Blog/Instantaneous vs storage water heater: pros and cons
Contractors

June 3, 2026

5 min read

Updated August 31, 2026

Instantaneous or storage water heater: what actually decides

The decision turns neither on litres nor on the headline price: it turns on the load profile declared under Regulation (EU) No 814/2013 and on the power the incoming supply can actually deliver. An instantaneous electric unit able to hold a shower draws a current no domestic single-phase service will give you. Here are the two tables to take to the survey.

Contents

Between an instantaneous water heater and a storage one, what decides is not the volume but the pairing of declared load profile and genuinely available electrical power. Regulation (EU) No 814/2013 defines no profile in litres: its Annex III sets a reference energy Qref, 2.100 kWh for the S profile, 5.845 kWh for M and 11.655 kWh for L, and it is on that sequence that the appliance's efficiency is measured. On the power side, an instantaneous electric unit holding 12 l/min at a 25 K rise calls for close to 21 kW, that is 91 A at 230 V single phase, where a domestic service fuse tops out at 100 A for the whole dwelling. The arbitration therefore happens on the product fiche and at the consumer unit, never in the sales pitch.

The two figures that decide, and the ones that do not

The declared load profile, not a volume in litres

Annex III of Regulation (EU) No 814/2013 defines ten profiles, from 3XS to 4XL. Each is a time-stamped sequence of draw-offs, with a useful energy, a flow rate and a minimum temperature for every draw. The profile the manufacturer declares sets the water heating energy efficiency threshold the appliance has to meet: the two figures are inseparable on the product fiche. No article of the regulation ties a profile to a storage volume, and any table that does is a commercial construction. The ten profiles and their maximum flow rates are covered in the DHW load profiles.

Declared profile Qref (kWh) Minimum water heating efficiency
XXS 2.100 32 %
XS 2.100 32 %
S 2.100 32 %
M 5.845 36 %
L 11.655 37 %
XL 19.070 37 %

These thresholds are minimum placing-on-the-market values from Annex II of the regulation, not site targets. A heat pump water heater sits well above them, and it is that gap, quantified on the product fiche, that holds up against a cheaper direct electric cylinder.

The connection capacity, which rules out options before any calculation

The flow of an instantaneous unit follows directly from its power. Raising one litre of water by one kelvin takes 1.163 Wh, so one litre per minute per kelvin takes 69.8 W. The table below applies that relation, with the current drawn at 230 V single phase.

Power Flow at ΔT = 25 K Flow at ΔT = 35 K Current at 230 V single phase
3.5 kW 2.0 l/min 1.4 l/min 15 A
7 kW 4.0 l/min 2.9 l/min 30 A
12 kW 6.9 l/min 4.9 l/min 52 A
18 kW 10.3 l/min 7.4 l/min 78 A
21 kW 12.0 l/min 8.6 l/min 91 A
24 kW 13.8 l/min 9.8 l/min 104 A

France gives the sharpest illustration of the constraint: procedure Enedis-NMO-RAC_010E sets a ceiling of 12 kVA on an individual single-phase connection in a dwelling, with a 9 kVA step in collective supplies, and everything above goes three phase. The British picture is the same arithmetic against a 60, 80 or 100 A service fuse. An instantaneous electric shower heater is therefore a three-phase appliance, or one you do not fit. The same trade-off plays out on a combination appliance, where the declared profile rather than a litres-per-minute figure compares two products, as set out in the gas combi with micro-storage.

What the survey sheet has to carry

The survey decides the system, not the other way round. Four lines are enough, provided they are measured rather than declared.

  • Subscribed power read at the meter, type of supply, and a photo of the consumer unit showing the free ways.
  • Flow measured at the shower head and at the sink with a graduated bucket, not the flow printed on the box.
  • Water volume between generation and the furthest outlet, to know whether the 3 litre threshold is crossed.
  • Cold water temperature read at the tap nearest the meter, which sets the rise to be produced.

The instantaneous water heater: where it holds, where it does not

The calculation to run before it goes on a quote

Start from the most demanding outlet and from winter cold water, not from the annual average. On a main at 8 °C and a shower blended to 40 °C, the rise is 32 K, not the 25 K of the brochures. Run the table above with that figure, then set the resulting current against the actual space in the consumer unit. On a 400 V three-phase supply, a 21 kW unit draws 30 A per phase, which brings it back into range. That single line of arithmetic is what protects the quote.

The limits in multi-point use and in winter

An instantaneous unit stores nothing: the flow is shared between the open outlets and the temperature falls at constant flow. Two simultaneous draws on a unit sized for one do not give two comfortable half flows, they give two lukewarm trickles. Add the season: between summer cold water at 16 °C and winter cold water at 8 °C, the energy to supply rises by close to a third at equal flow. A unit that suits in October fails in February.

The cases where it remains the right answer

A single outlet a long way from the generator, a hand basin, a plant room sink, a let property in intermittent use: there the instantaneous unit avoids keeping a cylinder hot for nobody. On gas it also opens configurations a cylinder cannot fit, provided flue and combustion air are treated as a work item in their own right, with their own lines on the quote.

The storage water heater: what it buys, what it costs

Peak demand, which is the real reason to store

Storage does not buy comfort in general, it buys simultaneity. Two showers at once and a bath filled in twenty minutes are power demands only an already-hot volume absorbs. It is also the only arrangement compatible with slow generation, heat pump or solar, where the heating output is low and the volume is what holds the profile. The sizing method is set out in the DHW storage volume.

