Blog/CO₂ sensor and ventilation: driving mechanical ventilation by air quality
Contractors

April 4, 2026

5 min read

Updated August 6, 2026

CO2 sensor: the regulatory thresholds, and what they do not cover

A single French text puts numbers on indoor CO2, and it does not target housing: the order of 27 December 2022, which frames the measurement in premises open to the public. It sets the thresholds, but it also sets what the instrument must be worth, and that part is what product sheets leave out. In a dwelling no CO2 threshold applies, the obligation is still a flow rate.

Contents

A single French text puts numbers on indoor CO2: the order of 27 December 2022, issued for the annual assessment of ventilation provision in the premises open to the public covered by decree no. 2022-1690. It keeps three classes, at most 800 ppm for satisfactory air renewal in occupied premises, 800 to 1,500 ppm, and above 1,500 ppm for insufficient renewal. It also sets what the instrument must be worth: non-dispersive infrared spectrometry or an equivalent technology, a range of at least 0 to 5,000 ppm, and a maximum uncertainty of ± (50 ppm + 5% of the reading). In a dwelling none of those thresholds applies: the obligation remains the extract flow rate of the order of 24 March 1982, and CO2 is only a commissioning tool.

Understanding CO₂ to fine-tune ventilation

Why the CO₂ level reflects occupancy and air renewal

CO2 is mainly produced by breathing. When people enter a room, the level rises. When the air is renewed, it drops back towards the outdoor value. It is an occupancy indicator, useful on site to check whether the ventilation and air inlets are bringing in enough fresh air, but it measures neither a flow rate nor compliance.

What the order of 27 December 2022 quantifies, and for whom

The text is short and entirely numerical. The right-hand column is the one that matters to you, because it separates what binds a housing job from what does not.

What the order sets Value What it governs
Instrument technology non-dispersive infrared absorption spectrometry or equivalent hardware
Minimum measuring range 0 to 5,000 ppm hardware
Measurement uncertainty ± (50 ppm + 5% of the reading) hardware
Duration of display monitoring at least two hours protocol
Measurement conditions heating season, occupancy between 0.5 and 1.5 times the design figure protocol
Instrument position 1 to 2 m above floor level, away from air inlets and outlets protocol
Satisfactory air renewal at most 800 ppm classification
Intermediate class 800 to 1,500 ppm inclusive classification
Insufficient air renewal above 1,500 ppm classification

This table does not apply to housing, and that is exactly what makes it useful in a client conversation: it gives you a public reference to point at, without ever letting the client believe a regulatory threshold applies at home. The protocol is as instructive as the thresholds, since it makes clear that a reading taken outside the heating season, in an empty room, or over ten minutes, means nothing.

CO₂ and humidity: what the sensor doesn't tell you, and what it helps you anticipate

A CO2 sensor measures neither humidity, nor VOCs, nor particulates. But a sustained rise usually signals heavy occupancy, and therefore more water vapour. If CO2 stays high after a shower or cooking, anticipate a risk of condensation or lingering odours. Adjust the flow rates and check the actual negative pressure room by room, instead of raising the thresholds.

Choosing the right CO₂ sensor to drive mechanical ventilation

NDIR, accuracy and drift: criteria the regulation already quantifies

To drive ventilation on air quality, take an NDIR sensor (non-dispersive infrared), the technology the order retains for regulatory measurement. Use that text's requirements as a purchasing grid even outside public premises: a range of at least 0 to 5,000 ppm, a stated uncertainty no worse than ± (50 ppm + 5% of the reading), and a declared measurement method. Also check the response time (T90) and drift handling, with a disable-able ABC function.

Location and installation: where to place the sensor for a reliable reading

For regulatory measurement the order requires the instrument to sit between 1 and 2 metres above floor level, away from air inlets and outlets. The same logic applies in a dwelling. Place the sensor in the breathing zone, away from extract points, windows and any heat source. Avoid corners and airflow paths. In a house, the living room and a bedroom are the most useful spots.

