LHV (lower heating value) and HHV (higher heating value). If it is not stated, ask for an extract from the manufacturer’s manual or the technical data page, and enforce the same basis in your quote and commissioning report so you are comparing like with like.

Share this article

Pierre-Louis Guhur

Pierre-Louis is CEO and co-founder of Argile. He holds a PhD in machine learning, written at Inria, and renovated a house with his own hands in 2017 before founding the company. On the blog he writes about what he implements in the software: the 3CL-DPE 2021 method, NF EN 12831 and building physics as a calculation engine has to handle them, assumption by assumption.

Further reading

ContractorsJune 22, 2026
Structural Junctions in Renovation: The Details That Make the Difference

In renovation, the junctions between walls, floors, and window openings often make the difference between a "clean" job and one that comes back to haunt you six months later. By getting these details right from the site visit onward and coordinating them across your trades (insulation, airtightness, finishes), you secure performance, comfort, and above all your own peace of mind. Here we go straight to the point — the checks to run and the mistakes that cost dearly.

5 min read

Energy renovationApril 13, 2026
Radon and renovation: understanding and mitigating this natural risk

Radon kills 2,500 to 3,000 people a year in France. Dosimeter measurement, slab airtightness, redesigned ventilation and SSD: the technical levers to master during renovation.

6 min read

Energy renovationApril 9, 2026
GCV/NCV: understanding the fuel conversion ratio

On a quote or an audit, the same gas can display two calorific values, and the gap is not a minor detail. GCV and NCV change the result, so your billed kWh, your stated efficiencies and your comparisons between solutions. By mastering the conversion ratio, you secure your pricing and avoid endless arguments at the end of a job.

5 min read