Standing losses, as they are actually declared

Do not repeat the orders of magnitude in circulation. For a hot water storage tank, Regulation (EU) No 814/2013 requires the standing loss to be declared in watts, and for a water heater the daily electricity or fuel consumption tied to the declared profile. Those values sit on the product fiche of the exact model, and only they are enforceable. A quote line promising a saving without citing the fiche of the model delivered binds nobody except the person who wrote it.

Reheat time, the forgotten sizing criterion

Adding litres costs in losses, in space and in price, while the real peak criterion is recharge speed. A 200 litre appliance that reheats in an hour covers a second peak that a slow-recharging 300 litre one will not. On a heat pump water heater, check the electric immersion backup and its switching logic before stepping up a profile: it is what carries the heavy days, not the compressor.

The duties and the evidence, whichever system you fit

The temperatures imposed by the French order of 23 June 1978

Article 36 of the French order of 23 June 1978 caps domestic hot water at 50 °C at outlets in rooms intended for washing and at 60 °C in other rooms. In parallel it requires at least 50 °C at every point of the distribution as soon as the volume between generation and the furthest outlet exceeds 3 litres. British practice lands in the same place through Approved Document G and the HSE guidance on legionella. Both are met together by a thermostatic mixing valve on the outlet, never by lowering the storage setpoint, which would move the subject onto the sanitary risk covered in the DHW sanitary safety devices.

What attracts support, and what does not

In France the energy savings certificate scheme funds the heat pump water heater through the BAR-TH-148 measure and the solar water heater through BAR-TH-101, while the direct electric cylinder and both instantaneous types, electric and gas, fall under no residential measure. In Great Britain the Boiler Upgrade Scheme covers space heating, so a stand-alone water heater draws nothing, and a cylinder only enters through an ECO4 package. That absence is not an oversight: presented as a whole-life cost gap rather than as red tape, it is a selling argument. The version that applies is the one in force at the commitment date, archived with the signed quote.

The lines that commit you, on the quote and at commissioning

Put the exact commercial reference on the quote, along with the declared load profile, the water heating energy efficiency and, for a cylinder, the storage volume. Those four figures come from the product fiche and carry across unchanged from a catalogue built on the verified technical characteristics of the ranges. At commissioning, record the setpoint read, the temperature at the least favourable outlet after blending, the thermostatic mixing valve setting and the pressure at the reducing valve, then date it and have it signed. Without that document, a dispute over comfort is settled against you, including under the structural cover on the pipework.

Key figures

2.100 kWh

Qref of the S profile

5.845 kWh

Qref of the M profile

12 kVA

French single-phase ceiling

Frequently asked questions

No, and this is the most widespread mistake. Annex III of Regulation (EU) No 814/2013 defines each profile by a time-stamped sequence of draw-offs and by a reference energy Qref in kWh, never by a volume. Sales tables of the kind « L profile equals 200 litres » have no regulatory basis at all. To talk litres with a client, divide Qref by the energy needed to raise one litre of cold water to the intended use temperature, and write the cold water figure you assumed on the calculation note.

Share this article

Pierre-Louis Guhur

Pierre-Louis is CEO and co-founder of Argile. He holds a PhD in machine learning, written at Inria, and renovated a house with his own hands in 2017 before founding the company. On the blog he writes about what he implements in the software: the 3CL-DPE 2021 method, NF EN 12831 and building physics as a calculation engine has to handle them, assumption by assumption.

Further reading

Catalogues

/

Argile catalogue

/

Air-to-water heat pump

Argile catalogue

Add a product

Article base

Central articles, shared across all your equipment

Careful, this article is shared

This article is used in 14 products; any change will apply everywhere.

Name / Reference

Brand

Purchase cost

Selling price

VAT

Unit

Used in

Liaison frigorifique 5 m

ATL-LF05

Atlantic

68,00 €

119,00 €

5,5 %

Unit

14 products

Ballon tampon 25 L

ATL-BT25

Atlantic

142,00 €

245,00 €

5,5 %

Unit

9 products

Câble d’alimentation 3G2,5

GEN-C3G25

3,10 €

5,80 €

5,5 %

Linear metre

37 products

Support antivibratile

GEN-SAV

24,00 €

42,00 €

5,5 %

Unit

22 products

Kit hydraulique 3 voies

ATL-KH3V-08

Atlantic

186,00 €

312,00 €

5,5 %

Unit

6 products

Vase d’expansion 12 L

GEN-VE12

31,00 €

58,00 €

5,5 %

Unit

41 products

Tube PER pré-gainé Ø16

GEN-PER16

2,40 €

4,60 €

5,5 %

Linear metre

28 products

Filtre magnétique

GEN-FM22

54,00 €

96,00 €

5,5 %

Unit

33 products

With argile

Your building price library, checked and kept up to date

Argile builds your price library from the catalogues of the brands you distribute: every product carries its price breakdown, equipment, labour and accessories, with technical specifications checked one by one and tariffs carried through at every range change.

ContractorsJuly 14, 2026
Sizing a solar water heater: collector area and storage volume

A solar water heater is not sized from the number of occupants: schemes ask for a declared tapping profile among M, L, XL and XXL, defined by Regulation (EU) 814/2013 and tied to a specific reference energy. Here is that table, the 2 m² collector floor, and how to check that the collector and volume pairing holds thermally before you price the job.

5 min read

ContractorsJune 21, 2026
Water heater service life: when to replace?

No regulation sets a service life for a water heater, and the durations in circulation carry no legal weight anywhere. What can be decided and quantified is the point at which keeping the unit costs more than replacing it. Three criteria settle it: the declared standing loss, the row the energy assessment already applies to the unit, and the compliance of the installation.

6 min read

Reveal your expertise

One demo, and you see your expertise proven.

Contact us