Blog/Insulating screed: choosing thickness and performance
Contractors

October 2, 2026

•

6 min read

•

Updated November 14, 2026

Insulation screed: work out the thickness for a target R-value, or lay a screed over insulation

The thickness of an insulation screed follows from the target thermal resistance and the lambda declared by the manufacturer: e = R × λ. In France, for insulating a ground floor over an unheated basement, crawl space or open passage, the CEE energy savings scheme's BAR-EN-103 sheet requires R ≥ 3 m²·K/W without counting existing insulation, which means 180 mm of mortar at a declared λ of 0.06 W/(m·K). Where the height is not there, the R-value comes from an insulation board under a floating screed, installed under NF DTU 52.10, and the screed only spreads the loads.

Contents

The thickness of an insulation screed is a calculation: e = R × λ, with e in metres, the target resistance R in m²·K/W and the manufacturer's declared lambda in W/(m·K). In France, for insulating a ground floor over an unheated basement, crawl space or open passage, the CEE sheet BAR-EN-103 published by the Ministry for the Ecological Transition requires R ≥ 3 m²·K/W, existing insulation not counted: with a mortar declared at λ = 0.06 W/(m·K), that is 180 mm. That is why the choice nearly always comes down to two options, a screed that insulates on its own or a floating screed over an insulation board.

Insulation screed, screed over insulation, levelling layer: what each one does

Three build-ups, three ways to justify them

Build-up What it does What justifies its thermal resistance
Insulation screed (mortar with insulating aggregate) Insulates and levels in a single layer Declared lambda and laid thickness, R = e/λ
Floating screed over insulation The screed spreads loads, the board provides the resistance Declared resistance of the board
Levelling layer Encases services and makes up levels None, unless the manufacturer declares a lambda

What counts on the quote

A thermal resistance is justified by a document, not by the type of product. On the quote and the invoice, show the laid thickness, the declared lambda and the resulting resistance, with brand and reference. Which lambda to use is covered in the article on the lambda value, and Argile's quote builder asks for the characteristic the CEE sheet requires before the quote is sent.

Working out the thickness of an insulation screed

The formula e = R × λ

The thickness needed is the target resistance multiplied by the lambda. The table applies the formula to three example lambdas, ranging from an insulation board to a lightweight mortar. They are not product values, so replace them with the declared lambda on your datasheet.

Declared lambda (W/(m·K)) For R = 1 m²·K/W (mm) For R = 2.1 m²·K/W (mm) For R = 3 m²·K/W (mm)
0.035 35 74 105
0.06 60 126 180
0.10 100 210 300

The calculation is set out in more detail in the article on working out thickness from lambda.

Low build-up: what the available height allows

Start from the height actually available between the substrate and the finished level set by the thresholds, take off the floor finish, adhesive and underlay, then turn the formula round: R = e/λ. At 50 mm and λ = 0.06 W/(m·K), the screed provides about 0.83 m²·K/W. If that falls short of the target, the insulation screed is a levelling layer that insulates a little, and the R-value has to come from a board.

Screed over insulation: the build-up when the R-value must be met

The NF DTU 52.10 framework

NF DTU 52.10 (June 2013) covers the installation of insulating underlays beneath floating screeds or slabs and beneath bedded tiling. That document, together with NF DTU 26.2 for the screed itself, sets the laying conditions for the board and the screed thickness above it. Over joists, check the load the screed adds first, as the article on lightweight screed over a timber floor shows.

With underfloor heating

With underfloor heating, the insulation goes under the pipes and the encasing screed above them. An insulation screed laid over the pipes adds resistance between the emitter and the room and reduces the output the floor can deliver: only use it in that position if the system allows for it. The drying and heat-up protocol is covered in the article on drying a screed over underfloor heating.

Incentives and regulations: what the screed has to prove

The BAR-EN-103 CEE sheet

Version A64.6 of the sheet, whose declaration form is updated from 1 July 2026, sets three conditions to check before you price an incentive:

  • Scope: a ground floor between a heated space and an unheated basement, a crawl space or an open passage. A slab on grade is not on that list.
  • Threshold: R ≥ 3 m²·K/W, without counting the resistance of existing insulation.
  • Proof: resistance assessed to NF EN 12664, NF EN 12667 or NF EN 12939 for a non-reflective insulant and, where insulants are layered, the overall resistance with the brand and reference of each.

