Heat pump weather compensation: heating curve setup (field method 2026)

On a heat pump, weather compensation is adjusted by first aiming for the lowest possible flow temperature that still delivers comfort, then fine-tuning the curve in small steps. In practice, you start from ADEME reference points: underfloor heating around 30 to 35 °C at 0 °C outdoor temperature, low-temperature radiators around 45 to 55 °C, high-temperature radiators around 60 to 70 °C, then you correct the slope if it overheats in cold weather and the parallel shift if it drifts in mid-season. The ADEME guide “How to choose your heat pump” also reminds you that the lower the flow temperature, the higher the COP, giving you a point to note on commissioning and to use in an inspection.

Contents

Understanding heat pump weather compensation without staying theoretical

On a heat pump, the heating curve sets the target flow temperature from the outdoor temperature. In practice, the control calculates a flow setpoint and modulates the compressor and circulator to hold it, rather than waiting for a thermostat to cut out. That is the core of a well-tuned heat pump weather compensation setup: stable and with little cycling.

The 2 settings you need to know on the control: slope and parallel shift (offset)

The slope defines how quickly the flow setpoint rises as outdoor temperature falls. The parallel shift moves the whole curve without changing its shape. During commissioning, correct the offset first if the error is uniform, then adjust the slope if the fault only appears in deep cold or in mid-season.

What you must check before touching the curve: sensors, flow rates, balancing, hysteresis

  • Sensors: consistency of outdoor, flow and return temperatures. Location, insulation, calibration.
  • Flow rates: filters, air removal, circulator. Flow/return ΔT consistent with the emitter.
  • Balancing: valves, manifolds, pressure losses, end-of-loop emitters.
  • Hysteresis: dead band and time delays, to avoid hunting and short restarts.

Choosing a coherent heat pump heating curve based on your emitters and the building fabric

High-temperature radiators vs low-temperature radiators: direct impact on the curve

Emitter Typical flow temperature in design cold weather (°C) Curve setup
High-temperature radiators 55 to 70 Steeper slope, higher base
Low-temperature radiators 35 to 50 Moderate slope, lower base

On a heat pump weather compensation setup, the emitter sets the realistic flow-temperature ceiling. If you target a flow temperature that is too high for an undersized radiator, you increase the slope, lose COP, and end up relying on backup heat.

Underfloor heating: limiting flow temperature and protecting comfort (and the screed)

Aim for a low, stable flow temperature. In practice, 25 to 35 °C covers most cases. Fit a flow-temperature limiter (control or mixing valve) and keep a low slope; otherwise you will quickly overheat the screed’s thermal mass and the system will start hunting.

Insulation level and thermal inertia: how they change slope and responsiveness

The better insulated the building, the flatter the curve can be. You reduce the slope and fine-tune the base of the curve. In a lightweight house, make small corrections and record your readings (outdoor temperature, flow temperature, return temperature, room temperature) over 24 hours before touching the slope. For more detail, see the heating curve as a function of outdoor temperature.

Heat pump weather-compensation setup: step-by-step commissioning procedure on the control

Quick starting point: the manufacturer’s “standard” curve + flow-temperature limits

Start from the manufacturer’s “standard” curve. For heat pump weather compensation, set the limits straight away. Set a max flow temperature that matches the emitter (underfloor heating, radiators) and a minimum flow temperature that prevents short cycling in mid-season. Also check that the outdoor sensor is enabled and that there is no parasitic compensation from an overly aggressive room setpoint.

Adjustment method over 48 to 72 hours: one change at a time, at the right time

Work with two levers. First the slope, to correct cold-weather performance. Then the parallel shift, to reset the overall level. Change only one parameter at a time, then let the system run for 48 to 72 hours with comparable weather. Make changes during stable conditions, outside domestic hot water recovery periods, and monitor compressor cycles and run time.

How to log your trials (2026): outdoor temp, flow temp, room temp, cycles and customer feedback

Keep a single log sheet. Record date, time, outdoor temperature (sensor), target and measured flow temperature, return temperature, room temperature (one reference point), number of starts, run time, events (defrost, domestic hot water). Add a daily note of customer feedback (too hot, too cold) without changing the setpoint on the fly.

Correcting an installation that is overheating: diagnose first, then adjust the curve

Site symptoms: rooms too warm, surging, short cycling, water noise

On site, overheating shows up as a flow temperature that stays too high for the current outdoor temperature. Record outdoor temperature, flow temperature, return temperature, pressure, circulator speed, emitter condition, and start frequency. Surging and water noise often point to a control setting that is too “high” or unstable flow in heat pump weather compensation.

