Wood lambda: thermal conductivity for walls and roofs (references and impacts in 2026)

For your wall and thermal bridge calculations in timber framing, keep in mind that the thermal conductivity of common dry timber typically ranges from around 0.12 to 0.18 W/m.K for softwoods and can rise to around 0.18 to 0.25 W/m.K for denser hardwoods. The tabulated values to use in quotations and calculation justifications are those in NF EN ISO 10456 (hygrothermal data for building materials) and, depending on the method, the tables associated with NF EN ISO 6946 for calculating the thermal resistance of building elements. In practice, lambda varies mainly with density and moisture content, and it is higher parallel to the grain than across it, which explains why framing can significantly degrade the average performance of a wall or roof; hence the value of continuous insulation or cross-insulation.

Contents

Understanding wood lambda and avoiding the trap: wood is not an insulator

Simple definition: thermal conductivity (λ) of wood and the units to remember

Material Thermal conductivity λ (W/m.K) Order of magnitude
Wood (solid, dry) 0.10 to 0.20 Structural material
Common insulation (mineral wool) 0.032 to 0.040 Site reference

Wood lambda is thermal conductivity. The lower λ is, the more the material resists heat flow. In a calculation, you work in W/m.K, not by “feel”.

Why you cannot give a single value: density, moisture content, species and grain direction

λ varies mainly with density and moisture content. At higher bulk density, conductivity increases. When wood takes up water, λ also increases. Add grain direction. Conductivity is higher along the grain than across it. For a defensible calculation, start from tabulated values and record the moisture assumption used.

When you really need it: wall calculation, framing, thermal bridge

You need it as soon as the framing becomes part of the equivalent resistance. A stud at 0.13 W/m.K is several times more conductive than the insulation between studs. The wood fraction degrades average performance. That is why cross-insulation or continuous external insulation is valuable, and why it should be quantified and justified on your construction drawings. To go further on the subject, also see thermal bridges.

Wood lambda: value ranges by family (softwoods and hardwoods) and factors that create differences

Softwoods: orders of magnitude and variation by density (pine, spruce, fir, Douglas fir…)

Family Density at 12% (kg/m³) Typical transverse λ (W/m.K)
Light softwoods (spruce, fir) 350 to 450 0.10 to 0.13
Denser softwoods (pine, Douglas fir) 450 to 600 0.12 to 0.16

For framing, keep in mind that wood lambda mainly follows density. For a given species, a change in bulk density or moisture content is enough to shift the value used in the calculation.

Hardwoods: orders of magnitude and variation by density (oak, beech, poplar…)

Family Density at 12% (kg/m³) Typical transverse λ (W/m.K)
Light hardwoods (poplar) 350 to 450 0.11 to 0.14
Dense hardwoods (beech, oak) 650 to 800 0.16 to 0.22

In practice, dense hardwoods push λ upward. In an element, the penalty becomes obvious as soon as the wood fraction increases in the resistance path.

Moisture and grain orientation: longitudinal λ higher than transverse λ

Factor Effect on λ Order of magnitude
Moisture content λ increases with bound and free water +10 to +30% depending on water content
Grain orientation Longitudinal λ > radial/tangential λ x2 to x3

For a defensible calculation, rely on tabulated values (reference conditions and grain direction). Never treat wood as an insulator; it is a structural material.

Tabulated values and defensible calculations: where to take the correct wood lambda in 2026

Why prioritize reference tabulated values rather than “internet” values

For a defensible calculation (RE2020 study, inspection justification), start from tabulated values taken from recognized standards and reference documents. “Internet” values often mix species, densities and moisture contents. The result is an overly “optimistic” wood lambda and an overestimated wall performance. In practice, rely on NF EN ISO 10456 and NF EN 12524, then on Th-U rules or verifiable product data (DoP, Technical Approval) when a board is covered. To frame the method, also see the lambda calculation and sizing to achieve a target R.

Choosing the value according to use: solid timber, framing timber, derived panels (OSB, plywood, glulam)

Choose a value consistent with the product family and the density assumption. In framing, do not forget that the timber “short-circuits” the insulation. The wood fraction must be included in the U-value calculation.

Product Typical density (kg/m³) Design lambda (W/m.K)
Softwood solid timber (dry) 350 to 500 0.11 to 0.14
Hardwood solid timber (dry) 550 to 800 0.15 to 0.20
Framing timber (studs) 400 to 550 0.12 to 0.16
OSB 550 to 650 0.13
Plywood 500 to 650 0.15
Glulam 450 to 550 0.13 to 0.16

Site watchpoints: actual moisture content, service classes and consistency of assumptions

  • Measure or record the wood moisture content at installation. Wet wood conducts more, and the “dry” assumption becomes untenable.
  • Tie the structure to a service class (Eurocode 5) and align the hygrothermal assumption with the study.
  • Document the source of the value used (standard, Th-U, DoP, Technical Approval). That is what stands up in audit and inspection.