Power, communication and ventilation compatibility: points to check before buying

Check the power supply (often 230 V or 24 V) and the control output. Depending on the unit you will need a 0-10 V output, a relay, or a bus (Modbus, KNX). Confirm compatibility with your unit, the cable length, and the ability to set thresholds and a minimum flow rate so the system never drops below the regulatory floor. For more on on-site checks, see also measuring ventilation flow rate.

Setting up effective CO₂-based control on mechanical ventilation

Step-based control or modulation: which setting for which home

Two logics exist. With step control, the unit switches between low and high speed when CO2 crosses a threshold, which suits two-speed units. With modulation, the flow rate varies continuously, more interesting in a well-sealed house and with heat-recovery ventilation. In both cases the control works above the permanent flow rate, never below it.

Parameters to set: CO₂ thresholds, delays, minimum and maximum flow rates

Set a trigger threshold and a return threshold, keeping enough separation to avoid hunting. Add a delay to smooth the reading. The non-negotiable point is the minimum flow rate: it follows the table in the order of 24 March 1982, not a comfort figure. The maximum follows acoustics and what the ductwork takes without whistling.

Practical cases: humidity-controlled and self-regulating single-flow, heat-recovery ventilation

With humidity-controlled systems, CO2 acts as an occasional boost to high speed, fine modulation staying driven by humidity. With self-regulating systems it is the same pattern, without fine variation. With heat-recovery ventilation, modulation on CO2 works well in the living room and bedrooms, with bypass and balancing checked. For more on this type of setup, see also key installation points for heat-recovery ventilation.

Checking and troubleshooting: when ventilation doesn't respond to CO₂

Common symptoms: over-ventilation, under-ventilation, noise, discomfort

When CO2-based control goes wrong, the most visible sign is over-ventilation, with continuously high flow, noise and draughts, until the occupant switches the system off. Conversely, under-ventilation lets CO2 climb despite occupancy. In both cases the cause is more often a false reading than a bad setting, and that is where to start.

On-site checks: measurement, calibration, wiring, air inlets, ductwork leaks

Before touching the settings, check the measurement. A sensor that is poorly placed or poorly calibrated is enough to throw off the whole control loop.

  • Compare the reading with a second instrument, then measure in outdoor air to obtain a low reference point.
  • Check the location, between 1 and 2 m above floor level, away from the kitchen and away from supply air.
  • Check the power supply and wiring (0-10 V, dry contact, Modbus) and the correct input assignment.
  • Inspect air inlets, extract points, filters, and dampers. Nothing should be obstructed.
  • Track down ductwork leaks and disconnections. A parasitic air intake changes the flow rates.

Fine-tuning tips: balancing, filtering, settings to stabilise the control

Once the measurement is reliable, balance the flow rates to nominal and record them. Then set the regulatory minimum, a realistic maximum, and add a delay or measurement smoothing to avoid oscillations. A gradual, room-by-room adjustment stabilises the result without running the fan flat out. For more on how ventilation affects rest, see also comfort and sleep quality.

Client pitch and compliance in 2026: selling CO₂-driven ventilation

What you are actually selling, and what you are not

You are selling control that adapts the flow rate to occupancy above the regulatory floor. You are not selling compliance: that comes from the flow rates in the order of 24 March 1982, measured and recorded. Setting that boundary on the quote heads off the most common dispute on this measure, from the client who understood they were buying an air quality guarantee. That boundary is drawn in black and white in the costing: Argile describes each item line by line on the quote, with the mandatory wording already drafted.

Traceability and evidence: how to present CO₂ readings to the client

Give dated proof. A seven-day export, before and after commissioning, with the sensor reference, its position, and the date of its last outdoor-air check. Use the classes from the order of 27 December 2022 as a reading grid, while stating that they govern premises open to the public. Keep those records in the job file: that is what turns a setting into evidence. That evidence does not have to go back out as an attachment: with Argile, the client finds the project documents and the follow-up of the installation in a dedicated space.