Priority actions: lower the parallel shift before reducing the slope

Start by lowering the parallel shift. You move the whole curve down without changing how it reacts to cold weather. Wait for stabilisation before touching the slope, otherwise you stack two effects and lose track of the diagnosis.

Setting Change per trial (unit) Wait before re-measurement (h)
Parallel shift -1 to -2 (K) 12 to 24
Slope -0.05 to -0.10 24
Anti-cycle delay +5 to +10 (min) 0 to 1

Common cases: oversized radiators, closed thermostatic valves, flow too low

With oversized radiators, keep a moderate slope and look for the lowest stable flow temperature. With thermostatic valves closed, leave one “reference” circuit open, or a bypass, otherwise the heat pump will cycle. With flow too low, check the filter, venting, isolation valves and balancing, then verify the flow rate via the flow/return ΔT. A very high ΔT often indicates insufficient flow.

Correcting an installation that is not reaching temperature: restore comfort without killing COP

Identify whether the issue comes from the heat pump weather-compensation curve or from a limit (max flow temp, power curve)

Start by getting objective data. Compare the flow temperature requested by the controller and the temperature actually achieved. If the calculated setpoint rises but the heat pump tops out, look for an active limit. Max flow temperature set too low, power curve limiting compressor output at low outdoor temperatures, or insufficient flow causing the delta T to rise and triggering safety cut-outs.

  • Record over 30 minutes. Outdoor temperature, flow, return, compressor %.
  • Check whether the demand matches the heat pump weather-compensation curve.

Raising the slope or the offset: choosing the right lever based on weather and inertia

If the lack of heat only appears when it is cold, adjust the slope. If it is constant, work on the offset. Make short changes, then let the system stabilise according to its inertia. Underfloor heating, be patient. Radiators, response is quicker. Keep the objective in mind: the lowest possible flow temperature to preserve the real COP.

Other points to check in parallel: defrost, backup heat, DHW curve, scheduling and setpoint

Before blaming the curve, check what is stealing kilowatts. Too-frequent defrost cycles, domestic hot water priority that stretches heating phases, backup heat disabled or, conversely, overactive, and time schedules that drop the setpoint at the wrong time. Also validate the room sensor, outdoor sensor and reduced-mode setpoints.

Key figures

55-70 °C

Radiator flow temperature HT

35-50 °C

Radiator flow temperature LT

25-35 °C

Underfloor heating flow temperature

Frequently asked questions

Take 24-hour readings of outdoor temperature, flow and return temperatures, and room temperature, ideally over two periods (mid-season and cold weather). At the same time, check the flow/return ΔT, generally 5-10 °C for radiators and 3-5 °C for underfloor heating; an inconsistent ΔT throws off any curve adjustment.

Share this article

Louis Meneteau

Louis is CPO of Argile. An engineer by training, he spent four years validating calculation software in systems engineering, then three years in software product. He turns the installer's daily reality into product workflows: technical survey, sizing, quotes and subsidy files. His articles describe field gestures rather than principles, because he watches them on site before specifying them.

Further reading

ContractorsApril 13, 2026
Heat pump and outdoor temperature: the heating curve

When the outdoor temperature drops, that's often when your clients judge comfort… and when the settings make all the difference. By mastering the logic behind varying the heating-water temperature with the climate, you save time on call-outs, cut down on 'it's not heating' calls, and secure consistent consumption. A few simple reference points are enough to get it right from commissioning.

5 min read

ContractorsJuly 20, 2026
Heat pump refrigerant connection: the rules for brazing

Three things are settled on a refrigerant line before the torch is lit: the filler metal, which follows the parent metals and not habit; the nitrogen purge, which decides whether oxides end up in the expansion valve; and the regulatory status of the circuit, since an assembly brazed on site is not hermetically sealed equipment. That last line moves the leak check threshold from ten tonnes of CO₂ equivalent down to five.

5 min read

ContractorsJuly 13, 2026
Heat pump manufacturer warranty: what's covered and what isn't

When a heat pump breaks down mid-project, it's not just a technical hiccup. It's lost time, a worried client, and sometimes a bill that lands on the wrong side of the ledger. To avoid unpleasant surprises, you need to know precisely what's covered, for how long, and what can be refused depending on maintenance, installation, or the parts involved.

5 min read

Reveal your expertise

One demo, and you see your expertise proven.

Contact us