Blog/Dew Point Calculation to Prevent Condensation on Site
Contractors

October 10, 2026

•

6 min read

Dew Point Calculation to Prevent Condensation: 3 Site Cases You Must Not Confuse (2026)

The dew point of ambient air is calculated from two site measurements, temperature and relative humidity, then read on a psychrometric chart or via an approximate formula. At 20 °C and 60% RH, air reaches saturation at around 12 °C: any colder surface (wall, chilled-water pipework, cooled floor) becomes a risk zone, a value derived from the Magnus-Tetens approximation. For condensation within a wall, verification is done by comparing vapor pressures and temperatures through the assembly in accordance with NF EN ISO 13788, with a vapor barrier on the warm side where required. Flue gas dew point, by contrast, is handled separately: it depends on the fuel and excess air and is addressed through the design rules for flue ducts in NF EN 13384.

Contents

Identify the right “dew point calculation” for your job straight away

Ambient air dew point: risk of condensation on cold surfaces

On site, the dew point calculation links air temperature and relative humidity. From this, you derive the surface temperature you must not go below to avoid fogging on cold walls, chilled-water pipework, or cooled floors. This is the value that sets the lower temperature limit for cooling supply water.

Condensation within a wall: check through the thickness, not just at the surface

Here, we are no longer talking about the surface. You check the interstitial risk by comparing vapor pressures through the layers, using a Glaser-type approach. The vapor barrier is installed on the warm side, and its continuity is tracked on drawings and site photos.

Flue gas dew point: condensation in the boiler and flue

Last case: flue gases. Their dew point depends on the fuel and excess air. It determines the choice of a condensing boiler, condensate drainage, and the durability of the flue (material, airtightness, slope, corrosion resistance). For sizing and installation constraints, also see the specifics of a concentric flue duct.

Ambient air dew point calculation: anticipate condensation on walls, pipework and cooling systems

Record temperature and relative humidity: what this changes in the result

For a reliable reading and a usable dew point calculation, measure dry-bulb temperature and relative humidity as close as possible to the risk zone, away from direct radiation and supply air. An error of 1 °C or 5% RH is enough to shift the dew point and change your decision on insulation, a setpoint, or resealing. Record the location, time and instrument.

Reading from a psychrometric chart and using an approximate formula: methods you can use on site

On a psychrometric chart, start from the dry-bulb temperature, follow the relative humidity curve, then read the dew point on the saturation curve. For a quick calculation, the Magnus formula works well. Td = (b·γ)/(a-γ), with γ = ln(RH/100) + a·T/(b+T), a = 17.62 and b = 243.12.

Using the dew point calculation: cold wall, chilled water, cooled floor and minimum supply temperature

Simple rule. Keep a 2 °C margin between the surface temperature, or the cooling supply temperature, and Td. That is what prevents condensation on cold walls, chilled-water pipework and cooled floors. To better understand what happens at the level of a cold wall, and its effects on comfort, explore the notion of a cold wall in more depth.

Air temperature (°C) Relative humidity (%) Dew point Td (°C) Recommended minimum surface or supply temp. (°C)
26 50 14.8 16.8
26 60 17.6 19.6
28 70 22.0 24.0

Condensation within a wall assembly: check the risk with vapor pressures

Principle of vapor pressure comparison: where and why condensation occurs

The approach is based on diffusion. At each layer interface, you track the partial pressure of water vapor and compare it with the saturated vapor pressure at the local temperature. If the partial pressure curve exceeds the saturation curve, interstitial condensation occurs. The dew point calculation is used here to set the indoor conditions, then unfold the temperature and vapor profile through the assembly.

Role of the vapor barrier on the warm side: continuity, junctions and common mistakes

A vapor barrier on the warm side is only effective if it is continuous. On site, performance is decided at overlaps, penetrations (service ducts, boxes), junctions with internal partitions and the window-to-wall connection. Classic mistake: confusing a variable-permeability vapor retarder with a vapor barrier, or installing an interrupted membrane behind a perforated lining.

Renovation case studies: internal insulation, cold zones and moisture transfer

With internal insulation, the masonry becomes colder in winter. The cold zones (floor junctions, reveals, cross walls) weaken the assessment if they are not modeled. Set the assumptions (temperature, RH, critical month), address thermal bridges, and document the choice of membrane and junction details to secure the trade during inspection.

Flue gas dew point calculation: avoid condensation damage on the appliance and flue

Why flue gases condense: return temperature, heat exchanger and efficiency

Flue gases condense when a surface in the appliance, often the heat exchanger, drops below their dew point. The on-site trigger is an excessively low return temperature or an overly aggressive heat transfer. In a condensing boiler, this is intentional to recover latent heat. Outside a design intended for condensation, condensates attack metals, load deposits and quickly degrade airtightness.