Framing thermal bridge: the most useful application in timber-frame walls and roofs

Why framing “short-circuits” the insulation: wood conducts several times more than mineral wool or bio-based insulation

In calculations, a stud or rafter is not “neutral”. With a typical wood lambda around 0.12 to 0.20 W/m·K (depending on species, density, moisture content and grain direction), the conductive path is 3 to 6 times more favorable than that of insulation at 0.032 to 0.045 W/m.K. As a result, part of the heat flow passes through the structural member and pulls average performance down.

Effect of the wood fraction: how studs/rafters degrade the average performance of the envelope

You do not average R-values. You average U-values. Take a “wood” surface fraction and an “insulation” fraction, then calculate U = f/Rwood + (1-f)/Rinsulation. The actual wood fraction (stud spacing, member sizes, doubling, openings) is therefore a site and design-data input, not a construction detail.

Practical examples: 145 mm wall and rafter roof, impact on overall R

Case Thickness (mm) λ (W/m·K) Local R (m²·K/W) Overall R with 15% wood (m²·K/W)
Wall, insulation 145 0.037 3.92 2.82
Wall, wood stud 145 0.13 1.12 2.82
Roof, insulation 200 0.035 5.71 4.09
Roof, wood rafter 200 0.13 1.54 4.09

To regain control, you have two robust levers. Reduce the fraction of wood that forms a thermal bridge and add a continuous cross layer. In walls as in pitched roofs, that is often where you secure the defensible R-value. To better frame the order of magnitude, also see thermal conductivity (λ), the key parameter for insulation materials.

How to limit the degradation: proven solutions (cross-insulation and continuous insulation)

Cross-insulation: principle, expected gains and mistakes to avoid on site

Cross-insulation adds a second layer perpendicular to the studs or rafters. It covers part of the wood, limits the impact of wood lambda on average wall performance, and makes the result more reliable both in calculation and in execution.

  • Non-contiguous cavities, rough cutting around services and boxes.
  • Compression of the cross layer by counter-battens, hangers or poorly detailed fixings.
  • Discontinuities in airtightness at wall-to-roof, wall-to-floor and edge junctions.

Continuous external insulation: when to choose it for façades and roofs

A continuous external insulation layer is the right choice when the wood fraction weighs heavily in the average U-value, or when you need to deal at once with reveals, slab edges and wall plates. On façades, ETICS simplifies continuity. On roofs, sarking, or insulation above the rafters, cuts thermal bridges if the weather barrier, air layer and vapour control remain consistent.

Optimizing the frame: spacing, member sizes, thermal breaks and details (junctions, floor ends, rafters)

Optimize the framing before adding centimeters. Adjust spacing, limit unnecessary doubling, and align structural members with the insulation layout. Thermal breaks and technical strips must remain compatible with structure, fire performance and systems covered by Technical Approval. Detail the design, and document the singular points at handover.

Key figures

0,10-0,20 W/m.K

Dry wood lambda

0,032-0,040 W/m.K

Common insulation lambda

x2-x3

Longitudinal grain

Frequently asked questions

Use tabulated values from normative documents or manufacturer technical data sheets, stating the reference condition (often 12% moisture content) and the grain direction. If no specific data is available, use an order of magnitude of 0.10-0.20 W/m.K for dry solid timber, then record your assumption in the calculation note.

Sources

  1. Règles Th-Bât 2020 — Annexe IV de l’arrêté du 4 août 2021 (méthode de calcul RE2020)

    Ministère de la Transition écologique (site RT-RE bâtiment), August 4, 2021

Share this article

Pierre-Louis Guhur

Pierre-Louis is CEO and co-founder of Argile. He holds a PhD in machine learning, written at Inria, and renovated a house with his own hands in 2017 before founding the company. On the blog he writes about what he implements in the software: the 3CL-DPE 2021 method, NF EN 12831 and building physics as a calculation engine has to handle them, assumption by assumption.

Further reading

ContractorsApril 29, 2026
Lambda of insulation materials: thermal conductivity λ, table and calculation

Thermal conductivity sets the thickness you have to install to reach a given resistance, and it is the one product figure that feeds straight into the energy assessment. It still has to be evidenced: without proof of the insulant’s resistance, the assessment method falls back on a default lambda that wipes out the performance of what you actually installed. Here are the orders of magnitude by family, the matching thickness, and what to write on the quote so the real lambda is the one that counts.

8 min read

ContractorsJuly 17, 2026
Concrete balcony thermal bridge: treat it or cut it

When a slab extends outside the heated envelope, heat escapes and your clients feel it immediately. In renovation, your real lever is deciding quickly between correcting it with continuous insulation or a clean structural break, depending on access, structure and finishes. With a clear method, you limit callbacks, secure the job site and gain performance without unnecessary complications.

5 min read

ContractorsJuly 10, 2026
Concrete, brick, concrete block: thermal conductivity compared

On a job site, the difference sometimes comes down to a few decimal places. Concrete, brick and concrete block don't have the same thermal conductivity, and that changes everything about insulation thickness, thermal bridge treatment and budget. As a tradesperson, you save time when you know what to expect from a wall before you even talk about wool, panels or render. Here we lay out the orders of magnitude simply, so you can decide quickly and accurately.

5 min read

Reveal your expertise

One demo, and you see your expertise proven.

Contact us