Make a clear distinction between LHV, HHV and units before calculating combustion
Methane LHV vs HHV: what you are actually measuring (and why the trap is common)
The LHV assumes that the water vapour formed during combustion remains in the gaseous state. The HHV also recovers the heat of condensation. In burner calculations, switching from one basis to the other shifts the balance by about 10%. Methane LHV is therefore a consistent basis if your efficiencies and gas flow rates are expressed on an LHV basis.
kWh, MJ, Nm³, meter m³ and kg: what each unit is for on site
kWh and MJ are energies. Nm³ is a volume referred to reference conditions (standardised temperature and pressure), which is essential for comparing gases. Meter m³ is the volume measured in service, then corrected. kg is used as soon as you move to a mass basis (LPG, heating oil, biomass) or for material balances.
When to use LHV in sizing (burner, boiler, gas heat pump) and when the bill is usually in HHV
For sizing (burner, boiler, gas heat pump), keep to one basis only. Use the LHV for useful thermal output and “on LHV” efficiencies. The gas bill, on the other hand, is most often in HHV kWh, after application of a conversion factor linked to the delivery point. Convert before comparing consumption with site calculations.
Reference LHV value for pure methane (CH₄)
Pure methane LHV in kWh/Nm³ (normal conditions must be specified): order of magnitude ≈ 9.94 kWh/Nm³
For your combustion calculations, use the methane LHV of pure methane at 9.94 kWh/Nm³, provided that you fix the normal conditions. In practice, 1 Nm³ corresponds to dry gas at 0 °C and 1.01325 bar (volumetric reference).
| Reference temperature (°C) | Reference pressure (bar abs) | LHV (kWh/Nm³) |
|---|---|---|
| 0 | 1.01325 | 9.94 |
Pure methane LHV in kWh/kg: order of magnitude ≈ 13.9 kWh/kg
On a mass basis, CH₄ LHV is close to 13.9 kWh/kg. This is the most robust value if your calculation starts from a mass flow rate or energy per tonne.
| LHV (MJ/kg) | LHV (kWh/kg) |
|---|---|
| 50.0 | 13.9 |
How to convert from kWh/kg to kWh/Nm³ (CH₄ density at normal conditions) without making a mistake
The conversion uses the density at normal conditions, not a density at 15 °C or 20 °C. At 0 °C and 1.01325 bar, use ρ(CH₄) ≈ 0.717 kg/Nm³. Apply LHVvol = LHVmass × ρ.
| Density ρ (kg/Nm³) | Formula | Example (kWh/Nm³) |
|---|---|---|
| 0.717 | 13.9 × ρ | 9.95 |
Why distributed natural gas is not pure methane: variations and conversion factor
Natural gas composition: how the mix (CH₄, C₂H₆, N₂…) affects calorific value
Methane LHV describes pure CH₄. But distributed natural gas is a mixture. It is mostly methane, but it also contains heavier hydrocarbons (ethane, propane), inert gases (nitrogen) and traces of CO₂. This mix changes the calorific value and therefore the energy actually available for the same gas quantity.
Supply zones, H gas/B gas and local variations: what changes from one delivery point to another
At the delivery-point level, quality depends on the supply zone. In France, a distinction has historically been made between H gas (richer gas) and B gas (leaner gas). Changes in source, interconnections and biomethane injection can create local differences. Direct consequence: sizing based on an “average” value can drift.
The distributor’s conversion factor: how billed kWh are calculated from m³ (and why this avoids “raw” m³)
Do not think in “raw” m³. The bill converts the measured volume into energy using a conversion factor. It incorporates the local gas characterisation (higher heating value retained for the delivery point) and a correction linked to measurement conditions (pressure, temperature, altitude). You then start from billed kWh, which is more robust for comparisons, combustion calculations or energy balance justification.
Practical conversions for your 2026 calculations: method and quick checks
Conversion formulas: meter m³ → billed kWh → LHV estimate (without mixing up LHV/HHV)
For your gas files, start from the meter reading, then stay aligned with the bill. Single reference only. The m³ → kWh conversion is done using the delivery-point conversion factor (it includes gas quality and corrections). To work back to an LHV energy value, then correct by the HHV/LHV ratio, not the other way around.
- billed kWh = meter m³ × conversion factor (kWh/m³)
- estimated LHV kWh ≈ billed kWh ÷ (HHV/LHV)
- Nm³ required = LHV kWh ÷ methane LHV value (kWh/Nm³)
Temperature/pressure reference conditions: without them, a volumetric value has no meaning (Nm³ must be specified)
A value in kWh/Nm³ assumes a volume referred to normal conditions. State the reference clearly, typically 0 °C and 1.01325 bar. A cubic metre measured by the meter is not an Nm³. Without normalisation (T, P), volumetric LHV comparisons are not usable.
Field checks: spotting an inconsistency in 30 seconds (typical HHV/LHV ratios)
Quick check. If your kWh/m³ is well outside the usual local range, recheck the factor, period and index. To avoid an HHV vs LHV error, also check typical HHV/LHV ratios.
| Fuel | Typical HHV/LHV |
|---|---|
| Methane | 1.11 |
| Propane | 1.09 |
| Butane | 1.09 |
Comparative table of LHVs for converting your fuels (tradesperson → site)
LHV table: methane (reference), propane, butane, heating oil, wood (with the most useful unit: kg, litre, stere)
Calculation basis. LHV at standard conditions for volumetric values. For methane LHV, work in Nm³ (dry gas, 0 °C, 1.01325 bar) or in kg depending on your model.
| Fuel | Unit | LHV (kWh/unit) | Site reference |
|---|---|---|---|
| Methane (pure) | Nm³ | 9.95 | Lab value, not network gas |
| Methane (pure) | kg | 13.9 | Useful for combustion/mass flow |
| Propane | kg | 12.9 | Pressurised LPG |
| Butane | kg | 12.7 | Pressurised LPG |
| Heating oil | L | 10.0 | Varies with density |
| Firewood (≈20% H2O) | stere | 1,600 | Highly dependent on moisture/species |
Conversion examples: turning a 10,000 kWh requirement into a fuel quantity (propane/heating oil/wood)
| Fuel | Quantity for 10,000 kWh |
|---|---|
| Propane | ≈ 775 kg |
| Heating oil | ≈ 1,000 L |
| Firewood (≈20% H2O) | ≈ 6.3 stere |
Key points by fuel: wood moisture, heating oil density, storage and safety for LPG
- Wood. Measure moisture on site. At 30% H2O, useful LHV drops sharply and sizing drifts.
- Heating oil. If you convert to kg, apply the actual density (often 0.83 to 0.86 kg/L depending on batch and temperature).
- LPG (propane/butane). Check storage volume, regulatory clearances, ventilation and hazard zones. One oversight leads to non-compliance.