The thickness of an insulation screed is a calculation: e = R × λ, with e in metres, the target resistance R in m²·K/W and the manufacturer's declared lambda in W/(m·K). In France, for insulating a ground floor over an unheated basement, crawl space or open passage, the CEE sheet BAR-EN-103 published by the Ministry for the Ecological Transition requires R ≥ 3 m²·K/W, existing insulation not counted: with a mortar declared at λ = 0.06 W/(m·K), that is 180 mm. That is why the choice nearly always comes down to two options, a screed that insulates on its own or a floating screed over an insulation board.
Insulation screed, screed over insulation, levelling layer: what each one does
Three build-ups, three ways to justify them
| Build-up | What it does | What justifies its thermal resistance |
|---|---|---|
| Insulation screed (mortar with insulating aggregate) | Insulates and levels in a single layer | Declared lambda and laid thickness, R = e/λ |
| Floating screed over insulation | The screed spreads loads, the board provides the resistance | Declared resistance of the board |
| Levelling layer | Encases services and makes up levels | None, unless the manufacturer declares a lambda |
What counts on the quote
A thermal resistance is justified by a document, not by the type of product. On the quote and the invoice, show the laid thickness, the declared lambda and the resulting resistance, with brand and reference. Which lambda to use is covered in the article on the lambda value, and Argile's quote builder asks for the characteristic the CEE sheet requires before the quote is sent.
Working out the thickness of an insulation screed
The formula e = R × λ
The thickness needed is the target resistance multiplied by the lambda. The table applies the formula to three example lambdas, ranging from an insulation board to a lightweight mortar. They are not product values, so replace them with the declared lambda on your datasheet.
| Declared lambda (W/(m·K)) | For R = 1 m²·K/W (mm) | For R = 2.1 m²·K/W (mm) | For R = 3 m²·K/W (mm) |
|---|---|---|---|
| 0.035 | 35 | 74 | 105 |
| 0.06 | 60 | 126 | 180 |
| 0.10 | 100 | 210 | 300 |
The calculation is set out in more detail in the article on working out thickness from lambda.
Low build-up: what the available height allows
Start from the height actually available between the substrate and the finished level set by the thresholds, take off the floor finish, adhesive and underlay, then turn the formula round: R = e/λ. At 50 mm and λ = 0.06 W/(m·K), the screed provides about 0.83 m²·K/W. If that falls short of the target, the insulation screed is a levelling layer that insulates a little, and the R-value has to come from a board.
Screed over insulation: the build-up when the R-value must be met
The NF DTU 52.10 framework
NF DTU 52.10 (June 2013) covers the installation of insulating underlays beneath floating screeds or slabs and beneath bedded tiling. That document, together with NF DTU 26.2 for the screed itself, sets the laying conditions for the board and the screed thickness above it. Over joists, check the load the screed adds first, as the article on lightweight screed over a timber floor shows.
With underfloor heating
With underfloor heating, the insulation goes under the pipes and the encasing screed above them. An insulation screed laid over the pipes adds resistance between the emitter and the room and reduces the output the floor can deliver: only use it in that position if the system allows for it. The drying and heat-up protocol is covered in the article on drying a screed over underfloor heating.
Incentives and regulations: what the screed has to prove
The BAR-EN-103 CEE sheet
Version A64.6 of the sheet, whose declaration form is updated from 1 July 2026, sets three conditions to check before you price an incentive:
- Scope: a ground floor between a heated space and an unheated basement, a crawl space or an open passage. A slab on grade is not on that list.
- Threshold: R ≥ 3 m²·K/W, without counting the resistance of existing insulation.
- Proof: resistance assessed to NF EN 12664, NF EN 12667 or NF EN 12939 for a non-reflective insulant and, where insulants are layered, the overall resistance with the brand and reference of each.
The regulatory minimum in the order of 3 May 2007
Outside any incentive, article 3 of the order of 3 May 2007 sets the minimum resistance of a ground floor you insulate in an existing building, where it sits over an unheated space or the outside: 3 m²·K/W in zones H1 and H2 and in H3 above 800 m, 2.1 m²·K/W in H3 below 800 m. The 2.1 column of the table above shows the thickness that represents for each lambda.