Points of caution: maintenance, filters, responsibilities, limits of the control

Compliance rests on a baseline of permanent ventilation. Control adjusts around it, it does not replace the minimum flow rates. Plan for regular maintenance, filters, extract points and sensor checks, then set out in writing who is responsible for it. And remember the limit: CO2 speaks to air renewal, not to humidity, nor to VOCs or radon.

Key figures

800 ppm

Below this, air renewal is satisfactory in occupied premises

1,500 ppm

Above this, air renewal is insufficient

± (50 ppm + 5%)

Maximum measurement uncertainty required of the instrument

Frequently asked questions

The French order of 27 December 2022 sorts concentrations into three classes: at or below 800 ppm, which indicates satisfactory air renewal in occupied premises, between 800 and 1,500 ppm inclusive, and above 1,500 ppm, which indicates insufficient air renewal. Those values frame the annual assessment of ventilation provision in the premises open to the public covered by decree no. 2022-1690, not housing. In a dwelling no CO2 threshold governs, and the obligation remains an extract flow rate set by the order of 24 March 1982.

Share this article

Louis Meneteau

Louis is CPO of Argile. An engineer by training, he spent four years validating calculation software in systems engineering, then three years in software product. He turns the installer's daily reality into product workflows: technical survey, sizing, quotes and subsidy files. His articles describe field gestures rather than principles, because he watches them on site before specifying them.

Further reading

Customers

/

Camille Martin

Details

Dwelling

Works plans

Quotes

Admin & finance

Quote no. D2026-0042

History

Analysis

Preview

Save

The property

Energy renovation

Information

4

The quote

5

Terms

Next step

The quote

No.

Description

Qty

Unit

Unit price excl.

Total excl.

VAT

Price incl.

1

Installing an air-to-water heat pump

Technical specifications of the heat pump (mandatory)

3 STILL TO FILL IN

Area heated by the heat pump (m²)

e.g. 120

Seasonal energy efficiency ηs (%)

e.g. 126

Controller class

I

II

III

IV

V

VI

VII

VIII

1.1

Installing an air-to-water heat pump

10 600,00 €

11 183,00 €

1.1.1

Air-to-water heat pump 14 kW

1,00

U

3600,00

3 600,00 €

5,5%

3798,00

B

I

U

Heat output +7 °C / +35 °C: 13.00 kW. Heat output -7 °C / +60 °C: 10.10 kW. Seasonal space heating efficiency (35 °C / 55 °C): 150 % / 117 %.

1.1.2

Heat pump fitting and commissioning

1,00

U

7000,00

7 000,00 €

5,5%

7385,00

Add a line

2

External wall insulation (EWI)

2.1

External wall insulation (EWI)

22 500,00 €

23 737,50 €

2.1.1

Polystyrene insulation, R of 3.7 m².K/W or above

120,00

M2

120,00

14 400,00 €

5,5%

15192,00

2.1.2

Insulation labour package

120,00

M2

75,00

9 000,00 €

5,5%

9495,00

Discount

-900,00 €

8 545,50 €

With argile

Flawless quotes, straight from the works plan

Equipment, labour and accessories come from the works plan, VAT applies line by line, grants are deducted from the amount due and the mandatory wording is already written: the quote goes out for signature without a proofread.

With argile

Give your customers a space that follows their project from A to Z

The home, consumption, documents, the job and the team's contact details: every customer gets a dedicated space that keeps them informed without having to call.

ContractorsMay 24, 2026
Self-regulating vs humidity-controlled single-flow mechanical ventilation: which one to choose?

The choice between self-regulating and humidity-controlled ventilation does not come down to a fitting preference but to a single figure: the floor flow rate you are allowed to hold. The French order of 24 March 1982 sets two different floors depending on whether the system modulates automatically, and the gap between them is close to a factor of three. Everything else, comfort, acoustics, consumption, follows from that.

5 min read

Reveal your expertise

One demo, and you see your expertise proven.

Contact us