Dependence on fuel and excess air: what changes the flue gas dew point

The dew point calculation for flue gases depends on the water vapor content, CO2, and the excess air that dilutes the combustion products. Also watch, depending on the fuel, for acid condensation.

Fuel Flue gas dew point, order of magnitude (°C) Sensitivity
Natural gas 50 to 60 Excess air, return temp
Oil 40 to 55 Sulfur, excess air
Biomass 45 to 65 Fuel moisture

Choosing the flue and materials: airtightness, condensate resistance and drainage slopes

If condensation is possible, use a Class W flue with corrosion resistance and proper condensate management. Provide slope, collection, trap and access for inspection. During renovation, check the liner, joints and material compatibility (suitable stainless steel, PP, ceramic) with the nature of the condensates; see also the DTU points and best practices for lining and flue compliance.

Avoid site mistakes: do not mix up the values and size for the worst-case scenario (2026)

Do not confuse ambient air dew point and flue gas dew point: order of magnitude and impact

Ambient air dew point is used to prevent condensation on a cold surface (chilled-water circuit, cooled floor). Flue gas dew point is used to define the condensing regime of a generator and the requirements for the flue. Keep the order of magnitude in mind.

Case Typical dew point (°C) Site impact
Indoor air 20 °C, 50 to 60% RH 9 to 12 Lower limit in cooling
Natural gas boiler flue gases (H2O) 55 Choice of condensing/non-condensing unit

Anti-condensation insulation: size it for the most humid conditions of the year

For insulation, size for the worst case. High RH, minimum surface temperature, and vapor barrier continuity. Aim for a 2 K margin between calculated surface temperature and dew point.

  • Calculation inputs. Air temp, RH, fluid temp, insulation λ, thickness, vapor barrier Sd.
  • Critical points. Flanges, supports, valves, penetrations, uninsulated areas.

Simple checks to put in place: measurements, safety margins and operating adjustments

During commissioning, impose a minimum cooling supply temperature via the control system, adjusted using the control strategy, based on air temperature and RH measurements. Record the readings, and lock in setpoints during operation.

  • Measure. Thermo-hygrometer, surface temperature, fluid temperature, and seasonal maximum humidity.
  • Adjust. RH alarm, cooling shutdown, gradual restart after a humidity peak.

Key figures

2 °C

Td safety margin

17,62

Magnus formula threshold

22,0 °C

Max dew point

Frequently asked questions

Use a calibrated thermo-hygrometer, ideally with a certificate or at least an annual verification, with a target accuracy of ±0.5 °C and ±3% RH. Measure in the shade, away from supply air and radiation, then record the time, location and instrument reference so your decisions can be traced.

Share this article

Louis Meneteau

Louis is CPO of Argile. An engineer by training, he spent four years validating calculation software in systems engineering, then three years in software product. He turns the installer's daily reality into product workflows: technical survey, sizing, quotes and subsidy files. His articles describe field gestures rather than principles, because he watches them on site before specifying them.

Further reading

ContractorsOctober 4, 2026
Solar panel production calculation to estimate output

To estimate photovoltaic output, start from the formula kWh/year = installed capacity (kWp) × plane-of-array irradiation (kWh/m²/year) × PR, with a PR typically kept between 0.75 and 0.85 on a standard roof (cables, temperature, inverter, mismatch, soiling). This range is what is used in practice; ADEME’s guide “How to choose your heat pump?” is not the right reference here, but ADEME commonly presents PR around 0.8 in its photovoltaic materials, and it provides a solid basis for a quote-level estimate before module layout. You then refine it using orientation and tilt via the “tilted-plane” irradiation (not horizontal), because for the same kWp the annual ratio varies significantly by area, as shown by public solar mapping tools (such as PVGIS) used in pre-studies.

5 min read

ContractorsOctober 4, 2026
Insulating sloped roof rafters: the go-to method on site

On sloped roofs, aim for at least a thermal resistance of R ≥ 6 m².K/W to meet the requirements of CEE sheet BAR-EN-102 (loft insulation), then choose the method that lets you reach that R without eating into finished height or blocking ventilation. Between rafters, you quickly run up against the available depth, whereas with two cross-layers below the rafters you gain R at the cost of a few centimetres of ceiling height. With sarking, you preserve internal volume and handle singular points better, provided the roofing is removed. If the underlay is not HPV, keep a ventilated air gap beneath the roof covering and maintain continuity of the vapour control layer with airtight sealing at junctions and penetrations to avoid condensation.

6 min read

ContractorsJuly 22, 2026
Refrigerant charge: calculation and precautions

The refrigerant charge commands two things: how the machine performs and what you owe the regulator. The second is not read in kilos but in tonnes of CO2 equivalent, and the conversion is one multiplication by the GWP. Here is the conversion table by refrigerant, the leak check interval table, and what gets logged after every job.

5 min read

Reveal your expertise

One demo, and you see your expertise proven.

Contact us