The regulatory minimum in the order of 3 May 2007

Outside any incentive, article 3 of the order of 3 May 2007 sets the minimum resistance of a ground floor you insulate in an existing building, where it sits over an unheated space or the outside: 3 m²·K/W in zones H1 and H2 and in H3 above 800 m, 2.1 m²·K/W in H3 below 800 m. The 2.1 column of the table above shows the thickness that represents for each lambda.

Key figures

R ≥ 3 m²·K/W

Insulated ground floor, CEE sheet BAR-EN-103 (v. A64.6), existing insulation not counted

2.1 m²·K/W

Minimum resistance of an insulated ground floor in H3 below 800 m (order of 3 May 2007, art. 3)

e = R × λ

Insulation thickness in m, R in m²·K/W, λ in W/(m·K)

Frequently asked questions

Multiply the target resistance by the declared lambda: at λ = 0.06 W/(m·K), e = 3 × 0.06 = 0.18 m, or 180 mm; at λ = 0.10 W/(m·K), 300 mm. Use the declared lambda of the product actually laid, then compare with a floating screed over an insulation board, where the board provides the resistance and the screed spreads the loads.

Share this article

Louis Airy

Louis is COO of Argile. After four years in strategy consulting and close to two as chief of staff in home adaptation and reuse, he joined Argile in March 2024. In daily contact with certified renovation companies, he follows French energy saving certificates, renovation subsidies and reduced VAT, and revises the affected articles whenever a rate changes. What he writes is what he then checks against real quotes.

Further reading

Customers

/

Camille Martin

Details

Dwelling

Works plans

Quotes

Admin & finance

Quote no. D2026-0042

History

Analysis

Preview

Save

The property

Energy renovation

Information

4

The quote

5

Terms

Next step

The quote

No.

Description

Qty

Unit

Unit price excl.

Total excl.

VAT

Price incl.

1

Installing an air-to-water heat pump

Technical specifications of the heat pump (mandatory)

3 STILL TO FILL IN

Area heated by the heat pump (m²)

e.g. 120

Seasonal energy efficiency ηs (%)

e.g. 126

Controller class

I

II

III

IV

V

VI

VII

VIII

1.1

Installing an air-to-water heat pump

10 600,00 €

11 183,00 €

1.1.1

Air-to-water heat pump 14 kW

1,00

U

3600,00

3 600,00 €

5,5%

3798,00

B

I

U

Heat output +7 °C / +35 °C: 13.00 kW. Heat output -7 °C / +60 °C: 10.10 kW. Seasonal space heating efficiency (35 °C / 55 °C): 150 % / 117 %.

1.1.2

Heat pump fitting and commissioning

1,00

U

7000,00

7 000,00 €

5,5%

7385,00

Add a line

2

External wall insulation (EWI)

2.1

External wall insulation (EWI)

22 500,00 €

23 737,50 €

2.1.1

Polystyrene insulation, R of 3.7 m².K/W or above

120,00

M2

120,00

14 400,00 €

5,5%

15192,00

2.1.2

Insulation labour package

120,00

M2

75,00

9 000,00 €

5,5%

9495,00

Discount

-900,00 €

8 545,50 €

With argile

Flawless quotes, straight from the works plan

Equipment, labour and accessories come from the works plan, VAT applies line by line, grants are deducted from the amount due and the mandatory wording is already written: the quote goes out for signature without a proofread.

ContractorsMarch 26, 2026
Ventilation duct insulation in unheated lofts: thickness, fitting and condensation

In a loft at 5 °C, a bare ventilation duct condenses all winter: bathroom air at 22 °C and 85 % humidity turns to water from 19.4 °C. Which ducts to insulate in extract-only and MVHR systems, 25 or 50 mm, a duct buried in the loft insulation or laid on top, joints, slope and crushing: the rules that prevent the callback, and the method for insulating an existing run.

8 min read

ContractorsMarch 20, 2026
Roof windows: thermal performance and blackout options

A well-chosen roof window means less overheating in summer, less loss in winter, and a comfort you feel from the very first night. For you, as a tradesperson, it all comes down to two simple points to secure on site: the actual thermal performance of the whole unit and effective blackout options suited to how the room is used. By mastering these choices, you save time on installation, cut down on callbacks, and deliver a clean, durable result that's easy to explain to the client.

5 min read

Reveal your expertise

One demo, and you see your expertise proven.

Contact us